Plan Review Notes
Plan Review Notes For Permit 04110228
Permit Number 04110228
Review Stop P
Sequence Number 3
Notes
Date Text
2005-07-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FHA-98 DESIGN MANUAL
  
 A) COMMENTS FROM PREVIOUS REVIEW THAT
 HAVE NOT BEEN ADDRESSED, OR NOT
 ADDRESSED PROPERLY. THE COMMENT NUMBER
 WILL REMAIN THE SAME AS THE FIRST
 REVIEW:
 1) SHTS I-1, & I-2 FIRM LICENSE NUMBER
 REQUIRED ON THE TITLE BLOCK, SIGNATURE
 REQUIRED, AND PRINTED NAME REQUIRED. FAC
 61G1-16.004(2)(5)(6), 61G1-16.003 AND FS
 481.219. - SUBMIT PROOF OF A LEGAL
 SIGNATURE IN THE FORM OF A DRIVERS
 LICENSE, VOTERS REG. CARD ECT., AND
 SUBMIT A SIGNED/SEALED/DATED NOTORIZED
 LETTER WITH YOUR LEGAL SIGNATURE FOR OUR
 FILES. (TITLE BLOCK REQD ON LETTER). -
 THIS COMMENT HAS NOT BEEN ADDRESSED, NOR
 HAS A RESPONSE BEEN NOTED.
 3) SHTS A-11 & A-12 SHT INDEX STATES
 PARTIAL 3RD-7TH FLOOR PLAN 1, BUT NOTE 5
 STATES 3RD-5TH FLOOR PLAN. PLEASE
 CLARIFY. SECTION 104.2.1. - THIS HAS NOT
 BEEN ADDRESSED, NOR HAS A RESPONSE BEEN
 NOTED.
 4) SHTS A-9 & A-15 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS
 PER SECTIONS 1106, & 1107 AND ALL
 SUBSECTIONS. SHOW SF OF EACH AREA WITH
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS AND ROOF AREA FROM ABOVE THAT
 DRAINS TO THE ROOF FROM ABOVE ADDED TO
 THE SF IN THE CALCULATIONS. SHOW THE
 LOCATION OF ALL PRIMARY AND SECONDARY
 ROOF DRAINS AND THE SCUPPERS. ALSO SEE
 SHTS A-17 & A-18. THIS APPLIES TO THE
 ROOF DECK AREAS AS WELL. THIS HAS NOT
 BEEN ADDRESSED, NOR HAS A RESPONSE BEEN
 NOTED.
 5) SHTS A-9 & A-15 SHOW THE LOCATION AND
 SIZE OF ALL SECONDARY ROOF DRAINS &
 SCUPPERS. SECTION 104.2.1. - THIS HAS
 NOT BEEN ADDRESSED, NOR HAS A RESPONSE
 BEEN NOTED.
 6) SHTS A-15 & A-16 SUBMIT CALCULATIONS
 FOR MINIMUM FACILITIES PER TABLES 1003.1
 AND 403.1. SHOW THE SF OF EACH COMMON
 AREA, AND THE TOTAL COMMON AREA IN THE
 CALCULATIONS. - THIS HAS NOT BEEN
 ADDRESSED, NOR HAS A RESPONSE BEEN
 NOTED.
 7) ARCHITECTURAL SHEETS, THE DATE
 PREPARED AND THE PRINTED NAME OF THE
 PERSON RESPONSIBLE FOR THE DOCUMENT ARE
 REQUIRED PER FAC 61G1-16.004(4)(6) AND
 FS 481.2055. - THE PRINTED NAME OF THE
 PERSON HAS NOT BEEN ADDED TO THE TITLE
 BLOCK. NO RESPONSE NOTED.
 8) SHTS A-30, A-31, & A-32 INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT
 OR BATHROOM AS REQUIRED ON PAGE 7.35 OF
 THE FHA DESIGN MANUAL. - SHT A-30 ONLY
 UNIT B-2 IS INDICATED. - SHT A-32 UNITS
 E-4, E-4L, & E-6 ARE NOT INDICATED. - IF
 SPECIFICATION "A" ALL BATHROOMS AND ALL
 FIXTURES SHALL COMPLY. SEE PAGE 7.34.
 9) SHTS A-30, A-31, & A-32 SHOW THE SIZE
 OF THE OPENINGS FOR ALL COVERED WATER
 CLOSETS. MINIMUM 33" REQUIRED. SEE PAGES
 6.5 AND 6.7 OF THE FHA DESIGN MANUAL. -
 THE 18" FROM THE WALL TO THE CENTERLINE
 OF THE W/C IS AN ABSOLUTE MEASURMENT.
 SEE FIGS PAGE 6.3 & 6.5. - NO RESPONSE
 NOTED AND NOT ALL OPENINGS ARE INDICATED
 AND NOT ALL OPENINGS MEET THE
 REQUIREMENTS OF FHA DESIGN MANUAL.
 10) SHT A-33 MENS AND WOMENS RESTROOMS,
 SHOW CLEAR FLOOR SPACE FOR EACH
 ACCESSIBLE FIXTURE. SECTIONS 11-4.16.2,
 11-4.19.3, & 11-4.22.3. THE TURNING AREA
 SHALL BE SHOWN IN THE TOILET ROOM, NOT
 IN THE ACCESSIBLE STALL. ALSO SHOW WATER
 CLOSET HEIGHT PER 11-4.16.3. GRAB BAR
 HEIGHT MAX. 36", SHOWN AS 48" ON DETAIL
 BEHIND W/C. SHOW FLUSH CONTROL 11-4.16.5
 SHOW URINAL HEIGHT 11-4.18.2. THE
 CENTERLINE OF THE W/C SHALL BE 18" TO
 THE WALL FROM THE CENTERLINE OF THE
 FIXTURE, NOT 20" AS SHOWN. (SEE FIG. 28)
 FOR THE LAVS SHOW KNEE CLEARANCE
 11-4.19.2, FOR THE SHOWER SHOW CONTROLS
 11-4.21.5, SHOWER UNIT 11-4.21.6, AND
 CURB HEIGHT 11-4.21.8. - BACK AND SIDE
 GRAB BARS SHALL BE AT THE SAME HEIGHT.
 SEE FIG. 29. W/C HEIGHT 17" TO 19". 20"
 DIMENSION SHOWN ON SOME W/C'S.
 11) NOT USED
 12) SHT A-33 DETAIL #1 IN BOTH THE MEN'S
 AND WOMEN'S RESTROOMS. THE DOUBLE LAVS
 TO BE 34" IN HEIGHT AND HAVE A CLEARANCE
 OF 29". SEE FIG 31. SECTION 11-4.19.2. -
 NO RESPONSE NOTED. NOT ADDRESSED.
 13) A DRINKING FOUNTAIN IS REQUIRED IN
 THE COMMON AREA. TABLE 403.1. SUBMIT A
 DETAIL COMPLYING WITH SECTIONS 11-4.15
 AND ALL SUBSECTIONS & 11-4.1.3(10)(A)
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING. - NO DETAIL FOUND, NOR WAS A
 RESPONSE NOTED.
 14) SHT A-36 SHOW HEIGHT AND WIDTH OF
 SCUPPER OPENINGS ON THE DETAIL. SECTIONS
 104.2.1 AND 1107.3. NO DETAIL FOUND, NOR
 WAS A RESPONSE NOTED.
 15) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME. INITIALS ARE NOT APPROVED PER
 FBPE RULING. SUBMIT AN EXAMPLE OF THE
 ENGINEERS LEGAL SIGNATURE BY WAY OF
 DRIVERS LICENSE, VOTERS REG. ECT., AND A
 SIGNED, SEALED, DATED, NOTORIZED LETTER
 WITH TITLE BLOCK INDICATING YOUR LEGAL
 SIGNATURE FOR OUR FILES.
 61G15-23.002(1)(2) AND FS 471.025. THIS
 IS FOR ALL ENGINEERED SHEETS. - LETTER
 WAS NOT SIGNED, SEALED, DATED, NOR DID
 THE LETTER HAVE A TITLE BLOCK ON IT.
 18) SUBMIT MANUF. SPECIFICATION SHEETS
 FOR THE STORM WATER SUMP PUMPS. PUMP
 INFORMATION SHALL SHOW THE LISTING.
 SECTION 303.4.(SUBMITTALS NOT FOUND). -
 STILL NO RESPONSE TO THIS COMMENT.
 19) SHTS P-3 & P-4 PIPE SIZING NOT
 CORRECT FOR EMERGENCY ROOF DRAIN PIPING,
 (SECONDARY ROOF DRAINS). SEE TABLES
 1106.2 & 1106.3. STAIRWAY #2 NOT ADDED
 TO THE SYSTEM. DOUBLE CHECK ALL PIPE
 SIZES AND SHOW ADDITION OF ALL SF AS
 THEY ACCUMULATE IN THE STORM BLDG.
 DRAIN. SECTION 104.2.1. - THERE ARE
 STILL SOME PIPE SIZES AND SF NOT SHOWN
 ON THESE SHEETS.
 27) SHT P-5 CHECK ALL PIPE SIZING ON THE
 STORM SYSTEM AND SHOW ALL PIPE SIZES.
 SECTION 104.2.1. & TABLES 1106.2 &
 1106.3. - THERE ARE STILL PIPE SIZES
 MISSING AND SF AS IT ACCUMULATES. NO
 RESPONSE NOTED.
 34) SHT P-11AUXILLARY HORIZONTAL DRAIN
 PIPE SIZE NOT CORRECT. TABLE 1106.3. -
 NO RESPONSE NOTED. - SEE RWL S/8.
 35) THE TRASH CHUTE BEQUIRES AN "N-36"
 VACUUM BREAKER FOR BACKFLOW PROTECTION.
 SECTION 608.13.6. NO RESPONSE. SHEET
 VOIDED BUT NO NEW SHEET SUBMITTED.
 36) SHT P-12 AUXILLARY HORIZONTAL DRAIN
 PIPE TO BE SIZED PER TABLE 1106.3. NO
 RESPONSE. SHEET VOIDED BUT NO NEW SHEET
 SUBMITTED.
 37) SHTS P-13, & P-14 AUXILLARY ROOF
 DRAIN NEAR POOL SHALL NOT BE A TRIPPING
 HAZARD. PLEASE SUBMIT A DETAIL FOR S/27,
 S/28, S/29, & S/30 SECONDARY DRAINS.
 SECTION 104.2.1. NO RESPONSE NOTED. SHT
 VOIDED, BUT NO NEW SHEET SUBMITTED.
 38) SHT P-22 NO WATER SUPPLY SHOWN TO
 THE TRASH ROOM FOR THE TRASH CHUTE.
 PLEASE SHOW ON PLANS. SECTION 104.2.1.
 NO RESPONSE NOTED. SHEET VOIDED, BUT NO
 NEW SHEET SUBMITTED. TRASH CHUTE NOTES
 ON SHT 42 INDICATES THAT A WASH DOWN
 HEAD IS LOCATED AT THE TOP OF THE CHUTE.
 39) SHTS P-24, P-25, P-26, P-27, & P-28
 DO NOT MEET CODE REQUIREMENTS. IN MANY
 CASES THESE ARE THE CODE ISSUES NOT
 ADDRESSED. - THESE COMMENTS NOW APPLY TO
 SHTS 23, 29, 30, & 31 AS NEW RISERS HAVE
 BEEN SUBMITTED, AND SHEET INFORMATION
 HAS CHANGED.
 A. OFFSET VENTS ARE REQUIRED WHEN
 HORIZONTAL OFFSET ARE USED. SECTION 915.
 RESPONSE NOT APPROVED. OFFSET VENTS
 SHALL BE SHOWN ON THE RISER DIAGRAMS.
 SEE SECTION 104.2.1. - STILL SOME NOT
 SHOWN AS REQUIRED
 B. NO HORIZONTAL DRY VENTS. SECTION
 905.3. - OK
 C. STACK DRAIN SHALL CONNECT DOWNSTREAM
 OF BATHROOM GROUP FIXTURES. SECTION
 909.1 - OK
 D. KITCHEN SINK SHALL NOT DRAIN THROUGH
 THE WET VENT. SECTION 909.1 - OK
 E. MAIN VENT REQUIRED AT TOP OF STACKS.
 SECTION 903.1. SOME STILL NOT PIPED
 CORRECTLY.
 F. CLEANOUTS REQUIRED AT THE BASE OF
 EACH STACK. SECTION 708.3.4. - OK
 G. NO HORIZONTAL BRANCH CONNECTIONS TO
 A HORIZONTAL STACK OFFSET. SECTIONS
 711.2 & 711.3. - OK
 H. VENTING REQUIRED 901.2.1.
 I. (NEW COMMENT) EVERY VENT STACK SHALL
 CONNECT TO THE BASE OF THE DRAINAGE
 STACK. THE VENT STACK SHALL CONNECT AT
 OR BELOW THE LOWEST HORIZONTAL BRANCH.
 SECTION 903.4 - SOME VENT STACKS ARE NOT
 CONNECTED TO THE STACK, BUT CONNECT TO
 THE BRANCH LINE.
 J. STACK INSTALLATION 910.2
 THE RISERS ARE NOT CLEAR AS TO THEIR
 INTENT. CHECK ALL RISERS FOR CODE
 REQUIREMENTS. - OK
 43) SHT P-31 AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM ALL RISERS. WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9 SHALL BE LOCATED AT ALL QUICK
 CLOSING VALVES, (W/M, ICE MAKER, & D/W),
 AND SHALL BE LOCATED NEAR THE FIXTURE.
 PDI-WH 201 AND MANUF. INSTALL. INSTRUCT.
 - ONLY ONE SET OF AIR CHAMBERS STILL
 REMAIN TO BE DELETED. SHT P-35 UNIT
 L/W-D-2 FIXTURE P-2 2ND FLOOR.
 44) SHTS P-33 & P-34 AUXILLARY ROOF
 DRAINS ON SOME SYSTEMS ARE UNDERSIZED.
 PLEASE SIZE PIPE PER TABLE 1106.3. ROOF
 DRAINS CHANGED TO SHTS 39, 40, 41, & 42,
 AND STILL HAVE SOME AUXILLARY ROOF DRAIN
 PIPING SIZED INCORRECTLY. SOME DRAINS
 ARE STILL SIZED INCORRECTLY. ALSO SHOW
 SF AS IT ACCUMULATES.
 45) SHT P-35 STORM DRAIN RISER 111, SHOW
 ALL PIPE SIZES AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. RECHECK ALL
 PIPE SIZES PER TABLES 1106.2 & 1106.3 AS
 SOME PIPE SIZES ARE INCORRECT. THERE ARE
 STILL SOME PIPE SIZES THAT ARE
 INCORRECT. RISER III CHANGED TO RISER II
 AND MOVED TO SHT 41.1. - SIZES ON SOME
 PIPES ARE INCORRECT STILL, AND SQUARE
 FOOTAGE AS IT ACCUMULATES IS STILL NOT
 SHOWN AT EACH BRANCH LINE OR RISER.
 49) SUBMIT A CONDENSATE DRAIN ISOMETRIC
 WITH ALL PIPE SIZES, LOCATION OF RISER
 CONNECTIONS, RISERS, TERMINATION POINT
 OF THE RISERS (VENTS), AND INDICATE
 WHERE THE CONDENSATE DRAINS TO THE
 OUTSIDE OF THE BUILDING. SECTION
 104.2.1. LOCATION OF TERMINATION POINT
 FOR THE CONDENSATE HAS NOT BEEN GIVEN.
 2ND REVIEW
 **************NEW COMMENTS**************
 1B) NEW FLOOR LAYOUTS, NEW REVIEW
 2B) SHTS A27 THRU A32 ALL TYPICAL UNITS
 SHOW CLEAR FLOOR SPACE FOR W/C'S PER
 PAGE 7.43 FHA DESIGN MANUAL. SEE MINIMUM
 CLEAR FLOOR SPACE SIZE REQUIREMENTS. -
 SHOWER CLEAR FLOOR SPACE SHALL BE
 PARALLEL AND FLUSH WITH THE CONTROL
 WALL. SEE PAGE 7.56.- THIS COMMENT HAS
 NOT BEEN ADDRESSED PROPERLY AS PER FHA
 DESIGN MANUAL. - NO RESPONSE NOTED.
 3B) SHTS A27 THRU A32 ALL TYPICAL UNITS
 WATER CLOSETS SHALL BE 18" OFF WALL TO
 CENERLINE OF FIXTURE. SEE PAGES 6.5,
 7.43, 7.44 & 7.45. THIS IS WHEN THE W/C
 IN NEXT TO A WALL. - THIS HAS NOT BEEN
 ADDRESSED, NOR HAS A RESPONSE BEEN
 NOTED.
 4B) SHTS A27 THRU A32 ALL TYPICAL UNITS
 SHALL SHOW THE DIMENSIONS FOR THE W/C
 OPENINGS. MINIMUM 33" REQUIRED. SEE
 PAGES 7.43 THRU 7.45. THIS HAS NOT BEEN
 ADDRESSED, NOR HAS A RESPONSE BEEN
 NOTED.
 5B) SHT A1 DRAWING INDEX DOES NOT
 REFLECT DRAWING SHEETS. SECTION 104.2.1.
 - THIS HAS NOT BEEN ADDRESSED, NOR HAS A
 RESPONSE BEEN NOTED.
 8B) SHT P-3 STORM AND AUXILLARY
 PIPING SIZE IS NOT CORRECT IN MANY
 AREAS. CHECK PIPE SIZE PER TABLES 1106.2
 AND 1106.3. SOME PIPE SIZE STILL NOT
 CORRECT.
 7B) SHT P-4 SOME PIPE SIZES ARE NOT
 SHOWN. TABLES 1106.2 & 1106.3 AND
 SECTION 104.2.1.
 11B) SHT P-6 SHOW PIPING FOR PD(3061SF).
 TABLE 1106.3 AND SECTION 104.2.1. - 4"
 SHOWN BUT 6" REQUIRED. - FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM (100).
 SECTION 104.2.1. - THIS STILL DOES NOT
 REFLECT THE FLOOR PLAN.
 12B) SHT P-7 6" REQUIRED ON AUXILLARY
 DRAIN LINES AT RISERS S/28, & S/29. 5"
 REQUIRED ON AUXILLARY DRAIN LINE BETWEEN
 COL. - PIPE SIZES NOT SHOWN FOR ROOF
 DRAINS, PRIMARY AND SECONDARY FOR COMMON
 PATIO AND PRIVATE LANAI AREAS. SECTION
 104.2.1 AND TABLE 1106.3. - UNABLE TO
 FIND S/28 & 2/29. PLEASE SHOW AN INDEX
 OF ALL STORM RISER DIAGRAMS USED. - PIPE
 SIZES NOT SHOWN ON AUXILLARY ROOF DRAINS
 DOWNSTREAM OF S/44 THEN SHOWN AS 4"
 DOWN. MINIMUM 5" REQUIRED. NOT ALL PIPE
 SIZES ARE SHOWN.
 13B) SHT P-8 6" REQUIRED ON AUXILLARY
 DRAINS S/26 & S/29. 8" REQUIRED ON
 AUXILLARY DRAINS S/14, & S/18. SHOW ALL
 PIPE SIZES FOR ROOM PRIMARY & SECONDARY
 DRAINS AT COMMON PATIO AND PRIVATE LANAI
 AREAS. TABLES 1106.2 & 1106.3. - NOW
 UNABLE TO LOCATE RISER S/29 PLEASE
 CLARIFY. - NOT ALL PIPES SIZES SHOWN.
 14B) SHT P-10 UNIT C-3L MAX. 4 FU ON 2"
 WET VENT. TABLE 909.3 - UNITS C-4L,
 B-4L, & C-6L STILL SHOW NO PIPE SIZE FOR
 THE SECTION OF PIPE DOWNSTREAM OF THE
 LAST FIXTURE, (P-2 OR P-2A), 5FU.
 MINIMUM 3" REQUIRED.
 17B) SHT P-23 RISER 3,4,5,6 DOES NOT
 REFLECT THE FLOOR PLAN. SHT P-3 SHOWS
 RISER 6 CONNECTING TO RISER 345 ON THE
 FIRST FLOOR NOT AT THE MEZZ. LEVEL AS
 SHOWN ON THE RISER. SECTION 104.2.1. -
 SHT P-5 SHOWS ONLY RISER #8 WITH RISERS
 3,4,5,6 CONNECTING TO THIS RISER.
 CORRELATE RISERS AND FLOOR PLAN. -
 SHOULD BE RISER 3,4,5,6,8 WITH 3,4,5,6
 SPLITTING OFF AT MEZZ. LEVEL AND RISER 8
 OFFSETTING AT THE 2ND FLOOR TO REFLECT
 THE FLOOR PLAN.
 18B) SHT P-23 RISER #7 DOES NOT REFLECT
 FLOOR PLAN ON SHT P-5 AT LAV. - THIS HAS
 NOT BEEN ADDRESSED, NOR WAS THERE A
 COMMENT RESPONSE.
 19B) SHT P-23 RISER DOES NOT REFLECT
 FLOOR PLAN AT RISER 10 ON THE 2ND FLOOR.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1. - NOT ADDRESSED, NO COMMENT
 RESPONSE.
 23B) SHT P-35 DELETE AIR CHAMBERS
 SECTION 104.2.1. SEE RISER 11-11R AT
 FIXTURE P2. AIR CHAMBER NOT DELETED.
 25B) SHTS P-39, P-40, P-41, & P-41.1,
 CHECK ALL AUXILLARY DRAINS FOR CORRECT
 SIZE. TABLE 1106.3 @ 4.5"/HR. - SOME
 SIZES NOT SHOWN. 42, 43, 44, TO BE 5"
 DOWN.
 ****************************************
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION. -
 NO RESPONSE TO THIS REQUIRES LAST
 SUBMITTAL. - NO RESPONSE TO THIS REQUEST
 SECOND REVIEW ALSO. THIS ADDS ADDITIONAL
 TIME TO THE PLAN REVIEW AS IT CAUSES THE
 PLAN TO BE REVIEWED AS A NEW REVIEW EACH
 TIME.
 ****************************************
 ********COMMENTS FOR THIRD REVIEW*******
 ****************************************
 1C. SHT P-6 AUXILLARY DRAINS, MINIMUM 6"
 REQUIRED FOR PD 3061SF BY HDCP PARKING
 SPACE 64, 4" SHOWN. - 8" HORIZONTAL
 REQUIRED PD'S 5866 SF TOTAL COL. 11/F.
 2C. SHT P-7 AUXILLARY DRAINS, MINIMUM 5"
 REQUIRED ON HORIZONTAL FOR S/9, S/32,
 S/33, @ 842 SF, & S/42, S/43, S/44 @
 1429 SF.
 3C. SHT P-8 AUXILLARY DRAINS, MINIMUM 5"
 REQUIRED ON HORIZONTAL FOR S/54, S/55,
 S/56 @ 1142 SF AND DOWNSTREAM, AND FOR
 S/16, S/46, S/47 @ 842 SF.
 4C. SHT P-39 RISERS S/2, S/9-S/32-S/33,
 S/42-S/43-S/44 MINIMUM 5" REQUIRED FOR
 AUXILLARY DRAINS OVER 800 SF.
 5C. SHT P-40 S/28.2 SF DOES NOT REFLECT
 SF ON SHT P-11. CORRELATE RISER AND ROOF
 LAYOUT. - AUXILLARY S/18 MINIMUM 8"
 REQUIRED. - AUXILLARY S/26 MINIMUM 6"
 REQUIRED. - AUXILLARY S/54-S/55-S/56
 SHOW 5" ON HORIZONTAL DOWNSTREAM OF
 S/55.
 6C. SHT P12 2/14 & S/18 8" REQUIRED ON
 AUXILLARY DRAIN. - S/26 6" REQUIRED ON
 AUXILLARY DRAIN. TABLE 1106.3
 7C. SUBMIT A DETAIL FOR ROOF SCUPPERS.
 SHOW HEIGHT AND WIDTH AND INDICATE
 MEASUREMENT FROM ROOF TO FLOW LINE OF
 SCUPPER AS REQUIRED BY SECTION 15-3.4.2.
 8C. SHT P-23 SANT. RISER DIAGRAM 1 & 2
 SHOWS A 4" VENT LINE THAT WAS OFFSET ON
 THE 2ND FLOOR CONTINUING ON THE 3RD THRU
 7TH FLOOR AND OFFSETTING AGAIN. PLEASE
 CLARIFY. - SANT. RISER 2 STACK VENT TO
 EXTEND AND CONNECT TO VENT LINE. SECTION
 903.1. - SANT. RISERS 6, 7, & 8 VENT
 STACK SHALL CONNECT TO THE DRAINAGE
 STACK NOT THE FIXTURE BRANCH. SECTION
 903.4. - SANT. RISER 7 UPPER PORTION OF
 OFFSET VENT REQUIRED.
 9C. SHT P-24 SANT RISERS 15, 18, 17, 19,
 VENT TO CONNECT TO DRAINAGE STACK NOT
 FIXTURE BRANCH. 903.4
 10C. SHT P-24 SANT. RISERS 17 & 19,
 (TOP), OFFSET VENTS REQUIRED. SECTION
 SECTION 915.
 11C. SHT P-24 SANT. RISERS 21 & 25 STACK
 VENT TO EXTEND AND TIE INTO VENT STACK.
 SECTION 903.1.
 12C. SANT. RISER 23 VENT STACK NOT
 REQUIRED. SANT. RISER 25 CHANGE OFFSET
 VENT TO CONNECT TO DRAINAGE STACK PER
 SECTION 903.4.
 10C. SHT P-25 SANT. RISER 28 VENT STACK
 NOT REQUIRED. - SANT. RISER 27 STACK
 VENT TO EXTEND AND TIE INTO VENT STACK.
 SECTION 903.1.
 11C. SHT P-25 SANT. RISERS 30, 31, 34.
 37 VENT STACK SHALL CONNECT TO THE
 DRAINAGE STACK, NOT THE BRANCH LINE.
 SECTION 903.4. - SANT. RISER 37 SHOWS
 THE PIPING DIRECTION AWAY FROM THE
 STACK. PLEASE CLARIFY. SECTION 104.2.1.
 12C. SANT. RISER 35 MAXIMUM 4 FU ON 2"
 WET VENT. NO PIPE SIZE SHOWN. ALL
 FLOORS. TABLE 909.3
 13C. SHT P-26 SANT. RISER 38/39 IDENTIFY
 FIXTURE ON MEZZ. LEVEL, AND A VENT IS
 REQUIRED FOR SAME FIXTURE. 901.2.1.
 14C. SHT P-26 SANT. RISERS 38/39, 40,
 41, 43, 44, 46, 47, 48/49 CONNECT VENT
 STACK TO DRAINAGE STACK AT BASE OF STACK
 PER SECTION 903.4. - SANT. RISER VENT TO
 EXTEND AND TIE INTO VENT STACK. SECTION
 903.1. - SANT. RISER 46 OFFSET VENT NOT
 REQUIRED. - SANT. 48/49 EXTEND STACK
 VENT AND CONNECT TO VENT STACK. SECTION
 903.1.
 15C. SHT P-27 SANT. RISER 81/105 OFFSET
 VENT NOT REQUIRED. - MAX 4 FU ON 2" WET
 VENT. TABLE 909.3 - ALL FLOORS. -
 CONNECT VENT STACK TO DRAINAGE STACK PER
 SECTION 903.4.
 16C. SHT P-27 SANT. RISER 79 CONNECT
 VENT STACK TO DRAINAGE STACK PER SECTION
 903.4 - STACK VENT TO CONNECT TO VENT
 STACK AT TOP OF RISER. SECTION 903.1.
 17C. SANT. RISERS 82.106 & 85 MAXIMUM 4
 FU ON 2" WET VENT. TABLE 903.3. ALL
 FLOORS.
 18C. SANT RISER 84 CONNECT VENT STACK TO
 DRAINAGE STACK NOT BRANCH LINE PER
 SECTION 903.4.
 19C. SHT P-28 ALL SANT. RISERS CONNECT
 THE VENT STACKS TO THE DRAINAGE STACKS
 PER SECTION 903.4.
 20C. SHT P-28 SANT. RISER 51/52 SHOW 3
 STACKS, BUT ONLY 2 STACK NUMBERS. PLEASE
 CLARIFY. SECTION 104.2.1. - OFFSET VENT
 SHALL CONNECT TO SOIL STACK (52) NOT
 STACK 51.
 21C. SHT P-28 SANT. RISER 53 OFFSET VENT
 REQUIRED FOR OFFSET BETWEEN MEZZ. & 2ND
 FLOOR. SECTION 915. - MAXIMUM 4 FU ON 2"
 WET VENT. TABLE 903.3.
 22C. SHT P-28 SANT. RISER 54-55-55.1
 OFFSET VENT REQUIRED BETWEEN MEZZ. LEVEL
 AND 2ND FLOOR.
 23C. SHT P-28 OFFSET VENT & VENT LINE
 ARE NOT REQUIRED.
 24C. SHT P-28 INDICATE STACK NUMBER FOR
 STACK BETWEEN RISERS 57 & 58. SECTION
 104.2.1.
 25C. SANT. RISER 57 EXTEND STACK VENT
 AND TIE INTO VENT STACK. SECTION 903.1.
 26C. SHT P-28 SANT. RISER 59 MAXIMUM 4
 FU ON 2" WET VENT. TABLE 903.3. ALL
 FLOORS.
 27C. SHT P-29 SANT. RISERS 62, 64, 66,
 71, 73, 74, 99, & 102 CONNECT THE VENT
 STACK TO THE DRAINAGE STACK PER SECTION
 903.4.
 28C. SHT P-29 SANT. RISER 73 EXTEND
 STACK VENT AND CONNECT TO VENT STACK.
 SECTION 903.4.
 29C. SHT P-29 SANT. 100 OFFSET VENT AND
 VENT LINE NOT REQUIRED. SECTION 104.2.1.
 30C. SHT P-31 SANT. RISERS 92, 95, 97/98
 CONNECT VENT STACK TO DRAINAGE STACK PER
 SECTION 903.4.
 31C. SHT P-31 SANT. RISER 93 INDICATE
 VENT SIZE. TABLE 916.1.
 32C. SHT P-31 SANT. RISER 97 EXTEND
 STACK VENT AND CONNECT TO VENT STACK.
 SECTION 903.1.
 33C. SHT P-38 A/C CLOSET IS SHOWN AS A
 PLENUM. PVC OR CPVC IS NOT ALLOWED IN
 THE PLENUM. INDICATE MATERIAL TYPE FOR
 CONDENSATE LINES IN THE PLENUM. SECTIONS
 303.2. AND 602.2.1 OF THE MECHANICAL
 CODE.
 34C. SHT P-42 WATER HEATER DIAGRAM SHOWS
 P/T TO HEATER PAN, BUT STATES 3/4" DRAIN
 TO OUTSIDE. PLEASE CLARIFY. SECTION
 104.2.1.
 35C. SHT P-1 STORM SHOWS 12" HORIZONTAL,
 THEN 10" UP TO FIRST FLOOR AT COL. LINE
 5/G. PIPING SHALL NOT BE REDUCED IN THE
 DIRECTION OF FLOW PER SECTION 704.2.
 36C. SUBMIT AN ISOMETRIC STORM DRAIN
 RISER DIAGRAM FOR THE PD DRAIN SYSTEMS
 SHOWING ALL PIPE SIZES AND SF AS IT
 ACCUMULATES IN THE SYSTEM TO REFLECT THE
 FLAT PD DRAINAGE SYSTEM. SECTION
 104.3.1.1.
 37C. SHT P-11 RISER S/8, 8" MINIMUM
 REQUIRED ON AUXILLARY. TABLE 1106.3.
 38C. SHT P-12 RISERS S/14, & S/18, 8"
 MINIMUM REQUIRED ON AUXILLARY. TABLE
 1106.3.
 39C. SHT P-12 RISER S/26, 6" MINIMUM
 REQUIRED ON AUXILLARY. TABLE 1106.3.
 40C. SHT P-12 RISERS S17, & S/17.1 DOWN
 AND DOWN AUXILLARY MISLABELED. SECTION
 104.2.1.
 41C. SHTS P13 & P14 SHOWS "THRU SCUPPER"
 PLEASE CLARIFY. POOL DECK REQUIRES
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107. SHOW THE LOCATION
 OF ALL REQUIRED DRAINS.
 42C. SHT P-32 RISER 3/4/5/6/8 DOES NOT
 REFLECT THE FLOOR PLAN. ALL VENT STACKS
 SHALL CONNECT TO THE DRAINAGE STACK PER
 SECTION 903.4.
 43C. SHTS P-33 & P-34 ALL VENT STACKS
 SHALL CONNECT TO THE DRAINAGE STACK.
 SECTION 903.4.
 44C. SHT P-35 UNIT L/W-D-2 DELETE
 AIR CHAMBERS FROM FIXTURE P-2, 2ND
 FLOOR. SECTION 604.9.
 45C. SHTS P-39 & P-40 SEE COMMENT NUMBER
 5 FROM PREVIOUS REVIEW CONCERNING
 DRAWING INDEX. SECTION 104.2.1.
 46C. SHTS P-41 & P41.1 SHOW ALL PIPE
 SIZES, AND RECHECK ADDITION ON SF. -
 DOWNSTREAM OF 8" @ 1/8"/FT 8615 SF SHOWS
 10" @ 1/8"/FT 10713 SF AND NO BRANCH
 LINES INBETWEEN. PLEASE CLARIFY. -
 DOWNSTREAM OF S/49-S/50 AUXILLARY SHOWS
 A LINE CONNECTING INTO THE STORM LINE.
 DELETE FROM SHEETS.
 47C. SHT P-42 SUMP PUMP DETAIL, PUMP AND
 WASTE LINE NOT APPROVED. OIL SHALL BE
 RECLAIMED AND RECYCLED. DELETE FROM
 DETAIL.
 48C. SHT P-42 CONDENSATE DRAIN TRAP
 DETAIL. MATERIAL TO BE USED FOR THE TRAP
 AND CONDENSATE LINE IS STATED AS PVC IN
 THE GENERAL PLUMBING NOTES #4(C). THIS
 IS NOT APPROVED IN THE PLENUM. INDICATE
 MATERIAL TO BE USED IN THE PLENUM.
 SECTION 606.2.1 (MECH).
 49C. SHT P-42 TRASH CHUTE SPECIFICATION
 #6 INDICATES A FLUSHING HEAD. AN N36
 VACUUM BREAKER IS REQUIRED AT THE
 HIGHEST POINT OF THE WATER SUPPLY. SHOW
 WATER LINE TO TRASH CHUTE ON THE WATER
 RISER DIAGRAM. SHOW PIPE SIZE AND VACUUM
 BREAKER. SECTIONS 104.3.1. & 608.13.8.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION. -
 THIS HAS BEEN REQUESTED EACH REVIEW AND
 NO RESPONSE TO THIS REQUEST HAS BEEN
 NOTED. NO COMMENT RESPONSE AND NOT
 RETURNING THE PREVIOUS PLANS ADDS MANY
 HOURS TO THE REVIEW PROCESS AND SLOWS
 THE PERMIT PROCESS.
  
 REVIEW BY KEN STEVENS