2005-08-03 00:00:00PLAN DENIED
 1) EXHAUST DUCT AND DRYER DUCT TO BE
 SUMITED AS ALTERNATIVE METERIALS AND
 METHODS SECTION 301.4.2 FBC(M)
 2) PAGE M.4 REFER TO SECTION 501.3
 OUTDOOR DISCHARGE.CONDENSOR DISCHARGING
 ON PATIOS.
 3) PAGE M.5 LOBBY PROVIDE FIRE
 DAMPERS.PLEASE REFER TO SECTION 607.4
 FLOOR PENETRATION.
 4) PAGE M.5 DRYER VENT MUST BE 10FT.
 FROM SF#1
 5) REFER TO SECTION 504.6 CLOTHES DRYER
 DUCT
 6) PLEASE PROVIDE INFORMATION ON RTU#2&3
 HOW ARE THEY GETTING FRESH AIR.
 7) PLEASE REFER TO SECTION 307.2.3
 AUXILIARY DRAIN PANS.
 8) COULD NOT FIND ANCERS FOR LAST REVIEW
  
 PLAN REVIEW BY HAROLD MOSER 561-805-6732