Text |
| 2005-08-14 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04110228 |
| | ADD: 516 BANYAN BLVD |
| | "THE PLACE VIA CLEMATIS" |
| | CONT:THE OPERIS GROUP, CORP. |
| | TEL: (305)624-0245 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 3RD REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2)YOUR RESPONCE TO THIS COMMENT IS |
| | BMD/LLC, PLEASE PROVIDE THE RECORDED |
| | DOCUMENT OR IF IT IS A NEW PLAT PROVIDE |
| | THE PLAT. |
| | THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES |
| | BETWEEN THE LOTS WHICH COMBINE TO FORM |
| | 'THE SITE'.A 'UNITY OF TITLE' SHALL |
| | BE RECORDED AT THE COUNTY COURTHOUSE. |
| | SUBMIT A COPY OF THE RECORDED 'UNITY OF |
| | OF TITLE' DOCUMENT SO THAT FBC TABLE |
| | 600 BOUNDARY LINE REQUIREMENTS MAY BE |
| | DEEMED NOT APPLICABLE. |
| | |
| | 3)THIS DOCUMENT MUST BE PROVIDED AS PART |
| | OF THE PERMIT PACKAGE BEFORE THE PERMIT |
| | WILL BE ISSUED. FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 |
| | FT IN HEIGHT, OR WHICH HAS AN ASSEMBLY |
| | OCCUPANCY CLASSIFICATION AS DEINED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | SRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER |
| | OF RECORD. THE "STRUCTURAL INSPECTION |
| | PLAN" MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A |
| | BUILDING PERMIT FOR THE CONSTRUCTION OF |
| | A THRESHOLD BUILDING. THE PURPOSE OF THE |
| | SRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND |
| | SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH |
| | THE PERMITTED DOCUMENTS. |
| | |
| | 4)RESPONCE TO THIS COMMENT IS SEE SHEET |
| | 1 OF 8? AGAIN THIS DOCUMENT MUST BE PART |
| | OF THE PERMIT PACKAGE BEFORE ISSUANCE OF |
| | THIS PERMIT PRIOR TO THE ISSUANCE OF |
| | THIS PERMIT. |
| | WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 5) W.P.B. AMENDMENT 105.13.4.4 ALL |
| | PLANS FOR THE BUILDING WHICH ARE |
| | REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CON- |
| | TAIN A STATEMENT THAT, TO THE BEST OF |
| | THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, |
| | THE PLANS AND SPECIFICATIONS COMPLY WITH |
| | THE APPLICABLE FIRE-SAFETY STANDARDS AS |
| | DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | THIS IS A THRESHOLD BUILDING THIS |
| | STATEMENT IS TO BE ON ALL SHEETS |
| | INCLUDING STRUCTURAL SHEETS. SEE |
| | REQUIREMENTS FOR THE MEP DRAWINGS TO SEE |
| | IF EACH OF THESE TRADES QUALIFY AS |
| | THRESHOLD BUILDING, IF SO THEY ALSO MUST |
| | HAVE THE SAME STATEMENT ON ALL PAGES. |
| | |
| | |
| | 6) FBC* F102.2.7ARCHITECTURAL TRIM, |
| | TRELLISES, ON BUILDINGS LOCATED IN THE |
| | FIRE DISTRICT,SHALL BE CONSTRUCTED OF |
| | APPROVED NON-COMBUSTIBLE MATERIALS OR |
| | FIRE RETARDANT TREATED WOOD.ANNOTATE |
| | THE PLANS TO DEMONSTRATE COMPLIANCE. |
| | A PAINT ON THE SURFACE PRODUCT WILL NOT |
| | BE ACCEEPTED BY THE BUILDING OFFICIAL. |
| | |
| | A NOTE WAS ADDED INDICATING TRELLISES |
| | SHALL BE OF ALUMINUM BUT THE ORIGINAL |
| | NOTE WOOD TRELLISES IS STILL THERE, |
| | "DELETE THE WOOD TRELLIS NOTE!!"ALSO |
| | DELETE THE NOTES FOR FIRE RETARDANT |
| | PAINT ON WOOD TRELLISES. |
| | |
| | |
| | |
| | 7) FBC* F102.2.8PERMANENT CANOPIES/ |
| | AWNINGS AND THEIR SUPPORTS, ON BUILDINGS |
| | LOCATED IN THE FIRE DISTRICT, SHALL BE |
| | OF NON-COMBUSTIBLE MATERIAL, FIRE |
| | RETARDANT TREATED WOOD, WOOD OF TYPE |
| | III SIZES OR OF 1-HOUR RESISTANT |
| | CONSTRUCTION.ANNOTATE THE PLANS TO |
| | DEMONSTRATE COMPLIANCE. THE BUILDING |
| | OFFICIAL HAS RULED THAT A PAINT ON |
| | RETARDANT WILL NOT BE ACCEPTABLE FOR |
| | WOOD PRODUCTS. AGAIN DELETE ALL NOTES |
| | ABOUT WOOD TRIM ON THE EXTERIOR OF THE |
| | BUILDING.1404.1.1 ARCHITECTURAL TRIM ON |
| | BUILDINGS OF TYPE I, II AND IV |
| | CONSTRUCTION NOT MORE THAN THREE STORIES |
| | OR 40 FT (12.2 M) HIGH MAY BE OFTYPE |
| | VI CONSTRUCTION, THIS BUILDING IS OVER |
| | 40' TALL. |
| | |
| | |
| | 8) FBC* F102.2.4ROOF COVERINGS, ON |
| | BUILDINGS LOCATED IN THE FIRE DISTRICT, |
| | SHALL CONFORM TO THE REQUIREMENTS OF |
| | CLASS A OR B ROOF COVERINGS, AS DEFINED |
| | IN FBC 1505.ANNOTATE THE PLANS TO |
| | DEMONSTRATE COMPLIANCE. THE MIAMI-DADE |
| | REPORT NEOGARD WAS NOT TEST FOR FIRE |
| | CLASSIFICATION. NO REPORTS WERE |
| | SUBMITTED FOR ASPHALT UNDERLAYMENT OR |
| | ROLL ROOFING.NO SUBMITTALS FOR THE |
| | FINISH ROOF TILE. |
| | |
| | *** ALSO NOTE THIS IS A TYPE II |
| | BUILDINGWHERE THE PLYWOOD ROOF |
| | SHEATHING IS SPECIFIED ( S2.1 DETAIL |
| | 4)SEE FOOTNOTE (E) TABLE 600, BUILDINGS |
| | NOT OVER TWO STORIES APPROVED FIRE |
| | RETARDANT TREATED WOOD MAY BE USED. |
| | |
| | |
| | 9) THE PLANS DO NOT PROVIDE |
| | INFORMATION FOR WORK TO BE COMPLETED IN |
| | THE PUBLIC PROPERTY. SEE CHAPTER 33, |
| | WHERE COVERED WALKWAYS WILL BE REQUIRED |
| | 3304, CONSTRUCTION OF WALKWAYS, FENCES |
| | AND PROTECTIVE COVERINGS. AGAIN THE NOTE |
| | ONLY COVERS THE UNDERMINING OF THE RIGHT |
| | OF WAY. NO PRECAUTIONS WERE TAKEN THE |
| | SHEET PILE ARE NOT IN AND THE ALEY WAY |
| | IS BEING ERODED AWAY, NO PRECAUTONS TO |
| | DATE HAVE BEEN TAKEN. |
| | |
| | |
| | |
| | 10) CONCERNS THAT TABLE 600 ISSUES EXIST |
| | SINCE THE BUILDING IS ON THE PROPERTY |
| | LINE AND THE ALLEY IS ONLY 14' WIDE. |
| | SINCE THE STRUCTURE IS DIRECTLY ON THE |
| | PROPERTY LINE TABLE 600 ISSUES OCCUR. |
| | PROVIDE DOCUMENTATION AS TO WHAT THE |
| | VARIANCE WAS GRANTED FOR. |
| | |
| | UNTIL COPIES OF THE GRANTED VARIANCE ARE |
| | RECEIVED NO COMMENT ON 10AOR B. |
| | |
| | |
| | 10C) PROVIDE THE EQUIVALENT THICKNESS |
| | REQUIRED FOR BEARING AND NONBEARING |
| | CONCRETE BLOCK. SEE 709.3.1. DO NOT |
| | PROVIDE A UL RATING BUT THE ACTUAL |
| | EQUIVALENT THICKNESS FROM THE BLOCK |
| | MANUFACTURE FOR2HR, 3 HR & 4HR WALLS. |
| | |
| | |
| | |
| | 11 SEE DOOR SCHEDULE A.35 IS MISSING |
| | PROTECTION OF OPENINGS IN INTERIOR |
| | WALLS,( 705.1.2) SEE TABLE 705.1.2 FOR |
| | THE REQUIRED RATINGS.PLANS INDICATE THIS |
| | TO BE A LOUVERED DOOR, PLANS ONLY |
| | INDICATE FIRE RATED NO RATING, INDICATE |
| | HOW RATING WILL BE ACHIEVED ON A |
| | LOUVERED DOOR. |
| | |
| | |
| | 12) ADDITIONAL INFORMATION REQUIRED, |
| | PLANS HAVE A COMMENT STATING "A SEPERATE |
| | PERMIT REQUIRED", SHEET A35 FOR WINDOWS |
| | AND DOORS. PRODUCT APPROVALS HAVE BEEN |
| | SUBMITTED, WHAT ISN'T CLEAR IS IF THESE |
| | SUBMITTALS ARE TO BE PART OF THIS |
| | PERMIT. |
| | ****SINCE THE LAST REVIEW THE BUILDING |
| | OFFICIAL HAS MADE ME AWARE THAT FOR AN |
| | ENCLOSED BUILDING WE SHALL HAVE ALL THE |
| | INFORMATION REQUIRED ( WINDOWS, DOORS |
| | AND ASSOCIATED ROOFING COMPONENTS) |
| | BEFORE A PERMIT TO START CONSTRUCTION |
| | SHALL BE ISSUED.**** |
| | |
| | 12A) THE DOORS OR WINDOWS THAT FACE THE |
| | SOUTH THAT ARE WITHIN 15' OF THE |
| | PROPERTY LINE WILL REQUIRE OPENING |
| | PROTECTIVES. ONCE IN RECEIPT OF THE |
| | VARIANCE THIS MAY BE RESOLVED. |
| | |
| | 12B) 1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR |
| | PROTECTED WITH AN IMPACT RESISTANT |
| | COVERING MEETING THE REQUIREMENTS OF |
| | SSTD 12, ASTM E 1886 AND ASTM E 1996 OR |
| | MIAMI-DADE. |
| | 1) GLAZED OPENINGS LOCATED WITHIN 30 |
| | FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST.SEE COPY OF CITY OF |
| | W.P.B. INTERPRETATION OF HURRICANE |
| | STANDARDS FOR LARGE PROJECTS. |
| | |
| | 12C) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 13)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS- FIXED OR OPERATABLE |
| | B) PANELWALL-STOREFRONT |
| | C) GLAZED EXTERIOR DOORS |
| | D) SOLID EXTERIOR DOORS |
| | E) MULLIONS |
| | F) VENTS/ LOUVERS |
| | G) STRUCTURAL COMPONENTS- TRUSS |
| | ANCHORS |
| | CONCRETE ADMIXTURES, RAILINGS |
| | H) ROOFING PRODUCTS- AND INSULATION. |
| | THE ABOVE IS MENTIONED AS TO |
| | REQUIREMENTS TO OBTAIN A BUILDING |
| | PERMIT. THE NOTES FOUND ON A.35 NOTE |
| | FOR WINDOWS AND STOREFRONT ARE TO BE |
| | UNDER A SEPERATE PERMIT. |
| | ****SINCE THE LAST REVIEW THE |
| | BUILDING OFFICIAL HAS MADE ME AWARE THAT |
| | FOR AN ENCLOSED BUILDING WE SHALL HAVE |
| | ALL THE |
| | INFORMATION REQUIRED ( WINDOWS, DOORS |
| | AND ASSOCIATED ROOFING COMPONENTS) |
| | BEFORE A PERMIT TO START CONSTRUCTION |
| | SHALL BE ISSUED.**** |
| | |
| | 14) THE 4 GARAGE OPENINGS ON THE SOUTH |
| | SIDE OF THE BUILDING DO NOT PROVIDE THE |
| | PRESSURES (POS/NEG) ASSSOCIATED WITH THE |
| | BUILDING? 1606.6/ ASCE 7-98. THE GARAGE |
| | DOOR REPORTS MAY OR MAY NOT WORK BECAUSE |
| | OF LOW PRESSURES?NO FL COVERSHEET MAY |
| | ALSO REQUIRE A LOCAL PRODUCT APPROVAL. |
| | THIS MAY ALSO CHANGE ON THE RESULTS |
| | OF THE VARIANCE, ORIGINALLY A CHAINED |
| | TYPE GATE OF GARAGE DOOR WAS CONSIDERED. |
| | IF NOT USING THE GARAGE DOOR REMOVE FROM |
| | PACKAGE, THE SAME WITH THE FIRELITE |
| | GLASS. |
| | |
| | 15) THE WINDOW REPORTS SUBMITTED HAVE |
| | MULTIPLE TYPES OF GLAZING THAT MAY BE |
| | USED, HIGHLIGHT OR INDICATE THE SYSTEM |
| | USED, ALSO LOOK AT THE HEIGHT/WIDTH AND |
| | PRESSURES, END ZONES -123, WILL THERE BE |
| | ONE TYPE OF GLAZING FOR END ZONES AND |
| | ANOTHER FOR INTERIOR ZONES IF SO |
| | INDICATE? |
| | |
| | 16) THE R C ALUMINIUM REPORT SUBMITTED |
| | IS FOR LARGE MISSLE TESTING ONLY NOT |
| | TESTED FOR PRESSURES. |
| | A) 2400 ST SLIDING GLASS DOOR |
| | B) "FX-345" IF IN END ZONE WILL NOT MEET |
| | THE REQUIRED -123.8 |
| | C) RD 45 ONLY GOOD FOR +- 80 WILL NOT |
| | MEET END ZONES |
| | D) STEELCRAFT OUTSWING +- 65 LOW |
| | PRESSURE FOR INTERIOR ZONES + END ZONES. |
| | |
| | |
| | 17) THE R C ALUMINIUM ENTRY DOOR LMI |
| | INDICATES MAXIMUM DESIGN PRESSURES GOOD |
| | FOR +/- 80, BUT END ZONES INDICATE -123. |
| | |
| | 18) STEELCRAFT DOORS INDICATES MAXIMUM |
| | DESIGN PRESSURE OF +- 65 THESE DOORS |
| | WILL BE USED ON THE ROOF TOP WHERE THE |
| | PRESSURES WILL BE -123. |
| | |
| | 19) ON THE ROOF TOP DECK THE RESTROOMS |
| | ARE USING INTERIOR DOORS, DOOR# 15 IS A |
| | INTERIOR DOOR. |
| | NOTE NO OTHER PRODUCT APPROVALS WERE |
| | SUBMITTED. |
| | |
| | 20) A-37 DETAILS 6 & 7, SOFFITS, DROP |
| | CEILINGS, OR TRAY CEILINGS ALL INDICATE |
| | THE SAME PHRASE," TO BE PROPERLY |
| | ANCHORED TO THEUNDERSIDE OF STRUCTURE" |
| | BUT THE DESIGN TEAM LACKS INDICATING HOW |
| | TO ACHIEVE THIS TASK? |
| | 104.2.1 W.P.B. ADMINISTRATIVE CODE |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR |
| | OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. |
| | SUCH INFORMATION SHALL BE SPECIFIC AND |
| | THE TECHNICAL CODES "SHALL NOT BE CITED |
| | AS A WHOLE OR IN PART, NOR THE TERM |
| | "LEGAL" OR ITS RQUIVALENT BE USED AS A |
| | SUBSTITUTE FOR SPECIFIC INFORMATION". |
| | |
| | 21) TYPE II CONSTRUCTION 604 REQUIRES |
| | STRUCTURAL MEMBERS TO BE NON |
| | COMBUSTIBLE. |
| | A.15 WOOD TRELLIS EIGHTHFLOOR TO BE |
| | NONCOMBUSTIBLE,1404.1.1 ARCHITECTURAL |
| | TRIM ON BUILDINGS OF TYPE I, II AND IV |
| | CONSTRUCTION NOT MORE THAN THREE |
| | STORIES OR 40 FT (12.2 M) HIGH MAY BE OF |
| | TYPE VI CONSTRUCTION.THIS BUILDINGS MEAN |
| | ROOF THEIGHT IS 90FT. |
| | A.20 THE POOL HOUSE, STAIR AND |
| | ELEVATION SHEETS INDICATE WOOD RAFTERS. |
| | A.24 WALL SECTIONS A&D INDICATE THE USE |
| | OF 5/8" CDX PLYWOOD FOR ROOF SHEATHING. |
| | ALSO 2X6 WOOD FACIA OVER 1X8????? |
| | TYPE II CONSTRUCTION, TABLE 600 ROOFS TO |
| | BE 1HR PROTECTED, NONCOMBUSTIBLE. |
| | |
| | 22) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | FOR THE POOL HOUSE AND ASSOCIATED |
| | STRUCTURES ATOP THE BUILDING, NO |
| | INFORMATION WAS SUBMITTED TO BE ABLE TO |
| | DO A THROUGH PLAN REVIEW!!!!!!!! ROOF |
| | FRAMING PACKAGE FOR POOL DECK |
| | STRUCTURES. THE ONLY ITEM THE POOL |
| | CONTRACTOR WILL BE PERMITING IS THE |
| | PLUMBING AND ELECTRICAL.STRUCTURAL |
| | DETAILS FOR THIS DECK TO BE PART OF THE |
| | STRUCTURAL PLANS. |
| | |
| | S-1.7A/S-1.7B POOL DECK PLANS DO NOT |
| | INDICATE STRUCTURAL DETAILS FOR THE |
| | STRUCTURESLOCATED ON THIS FLOOR, PLANS |
| | INDICATE LIGHT GAUGE STEEL TRUSSES. THE |
| | ENGINEER OF RECORD TO DESIGN THE |
| | MAGNITUDE OF LOADS ARE TO BE RESISTED, |
| | UPLIFT, GRAVITY AND LATERAL LOADS.ALSO R |
| | THE COLUMN FRAMING FOR THE BREEZEWAYS. |
| | 1606.1.3 ANCHORAGE AGAINST |
| | OVERTURNING, UPLIFT AND SLIDING. |
| | STRUCTURALMEMBERS AND SYSTEMS, AND |
| | COMPONENTS AND CLADDING IN A BUILDING OR |
| | STRUCTURE SHALL BE ANCHORED TO RESIST |
| | WIND-INDUCED OVERTURNING, UPLIFTAND |
| | SLIDING AND TO PROVIDE CONTINUOUS LOAD |
| | PATHS FOR THESE FORCES TO THE |
| | FOUNDATION.WHERE A PORTION OF THE |
| | RESISTANCE TO THESE FORCES IS PROVIDED |
| | BY DEAD LOAD, THE MINIMUM DEAD LOAD |
| | LIKELY TO BE IN PLACE DURING A DESIGN |
| | WIND EVENT SHALL BE USED. |
| | |
| | 23) STAIRWELLS INDICATE HOW PLANS ARE TO |
| | COMPLY WITH 11-4..4.2 HEADROOM.THIS |
| | SECTION OF THE CODE DEALS WITH THE BLIND |
| | ON THE BOTTOM OF THE STAIRWELL WALKING |
| | IN UNDERNEATH THE STAIRS AND CAUSING |
| | INJURY TO THEIR HEAD BECAUSE THIS AREA |
| | BENEATH THE STAIRWAY WAS NOT ENCLOSED OR |
| | BLOCKED OFF. |
| | SEE THIS SECTION OF THE CODE WHAT IS |
| | REQUIRED!!!!!!!! |
| | |
| | 24) SHOW COMPLIANCE WITH 412.5 SMOKE |
| | CONTROL, M-16 SMOKE ZONE CONTROLS/ ZONE |
| | II, PLANS INDICATE THE USE OF |
| | PRESSURIZATION, THIS STILL DOESN'T |
| | REMOVE SMOKE, SEE 412.5. |
| | |
| | 25) COMMEENT # 28 FROM THE PEVIOUS |
| | REVIEW: |
| | BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 25) COMMEENT# 29 FROM THE PREVIOUS |
| | REVIEW, PLEASE PULL THE ARCHITECTURAL |
| | AND STRUCTURAL SHEETS OUT TO FORM THERE |
| | OWN ROLL |
| | ** TO DATE THIS HAS NOT BEEN COMPLETED** |
| | |
| | 26) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| | WHICH REQUIRES NEW PLANS IN ORDER TO |
| | ADDRESS THE ABOVE COMMENTS, THE OLD |
| | SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| | REMAINING OLD SHEETS, TO FORM A SET OF |
| | 'OLD/VOID SHEETS', FOR COMPARISON OF |
| | REVISIONS WHEN REVIEWING THE RESUBMITTED |
| | PLANS. |
| | ***************TO DATE THIS HAS NOT BEEN |
| | COMPLETED, NONE OF THE OLD REVISED PLANS |
| | HAVE BEEN SUBMITTED******************** |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |