| Plan Review Notes For Permit 04110228 |
| Permit Number |
04110228 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-08-03 00:00:00 | PLAN DENIED | | | 1) EXHAUST DUCT AND DRYER DUCT TO BE | | | SUMITED AS ALTERNATIVE METERIALS AND | | | METHODS SECTION 301.4.2 FBC(M) | | | 2) PAGE M.4 REFER TO SECTION 501.3 | | | OUTDOOR DISCHARGE.CONDENSOR DISCHARGING | | | ON PATIOS. | | | 3) PAGE M.5 LOBBY PROVIDE FIRE | | | DAMPERS.PLEASE REFER TO SECTION 607.4 | | | FLOOR PENETRATION. | | | 4) PAGE M.5 DRYER VENT MUST BE 10FT. | | | FROM SF#1 | | | 5) REFER TO SECTION 504.6 CLOTHES DRYER | | | DUCT | | | 6) PLEASE PROVIDE INFORMATION ON RTU#2&3 | | | HOW ARE THEY GETTING FRESH AIR. | | | 7) PLEASE REFER TO SECTION 307.2.3 | | | AUXILIARY DRAIN PANS. | | | 8) COULD NOT FIND ANCERS FOR LAST REVIEW | | | | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|