| Date |
Text |
| 2005-08-05 00:00:00 | ******DENIED****** |
| | |
| | PLEASE NOTE THAT COMMENTS FROM THE LAST |
| | FIRE REVIEW DON'T APPEAR TO HAVE BEEN |
| | ADDRESSED. AS INDICATED IN LAST REVIEW, |
| | A RESPONSE LETTER ILLUSTRATING THE |
| | CORRESPONDING SHEET NUMBER WOULD HELP |
| | EXPEDITE THE PLAN REVIEW PROCESS. THANK |
| | YOU IN ADVANCE FOR YOUR CONSIDERATION |
| | REGARDING THIS MATTER. |
| | |
| | 1) FIRE PROTECTION SHEETS ARE MISSING |
| | WITH THIS RESUBMITTAL. PLEASE KEEP ALL |
| | APPROPRIATE SHEETS ATTACHED FOR EACH |
| | REVIEW. PLEASE SEE COMMENT #1 FROM LAST |
| | REVIEW. |
| | |
| | 2) ALL SHAFTS THAT ARE LARGE ENOUGH FOR |
| | PERSONS TO FALL INTO MUST BE MARKED |
| | SHAFTWAY IN 6" LETTERS. |
| | |
| | 3) PLEASE INDICATED PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS FOR HANDRAILS AND |
| | GUARDS. |
| | |
| | 4) PLEASE SUBMIT OCCUPANT LOAD |
| | CALCULATIONS FOR THE POOL DECK AND |
| | PATIO. |
| | |
| | 5) ALL DOOR SWINGS SERVING AREAS OR |
| | ROOMS WITH OCCUPANT LOADS GREATER THAN |
| | 50 SHALL SWING IN THE DIRECTION OF |
| | TRAVEL. |
| | |
| | 6) PLEASE INDICATE ON PLANS THAT ALL |
| | SMOKE DETECTORS SHALL BE NO CLOSER THAN |
| | 3' FROM AC DIFFUSERS. |
| | |
| | 7) PLEASE ILLUSTRATE VERIFICATION |
| | REGARDING STANDBY POWER REQUIREMENTS. |
| | |
| | 8) ELEVATOR WARNING SIGNS ARE REQUIRED. |
| | PLEASE INDICATE WITH NOTE ON DRAWINGS. |
| | |
| | 9) EXITS SHALL BE READILY VISIBLE FROM |
| | ANY DIRECTION WITHIN EXIT ACCESS. |
| | |
| | 10) PLEASE SHOW ON PLANS THAT THE VOICE |
| | EVACUATION MESSAGE SHALL COMPLY WITH THE |
| | REQUIREMENTS OF NFPA 72, AND NFPA 101, |
| | SECTION 9.6.3. |
| | |
| | WHEN RESUBMITTING PLANS FOR REVIEW, IT |
| | IS RECOMMENDED THAT EACH COMMENT BE |
| | ADDRESSED BY LETTER INDICATING THE SHEET |
| | NUMBER WHERE APPLICABLE. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN |
| | WPBFR(561) 804-4756 |
| | PLAN REVIEW(561) 805-6722 |