| 2005-07-30 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | FHA-98 DESIGN MANUAL |
| | |
| | A) COMMENTS FROM PREVIOUS REVIEW THAT |
| | HAVE NOT BEEN ADDRESSED, OR NOT |
| | ADDRESSED PROPERLY. THE COMMENT NUMBER |
| | WILL REMAIN THE SAME AS THE FIRST |
| | REVIEW: |
| | 1) SHTS I-1, & I-2 FIRM LICENSE NUMBER |
| | REQUIRED ON THE TITLE BLOCK, SIGNATURE |
| | REQUIRED, AND PRINTED NAME REQUIRED. FAC |
| | 61G1-16.004(2)(5)(6), 61G1-16.003 AND FS |
| | 481.219. - SUBMIT PROOF OF A LEGAL |
| | SIGNATURE IN THE FORM OF A DRIVERS |
| | LICENSE, VOTERS REG. CARD ECT., AND |
| | SUBMIT A SIGNED/SEALED/DATED NOTORIZED |
| | LETTER WITH YOUR LEGAL SIGNATURE FOR OUR |
| | FILES. (TITLE BLOCK REQD ON LETTER). - |
| | THIS COMMENT HAS NOT BEEN ADDRESSED, NOR |
| | HAS A RESPONSE BEEN NOTED. |
| | 3) SHTS A-11 & A-12 SHT INDEX STATES |
| | PARTIAL 3RD-7TH FLOOR PLAN 1, BUT NOTE 5 |
| | STATES 3RD-5TH FLOOR PLAN. PLEASE |
| | CLARIFY. SECTION 104.2.1. - THIS HAS NOT |
| | BEEN ADDRESSED, NOR HAS A RESPONSE BEEN |
| | NOTED. |
| | 4) SHTS A-9 & A-15 SUBMIT CALCULATIONS |
| | FOR PRIMARY AND SECONDARY ROOF DRAINS |
| | PER SECTIONS 1106, & 1107 AND ALL |
| | SUBSECTIONS. SHOW SF OF EACH AREA WITH |
| | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS AND ROOF AREA FROM ABOVE THAT |
| | DRAINS TO THE ROOF FROM ABOVE ADDED TO |
| | THE SF IN THE CALCULATIONS. SHOW THE |
| | LOCATION OF ALL PRIMARY AND SECONDARY |
| | ROOF DRAINS AND THE SCUPPERS. ALSO SEE |
| | SHTS A-17 & A-18. THIS APPLIES TO THE |
| | ROOF DECK AREAS AS WELL. THIS HAS NOT |
| | BEEN ADDRESSED, NOR HAS A RESPONSE BEEN |
| | NOTED. |
| | 5) SHTS A-9 & A-15 SHOW THE LOCATION AND |
| | SIZE OF ALL SECONDARY ROOF DRAINS & |
| | SCUPPERS. SECTION 104.2.1. - THIS HAS |
| | NOT BEEN ADDRESSED, NOR HAS A RESPONSE |
| | BEEN NOTED. |
| | 6) SHTS A-15 & A-16 SUBMIT CALCULATIONS |
| | FOR MINIMUM FACILITIES PER TABLES 1003.1 |
| | AND 403.1. SHOW THE SF OF EACH COMMON |
| | AREA, AND THE TOTAL COMMON AREA IN THE |
| | CALCULATIONS. - THIS HAS NOT BEEN |
| | ADDRESSED, NOR HAS A RESPONSE BEEN |
| | NOTED. |
| | 7) ARCHITECTURAL SHEETS, THE DATE |
| | PREPARED AND THE PRINTED NAME OF THE |
| | PERSON RESPONSIBLE FOR THE DOCUMENT ARE |
| | REQUIRED PER FAC 61G1-16.004(4)(6) AND |
| | FS 481.2055. - THE PRINTED NAME OF THE |
| | PERSON HAS NOT BEEN ADDED TO THE TITLE |
| | BLOCK. NO RESPONSE NOTED. |
| | 8) SHTS A-30, A-31, & A-32 INDICATE |
| | SPECIFICATION "A" OR "B" FOR EACH UNIT |
| | OR BATHROOM AS REQUIRED ON PAGE 7.35 OF |
| | THE FHA DESIGN MANUAL. - SHT A-30 ONLY |
| | UNIT B-2 IS INDICATED. - SHT A-32 UNITS |
| | E-4, E-4L, & E-6 ARE NOT INDICATED. - IF |
| | SPECIFICATION "A" ALL BATHROOMS AND ALL |
| | FIXTURES SHALL COMPLY. SEE PAGE 7.34. |
| | 9) SHTS A-30, A-31, & A-32 SHOW THE SIZE |
| | OF THE OPENINGS FOR ALL COVERED WATER |
| | CLOSETS. MINIMUM 33" REQUIRED. SEE PAGES |
| | 6.5 AND 6.7 OF THE FHA DESIGN MANUAL. - |
| | THE 18" FROM THE WALL TO THE CENTERLINE |
| | OF THE W/C IS AN ABSOLUTE MEASURMENT. |
| | SEE FIGS PAGE 6.3 & 6.5. - NO RESPONSE |
| | NOTED AND NOT ALL OPENINGS ARE INDICATED |
| | AND NOT ALL OPENINGS MEET THE |
| | REQUIREMENTS OF FHA DESIGN MANUAL. |
| | 10) SHT A-33 MENS AND WOMENS RESTROOMS, |
| | SHOW CLEAR FLOOR SPACE FOR EACH |
| | ACCESSIBLE FIXTURE. SECTIONS 11-4.16.2, |
| | 11-4.19.3, & 11-4.22.3. THE TURNING AREA |
| | SHALL BE SHOWN IN THE TOILET ROOM, NOT |
| | IN THE ACCESSIBLE STALL. ALSO SHOW WATER |
| | CLOSET HEIGHT PER 11-4.16.3. GRAB BAR |
| | HEIGHT MAX. 36", SHOWN AS 48" ON DETAIL |
| | BEHIND W/C. SHOW FLUSH CONTROL 11-4.16.5 |
| | SHOW URINAL HEIGHT 11-4.18.2. THE |
| | CENTERLINE OF THE W/C SHALL BE 18" TO |
| | THE WALL FROM THE CENTERLINE OF THE |
| | FIXTURE, NOT 20" AS SHOWN. (SEE FIG. 28) |
| | FOR THE LAVS SHOW KNEE CLEARANCE |
| | 11-4.19.2, FOR THE SHOWER SHOW CONTROLS |
| | 11-4.21.5, SHOWER UNIT 11-4.21.6, AND |
| | CURB HEIGHT 11-4.21.8. - BACK AND SIDE |
| | GRAB BARS SHALL BE AT THE SAME HEIGHT. |
| | SEE FIG. 29. W/C HEIGHT 17" TO 19". 20" |
| | DIMENSION SHOWN ON SOME W/C'S. |
| | 11) NOT USED |
| | 12) SHT A-33 DETAIL #1 IN BOTH THE MEN'S |
| | AND WOMEN'S RESTROOMS. THE DOUBLE LAVS |
| | TO BE 34" IN HEIGHT AND HAVE A CLEARANCE |
| | OF 29". SEE FIG 31. SECTION 11-4.19.2. - |
| | NO RESPONSE NOTED. NOT ADDRESSED. |
| | 13) A DRINKING FOUNTAIN IS REQUIRED IN |
| | THE COMMON AREA. TABLE 403.1. SUBMIT A |
| | DETAIL COMPLYING WITH SECTIONS 11-4.15 |
| | AND ALL SUBSECTIONS & 11-4.1.3(10)(A) |
| | FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. - NO DETAIL FOUND, NOR WAS A |
| | RESPONSE NOTED. |
| | 14) SHT A-36 SHOW HEIGHT AND WIDTH OF |
| | SCUPPER OPENINGS ON THE DETAIL. SECTIONS |
| | 104.2.1 AND 1107.3. NO DETAIL FOUND, NOR |
| | WAS A RESPONSE NOTED. |
| | 15) A PROFESSIONAL ENGINEER SHALL SIGN |
| | HIS NAME. INITIALS ARE NOT APPROVED PER |
| | FBPE RULING. SUBMIT AN EXAMPLE OF THE |
| | ENGINEERS LEGAL SIGNATURE BY WAY OF |
| | DRIVERS LICENSE, VOTERS REG. ECT., AND A |
| | SIGNED, SEALED, DATED, NOTORIZED LETTER |
| | WITH TITLE BLOCK INDICATING YOUR LEGAL |
| | SIGNATURE FOR OUR FILES. |
| | 61G15-23.002(1)(2) AND FS 471.025. THIS |
| | IS FOR ALL ENGINEERED SHEETS. - LETTER |
| | WAS NOT SIGNED, SEALED, DATED, NOR DID |
| | THE LETTER HAVE A TITLE BLOCK ON IT. |
| | 18) SUBMIT MANUF. SPECIFICATION SHEETS |
| | FOR THE STORM WATER SUMP PUMPS. PUMP |
| | INFORMATION SHALL SHOW THE LISTING. |
| | SECTION 303.4.(SUBMITTALS NOT FOUND). - |
| | STILL NO RESPONSE TO THIS COMMENT. |
| | 19) SHTS P-3 & P-4 PIPE SIZING NOT |
| | CORRECT FOR EMERGENCY ROOF DRAIN PIPING, |
| | (SECONDARY ROOF DRAINS). SEE TABLES |
| | 1106.2 & 1106.3. STAIRWAY #2 NOT ADDED |
| | TO THE SYSTEM. DOUBLE CHECK ALL PIPE |
| | SIZES AND SHOW ADDITION OF ALL SF AS |
| | THEY ACCUMULATE IN THE STORM BLDG. |
| | DRAIN. SECTION 104.2.1. - THERE ARE |
| | STILL SOME PIPE SIZES AND SF NOT SHOWN |
| | ON THESE SHEETS. |
| | 27) SHT P-5 CHECK ALL PIPE SIZING ON THE |
| | STORM SYSTEM AND SHOW ALL PIPE SIZES. |
| | SECTION 104.2.1. & TABLES 1106.2 & |
| | 1106.3. - THERE ARE STILL PIPE SIZES |
| | MISSING AND SF AS IT ACCUMULATES. NO |
| | RESPONSE NOTED. |
| | 34) SHT P-11AUXILLARY HORIZONTAL DRAIN |
| | PIPE SIZE NOT CORRECT. TABLE 1106.3. - |
| | NO RESPONSE NOTED. - SEE RWL S/8. |
| | 35) THE TRASH CHUTE BEQUIRES AN "N-36" |
| | VACUUM BREAKER FOR BACKFLOW PROTECTION. |
| | SECTION 608.13.6. NO RESPONSE. SHEET |
| | VOIDED BUT NO NEW SHEET SUBMITTED. |
| | 36) SHT P-12 AUXILLARY HORIZONTAL DRAIN |
| | PIPE TO BE SIZED PER TABLE 1106.3. NO |
| | RESPONSE. SHEET VOIDED BUT NO NEW SHEET |
| | SUBMITTED. |
| | 37) SHTS P-13, & P-14 AUXILLARY ROOF |
| | DRAIN NEAR POOL SHALL NOT BE A TRIPPING |
| | HAZARD. PLEASE SUBMIT A DETAIL FOR S/27, |
| | S/28, S/29, & S/30 SECONDARY DRAINS. |
| | SECTION 104.2.1. NO RESPONSE NOTED. SHT |
| | VOIDED, BUT NO NEW SHEET SUBMITTED. |
| | 38) SHT P-22 NO WATER SUPPLY SHOWN TO |
| | THE TRASH ROOM FOR THE TRASH CHUTE. |
| | PLEASE SHOW ON PLANS. SECTION 104.2.1. |
| | NO RESPONSE NOTED. SHEET VOIDED, BUT NO |
| | NEW SHEET SUBMITTED. TRASH CHUTE NOTES |
| | ON SHT 42 INDICATES THAT A WASH DOWN |
| | HEAD IS LOCATED AT THE TOP OF THE CHUTE. |
| | 39) SHTS P-24, P-25, P-26, P-27, & P-28 |
| | DO NOT MEET CODE REQUIREMENTS. IN MANY |
| | CASES THESE ARE THE CODE ISSUES NOT |
| | ADDRESSED. - THESE COMMENTS NOW APPLY TO |
| | SHTS 23, 29, 30, & 31 AS NEW RISERS HAVE |
| | BEEN SUBMITTED, AND SHEET INFORMATION |
| | HAS CHANGED. |
| | A. OFFSET VENTS ARE REQUIRED WHEN |
| | HORIZONTAL OFFSET ARE USED. SECTION 915. |
| | RESPONSE NOT APPROVED. OFFSET VENTS |
| | SHALL BE SHOWN ON THE RISER DIAGRAMS. |
| | SEE SECTION 104.2.1. - STILL SOME NOT |
| | SHOWN AS REQUIRED |
| | B. NO HORIZONTAL DRY VENTS. SECTION |
| | 905.3. - OK |
| | C. STACK DRAIN SHALL CONNECT DOWNSTREAM |
| | OF BATHROOM GROUP FIXTURES. SECTION |
| | 909.1 - OK |
| | D. KITCHEN SINK SHALL NOT DRAIN THROUGH |
| | THE WET VENT. SECTION 909.1 - OK |
| | E. MAIN VENT REQUIRED AT TOP OF STACKS. |
| | SECTION 903.1. SOME STILL NOT PIPED |
| | CORRECTLY. |
| | F. CLEANOUTS REQUIRED AT THE BASE OF |
| | EACH STACK. SECTION 708.3.4. - OK |
| | G. NO HORIZONTAL BRANCH CONNECTIONS TO |
| | A HORIZONTAL STACK OFFSET. SECTIONS |
| | 711.2 & 711.3. - OK |
| | H. VENTING REQUIRED 901.2.1. |
| | I. (NEW COMMENT) EVERY VENT STACK SHALL |
| | CONNECT TO THE BASE OF THE DRAINAGE |
| | STACK. THE VENT STACK SHALL CONNECT AT |
| | OR BELOW THE LOWEST HORIZONTAL BRANCH. |
| | SECTION 903.4 - SOME VENT STACKS ARE NOT |
| | CONNECTED TO THE STACK, BUT CONNECT TO |
| | THE BRANCH LINE. |
| | J. STACK INSTALLATION 910.2 |
| | THE RISERS ARE NOT CLEAR AS TO THEIR |
| | INTENT. CHECK ALL RISERS FOR CODE |
| | REQUIREMENTS. - OK |
| | 43) SHT P-31 AIR CHAMBERS ARE NOT |
| | APPROVED. DELETE FROM ALL RISERS. WATER |
| | HAMMER ARRESTORS REQUIRED BY SECTION |
| | 604.9 SHALL BE LOCATED AT ALL QUICK |
| | CLOSING VALVES, (W/M, ICE MAKER, & D/W), |
| | AND SHALL BE LOCATED NEAR THE FIXTURE. |
| | PDI-WH 201 AND MANUF. INSTALL. INSTRUCT. |
| | - ONLY ONE SET OF AIR CHAMBERS STILL |
| | REMAIN TO BE DELETED. SHT P-35 UNIT |
| | L/W-D-2 FIXTURE P-2 2ND FLOOR. |
| | 44) SHTS P-33 & P-34 AUXILLARY ROOF |
| | DRAINS ON SOME SYSTEMS ARE UNDERSIZED. |
| | PLEASE SIZE PIPE PER TABLE 1106.3. ROOF |
| | DRAINS CHANGED TO SHTS 39, 40, 41, & 42, |
| | AND STILL HAVE SOME AUXILLARY ROOF DRAIN |
| | PIPING SIZED INCORRECTLY. SOME DRAINS |
| | ARE STILL SIZED INCORRECTLY. ALSO SHOW |
| | SF AS IT ACCUMULATES. |
| | 45) SHT P-35 STORM DRAIN RISER 111, SHOW |
| | ALL PIPE SIZES AND SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM. RECHECK ALL |
| | PIPE SIZES PER TABLES 1106.2 & 1106.3 AS |
| | SOME PIPE SIZES ARE INCORRECT. THERE ARE |
| | STILL SOME PIPE SIZES THAT ARE |
| | INCORRECT. RISER III CHANGED TO RISER II |
| | AND MOVED TO SHT 41.1. - SIZES ON SOME |
| | PIPES ARE INCORRECT STILL, AND SQUARE |
| | FOOTAGE AS IT ACCUMULATES IS STILL NOT |
| | SHOWN AT EACH BRANCH LINE OR RISER. |
| | 49) SUBMIT A CONDENSATE DRAIN ISOMETRIC |
| | WITH ALL PIPE SIZES, LOCATION OF RISER |
| | CONNECTIONS, RISERS, TERMINATION POINT |
| | OF THE RISERS (VENTS), AND INDICATE |
| | WHERE THE CONDENSATE DRAINS TO THE |
| | OUTSIDE OF THE BUILDING. SECTION |
| | 104.2.1. LOCATION OF TERMINATION POINT |
| | FOR THE CONDENSATE HAS NOT BEEN GIVEN. |
| | 2ND REVIEW |
| | **************NEW COMMENTS************** |
| | 1B) NEW FLOOR LAYOUTS, NEW REVIEW |
| | 2B) SHTS A27 THRU A32 ALL TYPICAL UNITS |
| | SHOW CLEAR FLOOR SPACE FOR W/C'S PER |
| | PAGE 7.43 FHA DESIGN MANUAL. SEE MINIMUM |
| | CLEAR FLOOR SPACE SIZE REQUIREMENTS. - |
| | SHOWER CLEAR FLOOR SPACE SHALL BE |
| | PARALLEL AND FLUSH WITH THE CONTROL |
| | WALL. SEE PAGE 7.56.- THIS COMMENT HAS |
| | NOT BEEN ADDRESSED PROPERLY AS PER FHA |
| | DESIGN MANUAL. - NO RESPONSE NOTED. |
| | 3B) SHTS A27 THRU A32 ALL TYPICAL UNITS |
| | WATER CLOSETS SHALL BE 18" OFF WALL TO |
| | CENERLINE OF FIXTURE. SEE PAGES 6.5, |
| | 7.43, 7.44 & 7.45. THIS IS WHEN THE W/C |
| | IN NEXT TO A WALL. - THIS HAS NOT BEEN |
| | ADDRESSED, NOR HAS A RESPONSE BEEN |
| | NOTED. |
| | 4B) SHTS A27 THRU A32 ALL TYPICAL UNITS |
| | SHALL SHOW THE DIMENSIONS FOR THE W/C |
| | OPENINGS. MINIMUM 33" REQUIRED. SEE |
| | PAGES 7.43 THRU 7.45. THIS HAS NOT BEEN |
| | ADDRESSED, NOR HAS A RESPONSE BEEN |
| | NOTED. |
| | 5B) SHT A1 DRAWING INDEX DOES NOT |
| | REFLECT DRAWING SHEETS. SECTION 104.2.1. |
| | - THIS HAS NOT BEEN ADDRESSED, NOR HAS A |
| | RESPONSE BEEN NOTED. |
| | 8B) SHT P-3 STORM AND AUXILLARY |
| | PIPING SIZE IS NOT CORRECT IN MANY |
| | AREAS. CHECK PIPE SIZE PER TABLES 1106.2 |
| | AND 1106.3. SOME PIPE SIZE STILL NOT |
| | CORRECT. |
| | 7B) SHT P-4 SOME PIPE SIZES ARE NOT |
| | SHOWN. TABLES 1106.2 & 1106.3 AND |
| | SECTION 104.2.1. |
| | 11B) SHT P-6 SHOW PIPING FOR PD(3061SF). |
| | TABLE 1106.3 AND SECTION 104.2.1. - 4" |
| | SHOWN BUT 6" REQUIRED. - FLOOR PLAN DOES |
| | NOT REFLECT THE RISER DIAGRAM (100). |
| | SECTION 104.2.1. - THIS STILL DOES NOT |
| | REFLECT THE FLOOR PLAN. |
| | 12B) SHT P-7 6" REQUIRED ON AUXILLARY |
| | DRAIN LINES AT RISERS S/28, & S/29. 5" |
| | REQUIRED ON AUXILLARY DRAIN LINE BETWEEN |
| | COL. - PIPE SIZES NOT SHOWN FOR ROOF |
| | DRAINS, PRIMARY AND SECONDARY FOR COMMON |
| | PATIO AND PRIVATE LANAI AREAS. SECTION |
| | 104.2.1 AND TABLE 1106.3. - UNABLE TO |
| | FIND S/28 & 2/29. PLEASE SHOW AN INDEX |
| | OF ALL STORM RISER DIAGRAMS USED. - PIPE |
| | SIZES NOT SHOWN ON AUXILLARY ROOF DRAINS |
| | DOWNSTREAM OF S/44 THEN SHOWN AS 4" |
| | DOWN. MINIMUM 5" REQUIRED. NOT ALL PIPE |
| | SIZES ARE SHOWN. |
| | 13B) SHT P-8 6" REQUIRED ON AUXILLARY |
| | DRAINS S/26 & S/29. 8" REQUIRED ON |
| | AUXILLARY DRAINS S/14, & S/18. SHOW ALL |
| | PIPE SIZES FOR ROOM PRIMARY & SECONDARY |
| | DRAINS AT COMMON PATIO AND PRIVATE LANAI |
| | AREAS. TABLES 1106.2 & 1106.3. - NOW |
| | UNABLE TO LOCATE RISER S/29 PLEASE |
| | CLARIFY. - NOT ALL PIPES SIZES SHOWN. |
| | 14B) SHT P-10 UNIT C-3L MAX. 4 FU ON 2" |
| | WET VENT. TABLE 909.3 - UNITS C-4L, |
| | B-4L, & C-6L STILL SHOW NO PIPE SIZE FOR |
| | THE SECTION OF PIPE DOWNSTREAM OF THE |
| | LAST FIXTURE, (P-2 OR P-2A), 5FU. |
| | MINIMUM 3" REQUIRED. |
| | 17B) SHT P-23 RISER 3,4,5,6 DOES NOT |
| | REFLECT THE FLOOR PLAN. SHT P-3 SHOWS |
| | RISER 6 CONNECTING TO RISER 345 ON THE |
| | FIRST FLOOR NOT AT THE MEZZ. LEVEL AS |
| | SHOWN ON THE RISER. SECTION 104.2.1. - |
| | SHT P-5 SHOWS ONLY RISER #8 WITH RISERS |
| | 3,4,5,6 CONNECTING TO THIS RISER. |
| | CORRELATE RISERS AND FLOOR PLAN. - |
| | SHOULD BE RISER 3,4,5,6,8 WITH 3,4,5,6 |
| | SPLITTING OFF AT MEZZ. LEVEL AND RISER 8 |
| | OFFSETTING AT THE 2ND FLOOR TO REFLECT |
| | THE FLOOR PLAN. |
| | 18B) SHT P-23 RISER #7 DOES NOT REFLECT |
| | FLOOR PLAN ON SHT P-5 AT LAV. - THIS HAS |
| | NOT BEEN ADDRESSED, NOR WAS THERE A |
| | COMMENT RESPONSE. |
| | 19B) SHT P-23 RISER DOES NOT REFLECT |
| | FLOOR PLAN AT RISER 10 ON THE 2ND FLOOR. |
| | CORRELATE RISER AND FLOOR PLAN. SECTION |
| | 104.2.1. - NOT ADDRESSED, NO COMMENT |
| | RESPONSE. |
| | 23B) SHT P-35 DELETE AIR CHAMBERS |
| | SECTION 104.2.1. SEE RISER 11-11R AT |
| | FIXTURE P2. AIR CHAMBER NOT DELETED. |
| | 25B) SHTS P-39, P-40, P-41, & P-41.1, |
| | CHECK ALL AUXILLARY DRAINS FOR CORRECT |
| | SIZE. TABLE 1106.3 @ 4.5"/HR. - SOME |
| | SIZES NOT SHOWN. 42, 43, 44, TO BE 5" |
| | DOWN. |
| | **************************************** |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. - |
| | NO RESPONSE TO THIS REQUIRES LAST |
| | SUBMITTAL. - NO RESPONSE TO THIS REQUEST |
| | SECOND REVIEW ALSO. THIS ADDS ADDITIONAL |
| | TIME TO THE PLAN REVIEW AS IT CAUSES THE |
| | PLAN TO BE REVIEWED AS A NEW REVIEW EACH |
| | TIME. |
| | **************************************** |
| | ********COMMENTS FOR THIRD REVIEW******* |
| | **************************************** |
| | 1C. SHT P-6 AUXILLARY DRAINS, MINIMUM 6" |
| | REQUIRED FOR PD 3061SF BY HDCP PARKING |
| | SPACE 64, 4" SHOWN. - 8" HORIZONTAL |
| | REQUIRED PD'S 5866 SF TOTAL COL. 11/F. |
| | 2C. SHT P-7 AUXILLARY DRAINS, MINIMUM 5" |
| | REQUIRED ON HORIZONTAL FOR S/9, S/32, |
| | S/33, @ 842 SF, & S/42, S/43, S/44 @ |
| | 1429 SF. |
| | 3C. SHT P-8 AUXILLARY DRAINS, MINIMUM 5" |
| | REQUIRED ON HORIZONTAL FOR S/54, S/55, |
| | S/56 @ 1142 SF AND DOWNSTREAM, AND FOR |
| | S/16, S/46, S/47 @ 842 SF. |
| | 4C. SHT P-39 RISERS S/2, S/9-S/32-S/33, |
| | S/42-S/43-S/44 MINIMUM 5" REQUIRED FOR |
| | AUXILLARY DRAINS OVER 800 SF. |
| | 5C. SHT P-40 S/28.2 SF DOES NOT REFLECT |
| | SF ON SHT P-11. CORRELATE RISER AND ROOF |
| | LAYOUT. - AUXILLARY S/18 MINIMUM 8" |
| | REQUIRED. - AUXILLARY S/26 MINIMUM 6" |
| | REQUIRED. - AUXILLARY S/54-S/55-S/56 |
| | SHOW 5" ON HORIZONTAL DOWNSTREAM OF |
| | S/55. |
| | 6C. SHT P12 2/14 & S/18 8" REQUIRED ON |
| | AUXILLARY DRAIN. - S/26 6" REQUIRED ON |
| | AUXILLARY DRAIN. TABLE 1106.3 |
| | 7C. SUBMIT A DETAIL FOR ROOF SCUPPERS. |
| | SHOW HEIGHT AND WIDTH AND INDICATE |
| | MEASUREMENT FROM ROOF TO FLOW LINE OF |
| | SCUPPER AS REQUIRED BY SECTION 15-3.4.2. |
| | 8C. SHT P-23 SANT. RISER DIAGRAM 1 & 2 |
| | SHOWS A 4" VENT LINE THAT WAS OFFSET ON |
| | THE 2ND FLOOR CONTINUING ON THE 3RD THRU |
| | 7TH FLOOR AND OFFSETTING AGAIN. PLEASE |
| | CLARIFY. - SANT. RISER 2 STACK VENT TO |
| | EXTEND AND CONNECT TO VENT LINE. SECTION |
| | 903.1. - SANT. RISERS 6, 7, & 8 VENT |
| | STACK SHALL CONNECT TO THE DRAINAGE |
| | STACK NOT THE FIXTURE BRANCH. SECTION |
| | 903.4. - SANT. RISER 7 UPPER PORTION OF |
| | OFFSET VENT REQUIRED. |
| | 9C. SHT P-24 SANT RISERS 15, 18, 17, 19, |
| | VENT TO CONNECT TO DRAINAGE STACK NOT |
| | FIXTURE BRANCH. 903.4 |
| | 10C. SHT P-24 SANT. RISERS 17 & 19, |
| | (TOP), OFFSET VENTS REQUIRED. SECTION |
| | SECTION 915. |
| | 11C. SHT P-24 SANT. RISERS 21 & 25 STACK |
| | VENT TO EXTEND AND TIE INTO VENT STACK. |
| | SECTION 903.1. |
| | 12C. SANT. RISER 23 VENT STACK NOT |
| | REQUIRED. SANT. RISER 25 CHANGE OFFSET |
| | VENT TO CONNECT TO DRAINAGE STACK PER |
| | SECTION 903.4. |
| | 10C. SHT P-25 SANT. RISER 28 VENT STACK |
| | NOT REQUIRED. - SANT. RISER 27 STACK |
| | VENT TO EXTEND AND TIE INTO VENT STACK. |
| | SECTION 903.1. |
| | 11C. SHT P-25 SANT. RISERS 30, 31, 34. |
| | 37 VENT STACK SHALL CONNECT TO THE |
| | DRAINAGE STACK, NOT THE BRANCH LINE. |
| | SECTION 903.4. - SANT. RISER 37 SHOWS |
| | THE PIPING DIRECTION AWAY FROM THE |
| | STACK. PLEASE CLARIFY. SECTION 104.2.1. |
| | 12C. SANT. RISER 35 MAXIMUM 4 FU ON 2" |
| | WET VENT. NO PIPE SIZE SHOWN. ALL |
| | FLOORS. TABLE 909.3 |
| | 13C. SHT P-26 SANT. RISER 38/39 IDENTIFY |
| | FIXTURE ON MEZZ. LEVEL, AND A VENT IS |
| | REQUIRED FOR SAME FIXTURE. 901.2.1. |
| | 14C. SHT P-26 SANT. RISERS 38/39, 40, |
| | 41, 43, 44, 46, 47, 48/49 CONNECT VENT |
| | STACK TO DRAINAGE STACK AT BASE OF STACK |
| | PER SECTION 903.4. - SANT. RISER VENT TO |
| | EXTEND AND TIE INTO VENT STACK. SECTION |
| | 903.1. - SANT. RISER 46 OFFSET VENT NOT |
| | REQUIRED. - SANT. 48/49 EXTEND STACK |
| | VENT AND CONNECT TO VENT STACK. SECTION |
| | 903.1. |
| | 15C. SHT P-27 SANT. RISER 81/105 OFFSET |
| | VENT NOT REQUIRED. - MAX 4 FU ON 2" WET |
| | VENT. TABLE 909.3 - ALL FLOORS. - |
| | CONNECT VENT STACK TO DRAINAGE STACK PER |
| | SECTION 903.4. |
| | 16C. SHT P-27 SANT. RISER 79 CONNECT |
| | VENT STACK TO DRAINAGE STACK PER SECTION |
| | 903.4 - STACK VENT TO CONNECT TO VENT |
| | STACK AT TOP OF RISER. SECTION 903.1. |
| | 17C. SANT. RISERS 82.106 & 85 MAXIMUM 4 |
| | FU ON 2" WET VENT. TABLE 903.3. ALL |
| | FLOORS. |
| | 18C. SANT RISER 84 CONNECT VENT STACK TO |
| | DRAINAGE STACK NOT BRANCH LINE PER |
| | SECTION 903.4. |
| | 19C. SHT P-28 ALL SANT. RISERS CONNECT |
| | THE VENT STACKS TO THE DRAINAGE STACKS |
| | PER SECTION 903.4. |
| | 20C. SHT P-28 SANT. RISER 51/52 SHOW 3 |
| | STACKS, BUT ONLY 2 STACK NUMBERS. PLEASE |
| | CLARIFY. SECTION 104.2.1. - OFFSET VENT |
| | SHALL CONNECT TO SOIL STACK (52) NOT |
| | STACK 51. |
| | 21C. SHT P-28 SANT. RISER 53 OFFSET VENT |
| | REQUIRED FOR OFFSET BETWEEN MEZZ. & 2ND |
| | FLOOR. SECTION 915. - MAXIMUM 4 FU ON 2" |
| | WET VENT. TABLE 903.3. |
| | 22C. SHT P-28 SANT. RISER 54-55-55.1 |
| | OFFSET VENT REQUIRED BETWEEN MEZZ. LEVEL |
| | AND 2ND FLOOR. |
| | 23C. SHT P-28 OFFSET VENT & VENT LINE |
| | ARE NOT REQUIRED. |
| | 24C. SHT P-28 INDICATE STACK NUMBER FOR |
| | STACK BETWEEN RISERS 57 & 58. SECTION |
| | 104.2.1. |
| | 25C. SANT. RISER 57 EXTEND STACK VENT |
| | AND TIE INTO VENT STACK. SECTION 903.1. |
| | 26C. SHT P-28 SANT. RISER 59 MAXIMUM 4 |
| | FU ON 2" WET VENT. TABLE 903.3. ALL |
| | FLOORS. |
| | 27C. SHT P-29 SANT. RISERS 62, 64, 66, |
| | 71, 73, 74, 99, & 102 CONNECT THE VENT |
| | STACK TO THE DRAINAGE STACK PER SECTION |
| | 903.4. |
| | 28C. SHT P-29 SANT. RISER 73 EXTEND |
| | STACK VENT AND CONNECT TO VENT STACK. |
| | SECTION 903.4. |
| | 29C. SHT P-29 SANT. 100 OFFSET VENT AND |
| | VENT LINE NOT REQUIRED. SECTION 104.2.1. |
| | 30C. SHT P-31 SANT. RISERS 92, 95, 97/98 |
| | CONNECT VENT STACK TO DRAINAGE STACK PER |
| | SECTION 903.4. |
| | 31C. SHT P-31 SANT. RISER 93 INDICATE |
| | VENT SIZE. TABLE 916.1. |
| | 32C. SHT P-31 SANT. RISER 97 EXTEND |
| | STACK VENT AND CONNECT TO VENT STACK. |
| | SECTION 903.1. |
| | 33C. SHT P-38 A/C CLOSET IS SHOWN AS A |
| | PLENUM. PVC OR CPVC IS NOT ALLOWED IN |
| | THE PLENUM. INDICATE MATERIAL TYPE FOR |
| | CONDENSATE LINES IN THE PLENUM. SECTIONS |
| | 303.2. AND 602.2.1 OF THE MECHANICAL |
| | CODE. |
| | 34C. SHT P-42 WATER HEATER DIAGRAM SHOWS |
| | P/T TO HEATER PAN, BUT STATES 3/4" DRAIN |
| | TO OUTSIDE. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 35C. SHT P-1 STORM SHOWS 12" HORIZONTAL, |
| | THEN 10" UP TO FIRST FLOOR AT COL. LINE |
| | 5/G. PIPING SHALL NOT BE REDUCED IN THE |
| | DIRECTION OF FLOW PER SECTION 704.2. |
| | 36C. SUBMIT AN ISOMETRIC STORM DRAIN |
| | RISER DIAGRAM FOR THE PD DRAIN SYSTEMS |
| | SHOWING ALL PIPE SIZES AND SF AS IT |
| | ACCUMULATES IN THE SYSTEM TO REFLECT THE |
| | FLAT PD DRAINAGE SYSTEM. SECTION |
| | 104.3.1.1. |
| | 37C. SHT P-11 RISER S/8, 8" MINIMUM |
| | REQUIRED ON AUXILLARY. TABLE 1106.3. |
| | 38C. SHT P-12 RISERS S/14, & S/18, 8" |
| | MINIMUM REQUIRED ON AUXILLARY. TABLE |
| | 1106.3. |
| | 39C. SHT P-12 RISER S/26, 6" MINIMUM |
| | REQUIRED ON AUXILLARY. TABLE 1106.3. |
| | 40C. SHT P-12 RISERS S17, & S/17.1 DOWN |
| | AND DOWN AUXILLARY MISLABELED. SECTION |
| | 104.2.1. |
| | 41C. SHTS P13 & P14 SHOWS "THRU SCUPPER" |
| | PLEASE CLARIFY. POOL DECK REQUIRES |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTIONS 1106 & 1107. SHOW THE LOCATION |
| | OF ALL REQUIRED DRAINS. |
| | 42C. SHT P-32 RISER 3/4/5/6/8 DOES NOT |
| | REFLECT THE FLOOR PLAN. ALL VENT STACKS |
| | SHALL CONNECT TO THE DRAINAGE STACK PER |
| | SECTION 903.4. |
| | 43C. SHTS P-33 & P-34 ALL VENT STACKS |
| | SHALL CONNECT TO THE DRAINAGE STACK. |
| | SECTION 903.4. |
| | 44C. SHT P-35 UNIT L/W-D-2 DELETE |
| | AIR CHAMBERS FROM FIXTURE P-2, 2ND |
| | FLOOR. SECTION 604.9. |
| | 45C. SHTS P-39 & P-40 SEE COMMENT NUMBER |
| | 5 FROM PREVIOUS REVIEW CONCERNING |
| | DRAWING INDEX. SECTION 104.2.1. |
| | 46C. SHTS P-41 & P41.1 SHOW ALL PIPE |
| | SIZES, AND RECHECK ADDITION ON SF. - |
| | DOWNSTREAM OF 8" @ 1/8"/FT 8615 SF SHOWS |
| | 10" @ 1/8"/FT 10713 SF AND NO BRANCH |
| | LINES INBETWEEN. PLEASE CLARIFY. - |
| | DOWNSTREAM OF S/49-S/50 AUXILLARY SHOWS |
| | A LINE CONNECTING INTO THE STORM LINE. |
| | DELETE FROM SHEETS. |
| | 47C. SHT P-42 SUMP PUMP DETAIL, PUMP AND |
| | WASTE LINE NOT APPROVED. OIL SHALL BE |
| | RECLAIMED AND RECYCLED. DELETE FROM |
| | DETAIL. |
| | 48C. SHT P-42 CONDENSATE DRAIN TRAP |
| | DETAIL. MATERIAL TO BE USED FOR THE TRAP |
| | AND CONDENSATE LINE IS STATED AS PVC IN |
| | THE GENERAL PLUMBING NOTES #4(C). THIS |
| | IS NOT APPROVED IN THE PLENUM. INDICATE |
| | MATERIAL TO BE USED IN THE PLENUM. |
| | SECTION 606.2.1 (MECH). |
| | 49C. SHT P-42 TRASH CHUTE SPECIFICATION |
| | #6 INDICATES A FLUSHING HEAD. AN N36 |
| | VACUUM BREAKER IS REQUIRED AT THE |
| | HIGHEST POINT OF THE WATER SUPPLY. SHOW |
| | WATER LINE TO TRASH CHUTE ON THE WATER |
| | RISER DIAGRAM. SHOW PIPE SIZE AND VACUUM |
| | BREAKER. SECTIONS 104.3.1. & 608.13.8. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. - |
| | THIS HAS BEEN REQUESTED EACH REVIEW AND |
| | NO RESPONSE TO THIS REQUEST HAS BEEN |
| | NOTED. NO COMMENT RESPONSE AND NOT |
| | RETURNING THE PREVIOUS PLANS ADDS MANY |
| | HOURS TO THE REVIEW PROCESS AND SLOWS |
| | THE PERMIT PROCESS. |
| | |