| 2005-07-14 00:00:00 | ********* UNSAT 3RD REVIEW ************ |
| | |
| | "THE PLACE VIA CLEMATIS" |
| | |
| | PLEASE SEE COMMENTS FROM PREVIOUS TWO |
| | REVIEWS WHICH STILL NEED TO BE |
| | ADDRESSED. |
| | |
| | PLEASE ALSO SEE NEW COMMENTS DUE TO |
| | CHANGES IN PLANS/DESIGN AND SOME SHEETS |
| | MISSING FROM PREVIOUS SUBMITTED PLANS. |
| | |
| | THESE ARE TAKEN DIRECTLY FROM PREVIOUS |
| | TWO REVIEWS IN NUMMERICAL ORDER. |
| | |
| | 1)NOTE: NOTE #1 NO, PLEASE SEE LETTER |
| | COULD NOT BE LOCATED IN PACKAGE. |
| | |
| | 2)NOTE: NOTE #2 NO, PLEASE SEE OUTWARD |
| | SWINGS ON DOORS. PLEASE CORRELATE ALL |
| | SHEETS SHOWING ELECTRICAL ROOMS ETC. |
| | PLEASE HAVE PLANS INDICATE GUARD RAILS |
| | FOR EGRESS PROTECTION FROM SECOND FLR |
| | GEN RM. PLEASE UNDERSTAND ANY EGRESS IN |
| | CASE OF AN EMERGENCY OR OTHER MAY RESULT |
| | IN A LIFE SAFETY SITUATION AS SHOWN ON |
| | PLANS. |
| | PLEASE SEE DOORS WERE MOVED IN MAIN |
| | ELECTRICAL ROOM, HOWEVER, PLEASE SEE |
| | WALLS AND DOORS ARE SHOWN BUILT DIRECTLY |
| | |
| | IN FRONT OF ELECTRICAL EQUIPMENT. |
| | 110.26 |
| | PLEASE SEE MINIMUM STANDING/WALKING AREA |
| | ON THE OUTSIDE OF ELECTRICAL ROOM AFTER |
| | LEAVING DOOR SWING AREA. PLEASE SEE |
| | PLANS STILL MENTIONS: A SIGN TO BE |
| | PLACED AT DOORS LEAVING ELECTRICAL TO |
| | READ; "OPEN DOOR CAREFULLY, WATCH FOR |
| | CARS ON OTHERSIDE OF DOORS" PLEASE KNOW |
| | IN AN EMERGENCY SITUATION WHEN THE |
| | POSSIBILTY OF SOMEONE BEING BLINDED OR |
| | ON FIRE;A SIGN WILL NOT HELP IN EXITING |
| | ROOM AND ONCE AGAIN CREATING AN ADDITION |
| | LIFE SAFTEY HAZARD FOR THE PERSON(S) |
| | EXITING ROOM. |
| | |
| | NOTE FOR PANIC HARDWARE WAS PLACED ON |
| | A-SHEETS, HOWEVER PLEASE PLACE NOTE ON |
| | ELECTRICAL PLANS FOR ELECTRICAL RMS. |
| | |
| | 3)NOTE: NOTE #3 OK. |
| | |
| | 4)NOTE: NOTE #4 OK. |
| | |
| | 5)NOTE: NOTE #5 OK, CIRCUITS ADDED, |
| | HOWEVER PLEASE SEE CIRCUITING PER ROOM |
| | PER 620.23,.24. ONLY ONE ELEVATOR |
| | MACHINE RM PER CIRCUIT. |
| | PLEASE SEE NEW NOTES FOR ELEV RM #4. |
| | |
| | 6)NOTE: NOTE #6 NO, PLEASE SEE MANY |
| | RECEPTS FOR WALL SPACE ARE STILL |
| | MISSING. PLEASE SEE MOST LOCATIONS ARE |
| | REDLINED. 210.52 |
| | |
| | 7)NOTE: NOTE #7 OK. |
| | |
| | 8)NOTE: NOTE #8 OK, HOWEVER PLEASE SEE |
| | NEW NOTE FOR NOTE ON E-19. |
| | |
| | 9)NOTE: NOTE #9 OK. |
| | |
| | 10)NOTE: NOTE #10 OK. |
| | |
| | 11)NOTE: NOTE #11 OK, SEE NEW NOTES. |
| | |
| | 12)NOTE: NO, SEE NOTE #3 FROM PREVIOUS |
| | REVIEW. PLEASE SEE SOME AREAS ARE SHOWN |
| | WITH LIVING RM. PLEASE ALSO SEE COMMENTS |
| | ABOUT CIRCUITING FOR DINING RM AREAS. |
| | |
| | 13)NOTE: NOTE #13, OK, SHEETS SUBMITTED, |
| | HOWEVER SEE NEW NOTES DUE TO REVIEW |
| | BEING POSSIBLE AT THIS TIME. |
| | |
| | 14)NOTE: NOTE #14 NO, PLEASE SEE MISSING |
| | KITCHEN GFI RECEPTS PER 210.52C1, |
| | 210.8A6. PLEASE SEE SOME AREAS REDLINED |
| | ON PLANS. |
| | |
| | 15)NOTE: NOTE #15 NO, PLEASE SEE |
| | PREVIOUS NOTES: PLEASE SEE SEE MANY |
| | RECEPTSWHICH ARE ON SM APPL CIRCUITS |
| | WHICH ARE IN AREAS NOT PERMITTED UNDER |
| | NEC 210.52B1 |
| | |
| | 16)NOTE: NOTE #16 OK. |
| | |
| | 17)NOTE: NOTE #17 OK. |
| | |
| | 18)NOTE: NOTE #18 OK, |
| | |
| | 19)NOTE: NOTE #19 NO, SEE PREVIOUS NOTES |
| | #4 OF SECOND SECTION. |
| | MANY METER CENTERS STILL SHOWN AS |
| | "MAINS". |
| | |
| | 20)NOTE: NOTE #20 OK. |
| | |
| | 21)NOTE: NOTE #21 OK. SEE NEW NOTES. |
| | |
| | 22)NOTE: NOTE #22 OK. |
| | |
| | 23)NOTE: NOTE #23 OK. |
| | |
| | 24)NOTE: NOTE #OK. |
| | |
| | 25)NOTE: NOTE #25 OK. |
| | |
| | 26)NOTE: NOTE #26 OK. |
| | |
| | 27)NOTE: NOTE #27 OK. |
| | |
| | 28)NOTE: NOTE #28 OK, HOWEVER SEE NEW |
| | NOTES. |
| | |
| | 29)NOTE: NOTE #29 NO, SPECS SUBMITTED |
| | LIKE PREVIOUS REVIEW, HOWEVER SPECS |
| | SUBMITTED STILL DO NOT CORRELATE WITH |
| | PLANS FOR SIZING. |
| | PLEASE SEE NO SPECS SUBMITTED FOR SUB |
| | BASE FUEL TANK FOR FIRE REVIEW. |
| | |
| | 30)NOTE: NOTE #30, NO, PLEASE SEE RISER |
| | NOTES FOR GENERATOR. |
| | PLEASE ALSO SEE NOTES PERATAINING TO |
| | RISER ETC. |
| | |
| | 31)NOTE: NOTE #31 NO. |
| | PLEASE SEE BRKRS FROM GEN TO ATS AND OCP |
| | LISTED ON NOTES. |
| | PLEASE SEE NEW NOTES ALSO. |
| | |
| | 32)NOTE: NOTE #32 NO, PLEASE SEE THERE |
| | ARE NUMEROUS ITEMS ON ELECTRICAL RISER |
| | DIAGRAM AND NOTES FOR FEEDERS ETC WHICH |
| | DO NOT CORRELATE. |
| | PLEASE SEE NEW NOTES PERTAINING TO |
| | "FEEDER SCHEDULE NOTES" AND "ELECTRICAL |
| | RISER DIAGRAM". |
| | |
| | 33)NOTE: NOTE #33 OK. |
| | |
| | 34)NOTE: NOTE #34, NO, SEE NEW NOTES FOR |
| | EQUIPMENT GROUNDING MISSING ETC. |
| | |
| | 35)NOTE: NOTE #35 NO, SEE PREVIOUS TWO |
| | REVIEWS. |
| | 250.6,250.24,250.110,.250.122 SEE NEW |
| | NOTES. |
| | |
| | 36)NOTE: NOTE #36 OK, HOWEVER PLEASE SEE |
| | 250.104 TO BE LISTED ON GROUNDING |
| | ELECTRODE DETAIL. |
| | PLEASE SEE SHEETS E-19 MAKES REFERENCES |
| | TO CODES THAT GROUNDING SHALL BE |
| | INSATLLED BY, HOWEVER PLEASE SEE FBC |
| | 104.2.1, TECHNICAL CODES SHALL NOT BE |
| | USED IN LEIU OF PROVIDING THE DETAIL ON |
| | PLANS. |
| | |
| | 37)NOTE: NOTE #37 NO, PLEASE SEE THERE |
| | ARE STILL LOCATIONS ON PLANS WHICH STILL |
| | REFERENCE CODES FROM 1996/1999 CODES. |
| | |
| | 38)NOTE: NOTE #38 OK. |
| | |
| | 39)NOTE: NOTE #39 OK, NO 277V SYSTEMS |
| | PRESENT. |
| | |
| | 40)OK |
| | |
| | 41)OK. |
| | |
| | 42)OK. |
| | |
| | 43)OK. |
| | |
| | **************************************** |
| | PLEASE SEE NOTES DIRECTLY TAKEN FROM |
| | "NEW NOTE" ON 2ND REVIEW". |
| | |
| | 1)NOTE: NOTE #1 OK. |
| | |
| | 2)NOTE: NOTE #2 OK. |
| | |
| | 3)NOTE: NOTE #3 NO, PLEASE SEE MANY |
| | AREAS SHOWN AS DINING AND LIVING RM |
| | TOGETHER WHEN "DINING RM/AREA" |
| | DESIGNATION SHOULD BE MOVED TO CORRELATE |
| | WITH CIRCUTING SHOWN ON PLANS. |
| | PLEASE SEE AREAS WHERE A "HALLWAY/FOYER" |
| | AREA RECEPT IS ON SMALL APPLIANCE |
| | CIRCUIT. |
| | PLEASE SEE MANY AREAS REDLINED ON PLANS. |
| | |
| | 4)NOTE: NOTE #4 NO, PLEASE SEE PREVIOUS |
| | NOTES , MANY AREAS ON PLANS WHERE METER |
| | CENTERS ARE STILL SHOWN AS BEING |
| | "MAINS", PLEASE CORRECT. SEE NEW NOTES |
| | ALSO. |
| | |
| | 5)NOTE: NOTE #5, OK, LOAD CALCULATIONS |
| | AND PANEL SCHEDULES NOW SHOW AHU/HEAT |
| | LOADS @125%. PLEASE KNOW: ONLY THE OCP |
| | IS REQUIRED TO BE 125%. HOWEVER, IT IS |
| | PERMISSIBLE TO TO HAVE LOADS FIGURED AT |
| | A HIGHER AMOUNT THAN IS REQUIRED. |
| | NO CORRECTION IS NEEDED. |
| | |
| | 6)NOTE: NOTE #6 OK. |
| | |
| | 7)NOTE: NOTE #7 OK. |
| | |
| | 8)NOTE: NOTE #8 NO, PLEASE SEE MANY |
| | RECEPTS STILL MISSING . PLEASE SEE |
| | PREVIOUS NOTES FROM BOTH REVIEWS. |
| | |
| | 9)NOTE: NOTE #9 OK, SEE ALL SHEETS WERE |
| | SUBMITTED, HOWEVER PLEASE SEE SOME NOTES |
| | PERTAINING TO THESE SHEETS WHICH COULD |
| | NOT REVIEWED ON PREVIOUS SUBMITTAL. |
| | |
| | 10)NOTE: NOTE #10 OK, HOWEVER PLANS SEE |
| | ELECTRICAL RM #1 EAST ELEVATION, ONE |
| | SHOWS 110,000 AND THE OTHER 100,000? |
| | |
| | 11)NOTE: NOTE: OK, ALL ELECTRICAL |
| | REMOVED FROM VAULT. |
| | |
| | 12)NOTE: NOTE #12 NO, SAME COMMENT. |
| | |
| | 13)NOTE: NOTE #13 OK. |
| | |
| | 14)NOTE: NOTE #14 OK. |
| | |
| | 15)NOTE: NOTE #15 OK, HOWEVER SEE NEW |
| | NOTES; |
| | |
| | 16)NOTE: NOTE #16 NO, PREVIOUSLY NOTED |
| | ON THIS REVIEW. |
| | |
| | 17)NOTE: NOTE #17 OK, HOWEVER SEE NEW |
| | NOTES FOR FEED FROM FPL. |
| | |
| | 18)NOTE: NOTE #18 NO, PLEASE SEE ALL |
| | UNPROTECTED CONDUCTORS/BUS-DUCT IS STILL |
| | SHOWN "INSIDE" BLDG. INSTALLATION AS |
| | SHOWN SHALL NOT BE PERMITTED AS SHOWN. |
| | THIS WAS GONE OVER IN MEETING ,YET PLANS |
| | STILL CAME BACK WITH NO CORRECTIONS? |
| | PLEASE SEE 230.70,230.6 ETC. |
| | |
| | 19)NOTE: NOTE #19 NO, PLEASE SEE HDP-2 |
| | STILL SHOWN AS A "SHUNT TRIP".?? |
| | |
| | 20)NOTE: NOTE #20 NO,? PLEASE SEE HDP-2 |
| | IS STILL SHOWN AS GF PROTECTED. PLEASE |
| | ALSO SEE NEW NOTE ABOUT ATS. |
| | PLEASE SEE 230.95,240.13 GF PROTECTION |
| | IS NOT REQUIRED, HOWEVER MAY BE |
| | INSTALLED. PLEASE ATS NOTE: |
| | |
| | 21)NOTE: NOTE #21 OK? NOT NEEDED , |
| | HOWEVER MAY BE DONE. |
| | |
| | |
| | **************************************** |
| | NEW NOTES FOR 3RD REVIEW. |
| | |
| | 1)NOTE: PLEASE SEE ELEVATOR RM #4. |
| | PLEASE SEE STATE ELEVATOR CODE. ELEVATOR |
| | MACHINE ROOM SHALL CONTAIN NO OTHER |
| | EQUIPMENT, USEAGE , ELECTRICAL EQUIPMENT |
| | ETC UNLESS DIRECTLY USED FOR ELEVATOR |
| | EQUIPMENT. |
| | PLEASE SEE ROOM #4, SHOWS "TRASH RM, AND |
| | "MECH RM" THIS IS NOT PERMITTED. |
| | THESE RMS WILL BE REQUIRED TO BE |
| | SEPARATED. |
| | PLEASE ALSO SEE REQUIREMENTS FOR TRASH |
| | RMS UNDER LS 101. |
| | |
| | 2)NOTE: PLEASE CORRELATESIZES OF |
| | SWITCH GEAR MAINS. PLEASE SEE ONE SHEET |
| | SHOWS 3000A'S, RISER SHOWS 4,000A'S? |
| | PLEASE SEE REDLINED PLANS. SG #5? |
| | |
| | 3)NOTE: PLEASE SEE LS 7-9. PLEASE SEE |
| | ALTERNATING CIRCUITS FOR EM LTS IN |
| | STAIRS WILL BE REQUIRED. THIS IS TO |
| | ALLEAVIATE EGRESS AREAS TO BE IN TOTAL |
| | DARKNESS BYT THE TRIPPING OF A SINLGE |
| | BRKR. PLEASE SEE A BATTERY BACK UP |
| | FIXTURE MAY BE INSTALLED AT EVERY OTHER |
| | LEVEL AS AN OPTION. PLEASE SEE EGRESS |
| | HALLWAYS AS SHOWN ON PLANS ALREADY HAVE |
| | BATTERY BACK LTS SHOWN. EVEN IF A BRKR |
| | FROM EDP TRIPS, EGRESS LIGHTNING WILL |
| | STILL BE PROVIDED. |
| | |
| | 4)NOTE: PLEASE SEE SHEET #19 IS NOW |
| | SUBMITTED. PLEASE SEE SD NOTES: |
| | ONE NOTE MENTIONS FOR SD'S TO BE WIRED |
| | TO KITCHEN/BATH LIGHTING CIRCUIT, |
| | HOWEVER CIRCUITING ON PLANS DO NOT |
| | CORRELATE WITH THIS STATEMENT. |
| | PLEASE SEE KITCHEN/BATH LIGHTING |
| | CIRCUITS DO NOT INDICATE REQUIRED ARC |
| | FAULT PROTECTION AS REQUIRED UNDER 2002 |
| | NEC 210.12. PLEASE ADJUST NOTE OR |
| | PLANS/CIRCUITS ETC. |
| | |
| | PLEASE SEE SECOND SD NOTE MENTIONS SD'S |
| | MAY BE WITHIN 20' OF KITCHEN COOKING |
| | APPLIANCE. THIS IS PERMITTED HOWEVER |
| | PLEASE SEE NFPA-72 8-1.4.2, A SPECFIC |
| | TYPE OF SD'S SHALL BE REQUIRED FOR ANY |
| | SMOKE DETECTORS CLOSER THAN 20' TO A |
| | COOKING APPLIANCE. |
| | |
| | 5)NOTE: PLEASE CORRELATE RISER , RISER |
| | NOTESETC, PLEASE SEE RISER, PANEL |
| | SCHEDULES ETC INDICATE BUS-DUCT AND ALOS |
| | INDICATES FEEDERS ETC. |
| | PLEASE SEE NUMEROUS ITMES WHICH DO NOT |
| | CORRELATE. |
| | |
| | A) PLEASE SEE MAINS LISTED ON RISER |
| | DIAGRAM EQUIPMENT SCHEDULE ITME #4? THIS |
| | COULD NOT BE LOCATED ON RISER. |
| | |
| | B) PLEASE SEE MAIN DISC SHOWN AS 150A |
| | FOR ELEVATORS , YET NOTE MENTIONS |
| | 200A'S. |
| | |
| | C)PLEASE SEE FEEDER SCHEDULES AND |
| | EQUIPMENT NOTES DO NOT CORRELATE FOR |
| | MAINS SEC'S OR BUS-DUCT. |
| | |
| | D)PLEASE SEE FEEDER SCHEDULE 5,7,8,9 AND |
| | 10. PLEASE SEE THESE DO NOT CORRELATE |
| | WITH PANEL SCHEDULES FOR FEEDERS, ETC. |
| | PLEASE SEE THESE DO NOT INCLUDE ANY |
| | EQUIPMENT GRNDS? |
| | |
| | E)NOTE:PLEASE SEE SW GR #2 ONLY SHOWS |
| | ONE FEEDER TO MC'S. ETC ETC. |
| | MOST OF THESE ITEMS WERE REDLINED. |
| | |
| | 6)NOTE: PLEASE SEE SEE FEEDER SCHEDULE |
| | MENTIONS ALL FEEDS TO APT UNITS TO BE IN |
| | EMT? PLEASE VERIFY THIS.PLEASE SEE EMT |
| | MAY NOT BE INSTALLED IN CONCRETE. |
| | ONLY IF OVERHEAD. |
| | |
| | 7)NOTE:PLEASE SEE EQUIPMENT GROUNDING |
| | CONDUCTOR SHOWN FROM FPL TO FIRST MEANS |
| | OF DISCONNECT FOR FIRE PUMP. PLEASE SEE |
| | 250.6, 250.24, EQP GRNDS SHALL ONLY BE |
| | INSTALLED "AFTER" THE FIRST MENS OF |
| | DISCONNECT. |
| | |
| | 8)NOTE: PLEASE SEE OTHER CONDUITS ETC ON |
| | RISER MISSING ANY MENTION OF EQUIPMENT |
| | GROUNDING CONDUCTORS. PLEASE SEE FEEDERS |
| | FROM GEN TO FIRE PUMP AND EM ATS, EDP(SW |
| | GR #4). |
| | 250.110, 250.122 |
| | |
| | 9)NOTE: PLEASE SEE ATS FOR EM STAND-BY |
| | IS NOTED AS GFCI PROTECTED? |
| | PLEASE SEE EQUIPMENT PROTECTION WOULD BE |
| | GF PROTECTED, NOT GFCI FOR PERSONNEL |
| | PROTECTION. PLEASE SEE GF PROTECTION OS |
| | NOT REQUIRED ON EM STAND-BY SYSTEMS OF |
| | THIS VOLTAGE AND SIZE. 240.13,230.95 |
| | ETC. THIS IS ONLY NOTED AS TO WHY ? |
| | PLEASE SEE 701.17 FOR "LEGALLY REQUIRED |
| | STAND-BY SYSTEMS". |
| | |
| | 10)NOTE: PLEASE SEE PREVIOUS NOTE FROM |
| | THIRD REVIEW5)D: WHICH MENTIONS |
| | CORRELATION OF FEEDER SCHEDULES. |
| | PLEASE SEE FEEDERS FOR ALL RTU'S, POOL |
| | PANEL. PLEASE SEE EDP'S AND HDP'S PANEL |
| | SCHEDULES AND FEEDERS INDICATED AT THOSE |
| | LOCATIONS. PLEASE CORRELATE. |
| | SEE NEW NOTE IN REF TO POOL PANEL. |
| | |
| | 11)NOTE: PLEASE SEE NOTE #6 ON NOTES |
| | LISTED ON THE UPPER RIGHT HAND CORNER OF |
| | RISER DIAGRAM SHEET. THIS MENTIONS: |
| | "ONLY FOUR ELEVATOR THRU EMERGENCY |
| | GENERATOR"?? |
| | PLEASE CLARIFY AS ONLY ONE ELEVATOR IS |
| | LISTED ON SWITCH GEAR MAIN #4? |
| | PLEASE SEE FIRE DEPARMENT REQUIREMENTS |
| | FOR ELEVATOR ON EM GEN SHALL ALSO BE |
| | STRETCHER ACCESSSIBLE. SEE ANY FIRE |
| | REVIEW NOTES FOR THIS. |
| | |
| | 12)NOTE: PLEASE SEE SWITCH GEARR #4 |
| | INDICATES CONNECTED LOAD OVER 1600 A'S |
| | ON A 2000A MAIN WITH A 2000A FEED FROM |
| | FPL. THIS IS OK, HOWEVER , PLEASE SEE |
| | ATS IS ALSO SHOWN AS HAVING 2000A |
| | CAPACITY, AND SERVICE ENTRANCE |
| | CONDUCTORS FROM FPL SHOWN FOR 2000A'S |
| | YET GENERATOR ONLY SHOWS A 1600A MCB? |
| | PLEASE EITHER INCREASE FEED FROM |
| | GENERATOR TO CORRLELATE WITHALL OTHER |
| | EQUIPMENT TO 2000A'S OR PLEASE PROVIDE |
| | LOAD CALCUALTIONS FOR ANY DERATING. |
| | PLEASE BEAR IN MIND FUTURE POSSIBLE |
| | LOADS OF ANY ADDITIONS. |
| | PLEASE SEE 90.8WHICH REQUIRES PLANS |
| | AND SPECIFICATIONS THAT PROVIDE AMPLE |
| | SPACE IN RACEWAYS, SPARE RACEWAYS, AND |
| | ADDITIONAL SPACES ALLOW FOR FUTURE |
| | INCREASES IN THE USE OF ELECTRICITY. |
| | DISTRIBUTION CENTERS LOCATED IN READILY |
| | ACCESSIBLE LOCATIONS PROVIDE CONVENIENCE |
| | AND SAFETY OF OPERATION. |
| | THE REQUIREMENT FOR PROVIDING THE |
| | EXCLUSIVELY DEDICATED EQUIPMENT SPACE |
| | MANDATED BY 110.26(F) SUPPORTS THE |
| | INTENT OF 90.8(A) REGARDING FUTURE |
| | INCREASES IN THE USE OF ELECTRICITY. |
| | DISTRIBUTION CENTERS SHOULD CONTAIN |
| | ADDITIONAL SPACE AND CAPACITY FOR FUTURE |
| | ADDITIONS AND SHOULD BE CONVENIENTLY |
| | LOCATED FOR EASY ACCESSIBILITY. |
| | THIS SHOULD ALSO BE TAKEN IN NOTE FOR |
| | ALL SERVICE EQUIPMENT AND THE |
| | POSSIBILITY OF ANY FUTURE EXPANTION. |
| | PLEASE SEE NO LOAD CALCULATIONS WERE |
| | SUBMITTED FOR MAINS 4 AND 5. IF LOAD |
| | CALCULATIONS ARE SUBMITTED, PLEASE SHOW |
| | ALL CONTINUOUS LOADS (3OR MORE HOURS) AT |
| | 125%. 215.3,100,230.42 ETC. |
| | |
| | 13)NOTE: PLEASE SEE POOL PANEL IS NOW |
| | SHOWN ON RISER AS NOTED IN NEW NOTE #10, |
| | HOWEVER PLEASE SEE NO POOL PANEL |
| | SCHEDULE WAS SUBMITTED? PLEASE ALSO |
| | INCLUDE LOADS ON PANEL. PLEASE SEE |
| | PREVIOUS NOTE ABOUT FEEDERS LISTED ON |
| | RISER SCHEDULES, RISER AND HDP-3. |
| | |
| | 14)NOTE: PLEASE SEE MANY OF THE ABOVE |
| | ITEMS AS NOTED HAVE BEEN REDLINED ON |
| | PLANS AT AREAS OF NOTES. THIS IS IN NO |
| | WAY EVERY LOCATION OF SAID COMMENTS. |
| | |
| | 15)NOTE: PLEASE BE SURE TO SEE ANY |
| | POSSIBLE COMMENTS FROM OTHER REVIEWERS |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | IE: DOOR SWINGS, EGRESS ETC. |
| | |
| | 16)NOTE: PLEASE KNOW, A RESPONSE LETTER |
| | LISTING REVIEWERS COMMENTS AND ACTION |
| | TAKEN BY DESIGN TEAMWOULD HELP IN THE |
| | REVIEW PROCESS. |
| | |
| | 17)NOTE: PLEASE REMOVE ANY OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. |
| | IT IS SUGGEESTED AN ADDITIONAL MEETING |
| | BE SET UP TO GO OVER ALL COMMENTS ONCE |
| | ALL REVIEWS ARE DONE FOR TRADES. |
| | IF THERE ARE ANY QUESTIONS, PLEASE DO |
| | NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |