| Date |
Text |
| 2005-05-19 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | FHA-98 DESIGN MANUAL |
| | |
| | A) COMMENTS FROM PREVIOUS REVIEW THAT |
| | HAVE NOT BEEN ADDRESSED, OR NOT |
| | ADDRESSED PROPERLY. THE COMMENT NUMBER |
| | WILL REMAIN THE SAME AS THE FIRST |
| | REVIEW: |
| | 1) SHTS I-1, & I-2 FIRM LICENSE NUMBER |
| | REQUIRED ON THE TITLE BLOCK, SIGNATURE |
| | REQUIRED, AND PRINTED NAME REQUIRED. FAC |
| | 61G1-16.004(2)(5)(6), 61G1-16.003 AND FS |
| | 481.219. - SUBMIT PROOF OF A LEGAL |
| | SIGNATURE IN THE FORM OF A DRIVERS |
| | LICENSE, VOTERS REG. CARD ECT., AND |
| | SUBMIT A SIGNED/SEALED/DATED NOTORIZED |
| | LETTER WITH YOUR LEGAL SIGNATURE FOR OUR |
| | FILES. (TITLE BLOCK REQD ON LETTER). |
| | 2) SHT I-1, AN RPZ BACKFLOW, INSTALLED |
| | BY A LICENSED PLUMBING CONTRACTOR, IS |
| | REQUIRED FOR THE IRRIGATION SYSTEM. SHOW |
| | THE LOCATION ON THE IRRIGATION PLANS. |
| | SECTIONS 608.13.2 & 104.2.1. |
| | 3) SHTS A-11 & A-12 SHT INDEX STATES |
| | PARTIAL 3RD-7TH FLOOR PLAN 1, BUT NOTE 5 |
| | STATES 3RD-5TH FLOOR PLAN. PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | 4) SHTS A-9 & A-15 SUBMIT CALCULATIONS |
| | FOR PRIMARY AND SECONDARY ROOF DRAINS |
| | PER SECTIONS 1106, & 1107 AND ALL |
| | SUBSECTIONS. SHOW SF OF EACH AREA WITH |
| | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS AND ROOF AREA FROM ABOVE THAT |
| | DRAINS TO THE ROOF FROM ABOVE ADDED TO |
| | THE SF IN THE CALCULATIONS. SHOW THE |
| | LOCATION OF ALL PRIMARY AND SECONDARY |
| | ROOF DRAINS AND THE SCUPPERS. ALSO SEE |
| | SHTS A-17 & A-18. THIS APPLIES TO THE |
| | ROOF DECK AREAS AS WELL. |
| | 5) SHTS A-9 & A-15 SHOW THE LOCATION AND |
| | SIZE OF ALL SECONDARY ROOF DRAINS & |
| | SCUPPERS. SECTION 104.2.1. |
| | 6) SHTS A-15 & A-16 SUBMIT CALCULATIONS |
| | FOR MINIMUM FACILITIES PER TABLES 1003.1 |
| | AND 403.1. SHOW THE SF OF EACH COMMON |
| | AREA, AND THE TOTAL COMMON AREA IN THE |
| | CALCULATIONS. |
| | 7) ARCHITECTURAL SHEETS, THE DATE |
| | PREPARED AND THE PRINTED NAME OF THE |
| | PERSON RESPONSIBLE FOR THE DOCUMENT ARE |
| | REQUIRED PER FAC 61G1-16.004(4)(6) AND |
| | FS 481.2055. |
| | 8) SHTS A-30, A-31, & A-32 INDICATE |
| | SPECIFICATION "A" OR "B" FOR EACH UNIT |
| | OR BATHROOM AS REQUIRED ON PAGE 7.35 OF |
| | THE FHA DESIGN MANUAL. |
| | 9) SHTS A-30, A-31, & A-32 SHOW THE SIZE |
| | OF THE OPENINGS FOR ALL COVERED WATER |
| | CLOSETS. MINIMUM 33" REQUIRED. SEE PAGES |
| | 6.5 AND 6.7 OF THE FHA DESIGN MANUAL. - |
| | THE 18" FROM THE WALL TO THE CENTERLINE |
| | OF THE W/C IS AN ABSOLUTE MEASURMENT. |
| | SEE FIGS PAGE 6.3 & 6.5. |
| | 10) SHT A-33 MENS AND WOMENS RESTROOMS, |
| | SHOW CLEAR FLOOR SPACE FOR EACH |
| | ACCESSIBLE FIXTURE. SECTIONS 11-4.16.2, |
| | 11-4.19.3, & 11-4.22.3. THE TURNING AREA |
| | SHALL BE SHOWN IN THE TOILET ROOM, NOT |
| | IN THE ACCESSIBLE STALL. ALSO SHOW WATER |
| | CLOSET HEIGHT PER 11-4.16.3. GRAB BAR |
| | HEIGHT MAX. 36", SHOWN AS 48" ON DETAIL |
| | BEHIND W/C. SHOW FLUSH CONTROL 11-4.16.5 |
| | SHOW URINAL HEIGHT 11-4.18.2. THE |
| | CENTERLINE OF THE W/C SHALL BE 18" TO |
| | THE WALL FROM THE CENTERLINE OF THE |
| | FIXTURE, NOT 20" AS SHOWN. (SEE FIG. 28) |
| | FOR THE LAVS SHOW KNEE CLEARANCE |
| | 11-4.19.2, FOR THE SHOWER SHOW CONTROLS |
| | 11-4.21.5, SHOWER UNIT 11-4.21.6, AND |
| | CURB HEIGHT 11-4.21.8. |
| | 11) NOT USED |
| | 12) SHT A-33 DETAIL #1 IN BOTH THE MEN'S |
| | AND WOMEN'S RESTROOMS. THE DOUBLE LAVS |
| | TO BE 34" IN HEIGHT AND HAVE A CLEARANCE |
| | OF 29". SEE FIG 31. SECTION 11-4.19.2. |
| | 13) A DRINKING FOUNTAIN IS REQUIRED IN |
| | THE COMMON AREA. TABLE 403.1. SUBMIT A |
| | DETAIL COMPLYING WITH SECTIONS 11-4.15 |
| | AND ALL SUBSECTIONS & 11-4.1.3(10)(A) |
| | FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | 14) SHT A-36 SHOW HEIGHT AND WIDTH OF |
| | SCUPPER OPENINGS ON THE DETAIL. SECTION |
| | 104.2.1. |
| | 15) A PROFESSIONAL ENGINEER SHALL SIGN |
| | HIS NAME. INITIALS ARE NOT APPROVED PER |
| | FBPE RULING. SUBMIT AN EXAMPLE OF THE |
| | ENGINEERS LEGAL SIGNATURE BY WAY OF |
| | DRIVERS LICENSE, VOTERS REG. ECT., AND A |
| | SIGNED, SEALED, DATED, NOTORIZED LETTER |
| | WITH TITLE BLOCK INDICATING YOUR LEGAL |
| | SIGNATURE FOR OUR FILES. |
| | 61G15-23.002(1)(2) AND FS 471.025. THIS |
| | IS FOR ALL ENGINEERED SHEETS. |
| | 16) ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME, LICENSE NUMBER & CERTIFICATE |
| | OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS ON EACH SHEET. FAC |
| | 61G15-23.002(2). (WHITE OUT USED ON THE |
| | PLANS IS NOT APPROVED PER SECTION |
| | 104.2.1.3. |
| | 17) SHTS P-1 & P-2 PD'S SIZING AND |
| | PIPING SIZING ARE NOT CORRECT FOR ALL |
| | PD'S. RECHECK SIZING PER TABLES 1106.2 & |
| | 1106.3. SHOW ALL SF AND PIPE SIZES. |
| | (THIS HAS NOT BEEN ADDRESSED, AND NEW |
| | SHEETS P-1 & P-2 WERE NOT SUBMITTED). |
| | 18) SUBMIT MANUF. SPECIFICATION SHEETS |
| | FOR ELEVATOR SUMP PUMPS AND THE STORM |
| | WATER SUMP PUMPS. PUMP INFORMATION SHALL |
| | SHOW THE LISTING. SECTION 303.4. |
| | (SUBMITTALS NOT FOUND). |
| | 19) SHTS P-3 & P-4 PIPE SIZING NOT |
| | CORRECT FOR EMERGENCY ROOF DRAIN PIPING, |
| | (SECONDARY ROOF DRAINS). SEE TABLES |
| | 1106.2 & 1106.3. NO SF SHOWN FOR PD'S AT |
| | COL. LINE 5/G-F1 AND COL. LINE 6/F-E2. |
| | PD BETWEEN COLS. 8.1 & 8.3 NORTH OF |
| | STAIRWAY #2 NOT ADDED TO THE SYSTEM. |
| | DOUBLE CHECK ALL PIPE SIZES AND SHOW |
| | ADDITION OF ALL SF AS THEY ACCUMULATE IN |
| | THE STORM BLDG. DRAIN. SECTION 104.2.1. |
| | *** NEW COMMENT ** (ON PD LINE 8"PD |
| | (88185SF) NOTHING IS SHOWN ADDED TO |
| | 10713SF) CLARIFY. - ALL PD LINES REQUIRE |
| | A CLEANOUT AS LINE EXITS BLDG. |
| | 27) SHT P-5 CHECK ALL PIPE SIZING ON THE |
| | STORM SYSTEM AND SHOW ALL PIPE SIZES. |
| | SECTION 104.2.1. & TABLES 1106.2 & |
| | 1106.3. |
| | 34) SHT P-11AUXILLARY HORIZONTAL DRAIN |
| | PIPE SIZE NOT CORRECT. TABLE 1106.3. - |
| | NO RESPONSE NOTED. SHEET VOIDED BUT NO |
| | NEW SHEET SUBMITTED. |
| | 35) THE TRASH CHUTE BEQUIRES AN "N-36" |
| | VACUUM BREAKER FOR BACKFLOW PROTECTION. |
| | SECTION 608.13.6. NO RESPONSE. SHEET |
| | VOIDED BUT NO NEW SHEET SUBMITTED. |
| | 36) SHT P-12 AUXILLARY HORIZONTAL DRAIN |
| | PIPE TO BE SIZED PER TABLE 1106.3. NO |
| | RESPONSE. SHEET VOIDED BUT NO NEW SHEET |
| | SUBMITTED. |
| | 37) SHTS P-13, & P-14 AUXILLARY ROOF |
| | DRAIN NEAR POOL SHALL NOT BE A TRIPPING |
| | HAZARD. PLEASE SUBMIT A DETAIL FOR S/27, |
| | S/28, S/29, & S/30 SECONDARY DRAINS. |
| | SECTION 104.2.1. NO RESPONSE NOTED. SHT |
| | VOIDED, BUT NO NEW SHEET SUBMITTED. |
| | 38) SHT P-22 NO WATER SUPPLY SHOWN TO |
| | THE TRASH ROOM FOR THE TRASH CHUTE. |
| | PLEASE SHOW ON PLANS. SECTION 104.2.1. |
| | NO RESPONSE NOTED. SHEET VOIDED, BUT NO |
| | NEW SHEET SUBMITTED. |
| | 39) SHTS P-24, P-25, P-26, P-27, & P-28 |
| | DO NOT MEET CODE REQUIREMENTS. IN MANY |
| | CASES THESE ARE THE CODE ISSUES NOT |
| | ADDRESSED. - THESE COMMENTS NOW APPLY TO |
| | SHTS 23, 29, 30, & 31 AS NEW RISERS HAVE |
| | BEEN SUBMITTED, AND SHEET INFORMATION |
| | HAS CHANGED. |
| | A. OFFSET VENTS ARE REQUIRED WHEN |
| | HORIZONTAL OFFSET ARE USED. SECTION 915. |
| | RESPONSE NOT APPROVED. OFFSET VENTS |
| | SHALL BE SHOWN ON THE RISER DIAGRAMS. |
| | SEE SECTION 104.2.1. |
| | B. NO HORIZONTAL DRY VENTS. SECTION |
| | 905.3. |
| | C. STACK DRAIN SHALL CONNECT DOWNSTREAM |
| | OF BATHROOM GROUP FIXTURES. SECTION |
| | 909.1 |
| | D. KITCHEN SINK SHALL NOT DRAIN THROUGH |
| | THE WET VENT. SECTION 909.1 |
| | E. MAIN VENT REQUIRED AT TOP OF STACKS. |
| | SECTION 903.1. |
| | F. CLEANOUTS REQUIRED AT THE BASE OF |
| | EACH STACK. SECTION 708.3.4. |
| | G. NO HORIZONTAL BRANCH CONNECTIONS TO |
| | A HORIZONTAL STACK OFFSET. SECTIONS |
| | 711.2 & 711.3. |
| | H. VENTING REQUIRED 901.2.1. |
| | I. (NEW COMMENT) EVERY VENT STACK SHALL |
| | CONNECT TO THE BASE OF THE DRAINAGE |
| | STACK. THE VENT STACK SHALL CONNECT AT |
| | OR BELOW THE LOWEST HORIZONTAL BRANCH. |
| | SECTION 903.4 |
| | J. STACK INSTALLATION 910.2 |
| | THE RISERS ARE NOT CLEAR AS TO THEIR |
| | INTENT. CHECK ALL RISERS FOR CODE |
| | REQUIREMENTS. |
| | 40) SHTS P-24, P-25, P-26, P-27, &P-28 |
| | SANITARY RISER DIAGRAMS DO NOT REFLECT |
| | THE FLOOR PLAN. THE FIXTURES FOR THE |
| | MEZZANINE LEVEL ARE SHOWN ABOVE THE |
| | MEZZANINE LEVEL, WHEN THE PIPING WILL BE |
| | BELOW THE MEZZANINE LEVEL. FIXTURES FOR |
| | THE SECOND FLOOR ARE SHOWN ABOVE THE |
| | SECOND FLOOR WHEN THE PIPING WILL BE |
| | BELOW THE SECOND FLOOR. THE FIXTURES FOR |
| | THE THIRD THRU THE EIGHT FLOORS ARE |
| | SHOWN BELOW THE TERRACE FLOOR. THE |
| | PIPING SHOULD BE BELOW THE EIGHT FLOOR. |
| | SECTION 104.2.1. - NO RESPONSE NOTED, |
| | AND THIS COMMENT IS NOW FOR SHEETS P-23, |
| | P-29, P-30, & P-31 AS NEW RISERS HAVE |
| | BEEN SUBMITTED AND SHEET INFORMATION HAS |
| | CHANGED. |
| | 42) SHTS P-28 & P-29 SANT. BLDG. DRAIN |
| | ISOMETRIC, SHOW ALL PIPE SIZES AND SHOW |
| | THE DFU'S AS THEY ACCUMULATE IN THE |
| | SYSTEM. SECTION 104.2.1. & TABLE |
| | 710.1(1). - NO RESPONSE NOTED. PART OF |
| | THE BLDG DRAIN ISOMETRIC HAS BEEN |
| | DELETED AND THE ISOMETRIC IS INCOMPLETE. |
| | PLEASE SUBMIT A COMPLETE ISOMETRIC. |
| | 43) SHT P-31 AIR CHAMBERS ARE NOT |
| | APPROVED. DELETE FROM ALL RISERS. WATER |
| | HAMMER ARRESTORS REQUIRED BY SECTION |
| | 604.9 SHALL BE LOCATED AT ALL QUICK |
| | CLOSING VALVES, (W/M, ICE MAKER, & D/W), |
| | AND SHALL BE LOCATED NEAR THE FIXTURE. |
| | PDI-WH 201 AND MANUF. INSTALL. INSTRUCT. |
| | NO RESPONSE NOTED. WATER RISER DIAGRAMS |
| | HAVE CHANGED TO SHEETS P-35 & P-38. |
| | 44) SHTS P-33 & P-34 AUXILLARY ROOF |
| | DRAINS ON SOME SYSTEMS ARE UNDERSIZED. |
| | PLEASE SIZE PIPE PER TABLE 1106.3. ROOF |
| | DRAINS CHANGED TO SHTS 39, 40, 41, & 42, |
| | AND STILL HAVE SOME AUXILLARY ROOF DRAIN |
| | PIPING SIZED INCORRECTLY. |
| | 45) SHT P-35 STORM DRAIN RISER 111, SHOW |
| | ALL PIPE SIZES AND SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM. RECHECK ALL |
| | PIPE SIZES PER TABLES 1106.2 & 1106.3 AS |
| | SOME PIPE SIZES ARE INCORRECT. THERE ARE |
| | STILL SOME PIPE SIZES THAT ARE |
| | INCORRECT. RISER III CHANGED TO RISER II |
| | AND MOVED TO SHT 41.1. |
| | 46) SHT P-36 WATER HEATER DETAIL. |
| | THERMAL EXPANSION CONTROL IS REQUIRED |
| | PER SECTION 607.3.2. PLEASE INDICATE HOW |
| | THIS WILL BE ACCOMPLISHED. NO RESPONSE |
| | NOTED. |
| | 47) SHT P-36 GENERAL PLUMBING NOTES: |
| | #2 1/4"/FT FOR 2-1/2" & SMALLER PIPE. |
| | TABLE 704.1. INDICATE ON NOTE. NO |
| | RESPONSE NOTED. |
| | #16 AIR CHAMBERS ARE NOT APPROVED. |
| | DELETE SYMBOL & REFERENCE. SECTIONS |
| | 604.9 AND 104.2.1. - NO RESPONSE NOED. |
| | 49) SUBMIT A CONDENSATE DRAIN ISOMETRIC |
| | WITH ALL PIPE SIZES, LOCATION OF RISER |
| | CONNECTIONS, RISERS, TERMINATION POINT |
| | OF THE RISERS (VENTS), AND INDICATE |
| | WHERE THE CONDENSATE DRAINS TO THE |
| | OUTSIDE OF THE BUILDING. SECTION |
| | 104.2.1. |
| | 50) SUBMIT RISERS AND BLDG ISOMETRIC FOR |
| | THE EMERGENCY T&P VALVE DISCHARGE LINE |
| | AND EHT EMERGENCY PAN DRAIN LINE FOR THE |
| | WATER HEATERS. SHOW ALL PIPE SIZES FOR |
| | ALL PIPING. SECTIONS 104.2.1, & |
| | 104.3.1.1. |
| | 51) PLANS DO NOT APPEAR TO BE 100% AND |
| | MORE COMMENTS MAY FOLLOW ON THE NEXT |
| | REVIEW DEPENDING ON THE RESPONSE OF THIS |
| | REVIEW. - PLANS STILL ARE NOT 100% AND |
| | MORE COMMENTS MAY FOLLOW. |
| | **************NEW COMMENTS************** |
| | 1B) NEW FLOOR LAYOUTS, NEW REVIEW |
| | 2B) SHTS A27 THRU A32 ALL TYPICAL UNITS |
| | SHOW CLEAR FLOOR SPACE FOR W/C'S PER |
| | PAGE 7.43 FHA DESIGN MANUAL. SEE MINIMUM |
| | CLEAR FLOOR SPACE SIZE REQUIREMENTS. - |
| | SHOWER CLEAR FLOOR SPACE SHALL BE |
| | PARALLEL AND FLUSH WITH THE CONTROL |
| | WALL. SEE PAGE 7.56. |
| | 3B) SHTS A27 THRU A32 ALL TYPICAL UNITS |
| | WATER CLOSETS SHALL BE 18" OFF WALL TO |
| | CENERLINE OF FIXTURE. SEE PAGES 6.5, |
| | 7.43, 7.44 & 7.45. THIS IS WHEN THE W/C |
| | IN NEXT TO A WALL. |
| | 4B) SHTS A27 THRU A32 ALL TYPICAL UNITS |
| | SHALL SHOW THE DIMENSIONS FOR THE W/C |
| | OPENINGS. MINIMUM 33" REQUIRED. SEE |
| | PAGES 7.43 THRU 7.45 |
| | 5B) SHT A1 DRAWING INDEX DOES NOT |
| | REFLECT DRAWING SHEETS. SECTION 104.2.1. |
| | 6B) SHT P-3 8" PD(8393SF) TURNS INTO 8" |
| | PD(8818SF) IN UNIT L/W-D-1, COL. LINE 6 |
| | THEN BACK TO 8" PD(8393SF). CLARIFY. |
| | SECTION 104.2.1. |
| | 7B) MANY SHEETS ON FLOOR PLAN AND RISERS |
| | FOR MANY UNITS STATES "ISLEND VENT SEE |
| | DETAIL ON SHEET P-36 OR SHEET P-42. NO |
| | NEW SHT 36 SUBMITTED, AND NO SHT 42 |
| | SUBMITTED. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 8B) SHT P-3 15" REQUIRED FOR SANITARY |
| | BLDG. DRAIN (3907 FU), 10" REQUIRED ON |
| | SANITARY BLDG. DRAIN (1507 FU) COL. LINE |
| | 5/I, 5" MIN. (231 FU) UNIT L/W-C-1. |
| | TABLE 701.1(1). - STORM AND AUXILLARY |
| | PIPING SIZE IS NOT CORRECT IN MANY |
| | AREAS. CHECK PIPE SIZE PER TABLES 1106.2 |
| | AND 1106.3. |
| | 7B) SHT P-4 STORM DRAIN RISERS S14.2, |
| | S14.3, & S14.4 NO PIPING TO STORM DRAIN |
| | SHOWN. SECTION 104.2.1. STORM & |
| | AUXILLARY PIPE SIZES INCORRECT, AND SOME |
| | PIPE SIZES ARE NOT SHOWN. TABLES 1106.2 |
| | & 1106.3 AND SECTION 104.2.1. |
| | 8B) SHT P-4 UNITS L/W-E-2 & L/W-E-3 |
| | WATER CLOSETS ARE NOT VENTED, AND |
| | KITCHEN SINK AND FIXTURES FROM UPPER |
| | FLOORS SHALL NOT DRAIN THROUGH BATHROOM |
| | FIXTURES. SECTIONS 901.2.1 & 909.1 |
| | 9B) THE FOLLOWING SHEETS HAVE BEEN |
| | VOIDED, BUT NO NEW SHEETS HAVE BEEN |
| | SUBMITTED. P-1, P-2, P-11 THRU P-22, |
| | P-32, P-36, P-37, & P-42. PLANS |
| | INCOMPLETE. SECTION 104.2.1. |
| | 10B) SHT P-5 6" REQUIRED FROM PD(3080SF) |
| | - 6" REQUIRED FROM PD(3719SF) - 6" |
| | REQUIRED FROM PD(3361SF) - RISER 10, 11, |
| | 16, 10.1, SHOW RISER DESIGNATION NUMBER |
| | ON PLAN. TABLE 1106.3 & SECTION 104.2.1. |
| | UNIT L/W-B-1 WASH MACHINE SHALL NOT |
| | DRAIN INTO THE WET VENT FOR THE BATHROOM |
| | FIXTURES. SECTION 909.1 |
| | 11B) SHT P-6 5" MINIMUM REQUIRED PD |
| | (2343SF), 6" REQUIRED PF(3080SF) SHOW |
| | PIPING FOR PD(3061SF). TABLE 1106.3 AND |
| | SECTION 104.2.1. - UNIT L/W-B-1 WASH |
| | MACHINE SHALL NOT DRAIN INTO THE WET |
| | VENT FOR THE BATHROOM FIXTURES. SECTION |
| | 909.1. - RISER DIAGRAM DESIGNATION 56 IS |
| | POINTING TO CONDENSATE LINE, NOT SANT. |
| | RISER. - FLOOR PLAN DOES NOT REFLECT THE |
| | RISER DIAGRAM (100). SECTION 104.2.1. |
| | 12B) SHT P-7 6" REQUIRED ON AUXILLARY |
| | DRAIN LINES AT RISERS S/28, & S/29. 5" |
| | REQUIRED ON AUXILLARY DRAIN LINE BETWEEN |
| | COL. LINES 5 & 7/D & C. 8" REQUIRED ON |
| | AUXILLARY DRAINS S/8 & S/12. SHOW RISERS |
| | 70 & 98 LOCATIONS ON FLOOR PLAN. - PIPE |
| | SIZES NOT SHOWN FOR ROOF DRAINS, PRIMARY |
| | AND SECONDARY FOR COMMON PATIO AND |
| | PRIVATE LANAI AREAS. SECTION 104.2.1 AND |
| | TABLE 1106.3. - UNITS C-3L MAX. 4 FU ON |
| | 2" WET VENT TABLE 909.3. |
| | 13B) SHT P-8 6" REQUIRED ON AUXILLARY |
| | DRAINS S/26 & S/29. 8" REQUIRED ON |
| | AUXILLARY DRAINS S/14, & S/18. SHOW ALL |
| | PIPE SIZES FOR ROOM PRIMARY & SECONDARY |
| | DRAINS AT COMMON PATIO AND PRIVATE LANAI |
| | AREAS. TABLES 1106.2 & 1106.3. |
| | 14B) SHT P-10 UNIT C-3L MAX. 4 FU ON 2" |
| | WET VENT. TABLE 909.3 - BLDG DRAIN |
| | ISOMETRIC ON VOID SHT P-28 HAS BEEN |
| | DELETED. NEW SHEET DO NOT HAVE ALL THE |
| | BLDG. DRAIN ISOMETRIC SHOWN AND IS |
| | INCOMPLETE. SUBMIT A COMPLETE BLDG. |
| | DRAIN ISOMETRIC AS REQUIRED IN SECTION |
| | 104.3.1.1. SHOW ALL PIPE SIZES, |
| | CLEANOUTS, RISERS ECT. SECTION 104.2.1. |
| | 15B) SHT P-23 RISERS INDICATE TYPICAL |
| | 3RD THRU 8TH FLOORS, BUT 3RD THRU 7TH |
| | FLOORS ARE DIFFERENT FROM 8TH FLOOR AS |
| | THE 8TH FLOOR SHOWS THE REVENTING. THIS |
| | IS NOT TYPICAL ON 3RD THRU 7TH FLOORS. |
| | SECTION 104.2.1. |
| | 16B) ALL RISERS THAT SHOW RELIEF VENTS, |
| | RELEIF VENTS ARE ONLY REQUIRED IN SOIL & |
| | WASTE STACKS IN BUILDINGS HAVING MORE |
| | THAN 10 BRANCH INTERVALS. THESE ARE NOT |
| | REQUIRED. PLEASE DELETE FROM RISERS. |
| | SECTIONS 104.2.1 & 914.1. |
| | 17B) SHT P-23 RISER 3,4,5,6 DOES NOT |
| | REFLECT THE FLOOR PLAN. SHT P-3 SHOWS |
| | RISER 6 CONNECTING TO RISER 345 ON THE |
| | FIRST FLOOR NOT AT THE MEZZ. LEVEL AS |
| | SHOWN ON THE RISER. SECTION 104.2.1. - |
| | SHT P-5 SHOWS ONLY RISER #8 WITH RISERS |
| | 3,4,5,6 CONNECTING TO THIS RISER. |
| | CORRELATE RISERS AND FLOOR PLAN. |
| | 18B) SHT P-23 RISER #7 DOES NOT REFLECT |
| | FLOOR PLAN ON SHT P-5 AT LAV. - RISER |
| | #10/11/10.1 STARTS OFF ON THE FLOOR PLAN |
| | SHT P-3 AS RISER 10/11/16, THEN CHANGES |
| | TO 10/11/10.1. PLEASE CLARIFY. WHY WAS |
| | 10.1 NOT SHOWN AT BASE OF RISER, & WHY |
| | WAS RISER 16 NOT INDICATED ON SHT P-5 OR |
| | ON SHT P-23 RISER DESIGNATION? SECTION |
| | 104.2.1. |
| | 19B) SHT P-23 RISER 16 SHOWS NOTHING, & |
| | STOPS AT 2ND FLOOR. PLEASE CLARIFY. |
| | RISER 10/11/16/10.1 SHOWS VENT RISER #7. |
| | PLEASE CLARIFY. RISER DOES NOT REFLECT |
| | FLOOR PLAN AT RISER 10 ON THE 2ND FLOOR. |
| | CORRELATE RISER AND FLOOR PLAN. SECTION |
| | 104.2.1. |
| | 20B) TITLE BLOCK ON SOME SHEETS HAS |
| | WHITE OUT ON THEM AND THIS IS NOT |
| | APPROVED. SECTION 104.2.1.3 |
| | 21B) SHTS P-23, P-24, P-25, P-26, P-27, |
| | P-29, P-30, & P-31 CHECK ALL RISERS FOR |
| | COMPLIANCE WITH SECTIONS 903.1, 903.4, |
| | 915, MAKE SURE THEY REFLECT THE FLOOR |
| | PLAN, 909.1, 909.3, RELIEF VENTS NOT |
| | REQUIRED 914, 905.3, 708.3.4, 711.2, |
| | 711.3, 901.2.1. 910.2 AS THERE ARE |
| | NUMEROUS CODE VIOLATIONS AND ALL RISERS |
| | HAVE NOT BEEN CHECKED ON REVIEW. PLANS |
| | ARE MISSING FLOOR PLAN FOR NUMEROUS |
| | RISERS AND CAN NOT BE CHECKED TO SEE IF |
| | THEY REFLECT THE FLOOR PLAN. THESE WILL |
| | ALL BE CHECKED NEXT SUBMITTAL. |
| | 22B) SHT P-34 W/C NOT VENTED AT UNITS |
| | L/W-E-2 & L/W-E-3 AND RISERS 96, 97, |
| | 97.1, & 98 AND KITCHEN SINKS SHALL NOT |
| | DRAIN THROUGH THE WET VENT OF THE |
| | BATHROOM FIXTURES. 909.1 |
| | 23B) SHT P-35 SHOW ALL PIPE SIZES, |
| | DELETE AIR CHAMBERS, & SHOW ALL WATER |
| | HAMMER ARRESTORS REQUIRED BY SECTION |
| | 604.9. SECTION 104.2.1. |
| | 24B) SHT P-38 AIR CHAMBERS NOT APPROVED. |
| | DELETE FROM MENS AND WOMENS TOILET ROOMS |
| | ON ROOF TERRACE LEVEL. 604.9 |
| | 25B) SHTS P-39, P-40, P-41, & P-41.1, |
| | CHECK ALL AUXILLARY DRAINS FOR CORRECT |
| | SIZE. TABLE 1106.3 @ 4.5"/HR. |
| | **************************************** |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. - |
| | NO RESPONSE TO THIS REQUIRES LAST |
| | SUBMITTAL. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |
| | |