Plan Review Notes
Plan Review Notes For Permit 04110228
Permit Number 04110228
Review Stop P
Sequence Number 2
Notes
Date Text
2005-05-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FHA-98 DESIGN MANUAL
  
 A) COMMENTS FROM PREVIOUS REVIEW THAT
 HAVE NOT BEEN ADDRESSED, OR NOT
 ADDRESSED PROPERLY. THE COMMENT NUMBER
 WILL REMAIN THE SAME AS THE FIRST
 REVIEW:
 1) SHTS I-1, & I-2 FIRM LICENSE NUMBER
 REQUIRED ON THE TITLE BLOCK, SIGNATURE
 REQUIRED, AND PRINTED NAME REQUIRED. FAC
 61G1-16.004(2)(5)(6), 61G1-16.003 AND FS
 481.219. - SUBMIT PROOF OF A LEGAL
 SIGNATURE IN THE FORM OF A DRIVERS
 LICENSE, VOTERS REG. CARD ECT., AND
 SUBMIT A SIGNED/SEALED/DATED NOTORIZED
 LETTER WITH YOUR LEGAL SIGNATURE FOR OUR
 FILES. (TITLE BLOCK REQD ON LETTER).
 2) SHT I-1, AN RPZ BACKFLOW, INSTALLED
 BY A LICENSED PLUMBING CONTRACTOR, IS
 REQUIRED FOR THE IRRIGATION SYSTEM. SHOW
 THE LOCATION ON THE IRRIGATION PLANS.
 SECTIONS 608.13.2 & 104.2.1.
 3) SHTS A-11 & A-12 SHT INDEX STATES
 PARTIAL 3RD-7TH FLOOR PLAN 1, BUT NOTE 5
 STATES 3RD-5TH FLOOR PLAN. PLEASE
 CLARIFY. SECTION 104.2.1.
 4) SHTS A-9 & A-15 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS
 PER SECTIONS 1106, & 1107 AND ALL
 SUBSECTIONS. SHOW SF OF EACH AREA WITH
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS AND ROOF AREA FROM ABOVE THAT
 DRAINS TO THE ROOF FROM ABOVE ADDED TO
 THE SF IN THE CALCULATIONS. SHOW THE
 LOCATION OF ALL PRIMARY AND SECONDARY
 ROOF DRAINS AND THE SCUPPERS. ALSO SEE
 SHTS A-17 & A-18. THIS APPLIES TO THE
 ROOF DECK AREAS AS WELL.
 5) SHTS A-9 & A-15 SHOW THE LOCATION AND
 SIZE OF ALL SECONDARY ROOF DRAINS &
 SCUPPERS. SECTION 104.2.1.
 6) SHTS A-15 & A-16 SUBMIT CALCULATIONS
 FOR MINIMUM FACILITIES PER TABLES 1003.1
 AND 403.1. SHOW THE SF OF EACH COMMON
 AREA, AND THE TOTAL COMMON AREA IN THE
 CALCULATIONS.
 7) ARCHITECTURAL SHEETS, THE DATE
 PREPARED AND THE PRINTED NAME OF THE
 PERSON RESPONSIBLE FOR THE DOCUMENT ARE
 REQUIRED PER FAC 61G1-16.004(4)(6) AND
 FS 481.2055.
 8) SHTS A-30, A-31, & A-32 INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT
 OR BATHROOM AS REQUIRED ON PAGE 7.35 OF
 THE FHA DESIGN MANUAL.
 9) SHTS A-30, A-31, & A-32 SHOW THE SIZE
 OF THE OPENINGS FOR ALL COVERED WATER
 CLOSETS. MINIMUM 33" REQUIRED. SEE PAGES
 6.5 AND 6.7 OF THE FHA DESIGN MANUAL. -
 THE 18" FROM THE WALL TO THE CENTERLINE
 OF THE W/C IS AN ABSOLUTE MEASURMENT.
 SEE FIGS PAGE 6.3 & 6.5.
 10) SHT A-33 MENS AND WOMENS RESTROOMS,
 SHOW CLEAR FLOOR SPACE FOR EACH
 ACCESSIBLE FIXTURE. SECTIONS 11-4.16.2,
 11-4.19.3, & 11-4.22.3. THE TURNING AREA
 SHALL BE SHOWN IN THE TOILET ROOM, NOT
 IN THE ACCESSIBLE STALL. ALSO SHOW WATER
 CLOSET HEIGHT PER 11-4.16.3. GRAB BAR
 HEIGHT MAX. 36", SHOWN AS 48" ON DETAIL
 BEHIND W/C. SHOW FLUSH CONTROL 11-4.16.5
 SHOW URINAL HEIGHT 11-4.18.2. THE
 CENTERLINE OF THE W/C SHALL BE 18" TO
 THE WALL FROM THE CENTERLINE OF THE
 FIXTURE, NOT 20" AS SHOWN. (SEE FIG. 28)
 FOR THE LAVS SHOW KNEE CLEARANCE
 11-4.19.2, FOR THE SHOWER SHOW CONTROLS
 11-4.21.5, SHOWER UNIT 11-4.21.6, AND
 CURB HEIGHT 11-4.21.8.
 11) NOT USED
 12) SHT A-33 DETAIL #1 IN BOTH THE MEN'S
 AND WOMEN'S RESTROOMS. THE DOUBLE LAVS
 TO BE 34" IN HEIGHT AND HAVE A CLEARANCE
 OF 29". SEE FIG 31. SECTION 11-4.19.2.
 13) A DRINKING FOUNTAIN IS REQUIRED IN
 THE COMMON AREA. TABLE 403.1. SUBMIT A
 DETAIL COMPLYING WITH SECTIONS 11-4.15
 AND ALL SUBSECTIONS & 11-4.1.3(10)(A)
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 14) SHT A-36 SHOW HEIGHT AND WIDTH OF
 SCUPPER OPENINGS ON THE DETAIL. SECTION
 104.2.1.
 15) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME. INITIALS ARE NOT APPROVED PER
 FBPE RULING. SUBMIT AN EXAMPLE OF THE
 ENGINEERS LEGAL SIGNATURE BY WAY OF
 DRIVERS LICENSE, VOTERS REG. ECT., AND A
 SIGNED, SEALED, DATED, NOTORIZED LETTER
 WITH TITLE BLOCK INDICATING YOUR LEGAL
 SIGNATURE FOR OUR FILES.
 61G15-23.002(1)(2) AND FS 471.025. THIS
 IS FOR ALL ENGINEERED SHEETS.
 16) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, LICENSE NUMBER & CERTIFICATE
 OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2). (WHITE OUT USED ON THE
 PLANS IS NOT APPROVED PER SECTION
 104.2.1.3.
 17) SHTS P-1 & P-2 PD'S SIZING AND
 PIPING SIZING ARE NOT CORRECT FOR ALL
 PD'S. RECHECK SIZING PER TABLES 1106.2 &
 1106.3. SHOW ALL SF AND PIPE SIZES.
 (THIS HAS NOT BEEN ADDRESSED, AND NEW
 SHEETS P-1 & P-2 WERE NOT SUBMITTED).
 18) SUBMIT MANUF. SPECIFICATION SHEETS
 FOR ELEVATOR SUMP PUMPS AND THE STORM
 WATER SUMP PUMPS. PUMP INFORMATION SHALL
 SHOW THE LISTING. SECTION 303.4.
 (SUBMITTALS NOT FOUND).
 19) SHTS P-3 & P-4 PIPE SIZING NOT
 CORRECT FOR EMERGENCY ROOF DRAIN PIPING,
 (SECONDARY ROOF DRAINS). SEE TABLES
 1106.2 & 1106.3. NO SF SHOWN FOR PD'S AT
 COL. LINE 5/G-F1 AND COL. LINE 6/F-E2.
 PD BETWEEN COLS. 8.1 & 8.3 NORTH OF
 STAIRWAY #2 NOT ADDED TO THE SYSTEM.
 DOUBLE CHECK ALL PIPE SIZES AND SHOW
 ADDITION OF ALL SF AS THEY ACCUMULATE IN
 THE STORM BLDG. DRAIN. SECTION 104.2.1.
 *** NEW COMMENT ** (ON PD LINE 8"PD
 (88185SF) NOTHING IS SHOWN ADDED TO
 10713SF) CLARIFY. - ALL PD LINES REQUIRE
 A CLEANOUT AS LINE EXITS BLDG.
 27) SHT P-5 CHECK ALL PIPE SIZING ON THE
 STORM SYSTEM AND SHOW ALL PIPE SIZES.
 SECTION 104.2.1. & TABLES 1106.2 &
 1106.3.
 34) SHT P-11AUXILLARY HORIZONTAL DRAIN
 PIPE SIZE NOT CORRECT. TABLE 1106.3. -
 NO RESPONSE NOTED. SHEET VOIDED BUT NO
 NEW SHEET SUBMITTED.
 35) THE TRASH CHUTE BEQUIRES AN "N-36"
 VACUUM BREAKER FOR BACKFLOW PROTECTION.
 SECTION 608.13.6. NO RESPONSE. SHEET
 VOIDED BUT NO NEW SHEET SUBMITTED.
 36) SHT P-12 AUXILLARY HORIZONTAL DRAIN
 PIPE TO BE SIZED PER TABLE 1106.3. NO
 RESPONSE. SHEET VOIDED BUT NO NEW SHEET
 SUBMITTED.
 37) SHTS P-13, & P-14 AUXILLARY ROOF
 DRAIN NEAR POOL SHALL NOT BE A TRIPPING
 HAZARD. PLEASE SUBMIT A DETAIL FOR S/27,
 S/28, S/29, & S/30 SECONDARY DRAINS.
 SECTION 104.2.1. NO RESPONSE NOTED. SHT
 VOIDED, BUT NO NEW SHEET SUBMITTED.
 38) SHT P-22 NO WATER SUPPLY SHOWN TO
 THE TRASH ROOM FOR THE TRASH CHUTE.
 PLEASE SHOW ON PLANS. SECTION 104.2.1.
 NO RESPONSE NOTED. SHEET VOIDED, BUT NO
 NEW SHEET SUBMITTED.
 39) SHTS P-24, P-25, P-26, P-27, & P-28
 DO NOT MEET CODE REQUIREMENTS. IN MANY
 CASES THESE ARE THE CODE ISSUES NOT
 ADDRESSED. - THESE COMMENTS NOW APPLY TO
 SHTS 23, 29, 30, & 31 AS NEW RISERS HAVE
 BEEN SUBMITTED, AND SHEET INFORMATION
 HAS CHANGED.
 A. OFFSET VENTS ARE REQUIRED WHEN
 HORIZONTAL OFFSET ARE USED. SECTION 915.
 RESPONSE NOT APPROVED. OFFSET VENTS
 SHALL BE SHOWN ON THE RISER DIAGRAMS.
 SEE SECTION 104.2.1.
 B. NO HORIZONTAL DRY VENTS. SECTION
 905.3.
 C. STACK DRAIN SHALL CONNECT DOWNSTREAM
 OF BATHROOM GROUP FIXTURES. SECTION
 909.1
 D. KITCHEN SINK SHALL NOT DRAIN THROUGH
 THE WET VENT. SECTION 909.1
 E. MAIN VENT REQUIRED AT TOP OF STACKS.
 SECTION 903.1.
 F. CLEANOUTS REQUIRED AT THE BASE OF
 EACH STACK. SECTION 708.3.4.
 G. NO HORIZONTAL BRANCH CONNECTIONS TO
 A HORIZONTAL STACK OFFSET. SECTIONS
 711.2 & 711.3.
 H. VENTING REQUIRED 901.2.1.
 I. (NEW COMMENT) EVERY VENT STACK SHALL
 CONNECT TO THE BASE OF THE DRAINAGE
 STACK. THE VENT STACK SHALL CONNECT AT
 OR BELOW THE LOWEST HORIZONTAL BRANCH.
 SECTION 903.4
 J. STACK INSTALLATION 910.2
 THE RISERS ARE NOT CLEAR AS TO THEIR
 INTENT. CHECK ALL RISERS FOR CODE
 REQUIREMENTS.
 40) SHTS P-24, P-25, P-26, P-27, &P-28
 SANITARY RISER DIAGRAMS DO NOT REFLECT
 THE FLOOR PLAN. THE FIXTURES FOR THE
 MEZZANINE LEVEL ARE SHOWN ABOVE THE
 MEZZANINE LEVEL, WHEN THE PIPING WILL BE
 BELOW THE MEZZANINE LEVEL. FIXTURES FOR
 THE SECOND FLOOR ARE SHOWN ABOVE THE
 SECOND FLOOR WHEN THE PIPING WILL BE
 BELOW THE SECOND FLOOR. THE FIXTURES FOR
 THE THIRD THRU THE EIGHT FLOORS ARE
 SHOWN BELOW THE TERRACE FLOOR. THE
 PIPING SHOULD BE BELOW THE EIGHT FLOOR.
 SECTION 104.2.1. - NO RESPONSE NOTED,
 AND THIS COMMENT IS NOW FOR SHEETS P-23,
 P-29, P-30, & P-31 AS NEW RISERS HAVE
 BEEN SUBMITTED AND SHEET INFORMATION HAS
 CHANGED.
 42) SHTS P-28 & P-29 SANT. BLDG. DRAIN
 ISOMETRIC, SHOW ALL PIPE SIZES AND SHOW
 THE DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM. SECTION 104.2.1. & TABLE
 710.1(1). - NO RESPONSE NOTED. PART OF
 THE BLDG DRAIN ISOMETRIC HAS BEEN
 DELETED AND THE ISOMETRIC IS INCOMPLETE.
 PLEASE SUBMIT A COMPLETE ISOMETRIC.
 43) SHT P-31 AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM ALL RISERS. WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9 SHALL BE LOCATED AT ALL QUICK
 CLOSING VALVES, (W/M, ICE MAKER, & D/W),
 AND SHALL BE LOCATED NEAR THE FIXTURE.
 PDI-WH 201 AND MANUF. INSTALL. INSTRUCT.
 NO RESPONSE NOTED. WATER RISER DIAGRAMS
 HAVE CHANGED TO SHEETS P-35 & P-38.
 44) SHTS P-33 & P-34 AUXILLARY ROOF
 DRAINS ON SOME SYSTEMS ARE UNDERSIZED.
 PLEASE SIZE PIPE PER TABLE 1106.3. ROOF
 DRAINS CHANGED TO SHTS 39, 40, 41, & 42,
 AND STILL HAVE SOME AUXILLARY ROOF DRAIN
 PIPING SIZED INCORRECTLY.
 45) SHT P-35 STORM DRAIN RISER 111, SHOW
 ALL PIPE SIZES AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. RECHECK ALL
 PIPE SIZES PER TABLES 1106.2 & 1106.3 AS
 SOME PIPE SIZES ARE INCORRECT. THERE ARE
 STILL SOME PIPE SIZES THAT ARE
 INCORRECT. RISER III CHANGED TO RISER II
 AND MOVED TO SHT 41.1.
 46) SHT P-36 WATER HEATER DETAIL.
 THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.3.2. PLEASE INDICATE HOW
 THIS WILL BE ACCOMPLISHED. NO RESPONSE
 NOTED.
 47) SHT P-36 GENERAL PLUMBING NOTES:
 #2 1/4"/FT FOR 2-1/2" & SMALLER PIPE.
 TABLE 704.1. INDICATE ON NOTE. NO
 RESPONSE NOTED.
 #16 AIR CHAMBERS ARE NOT APPROVED.
 DELETE SYMBOL & REFERENCE. SECTIONS
 604.9 AND 104.2.1. - NO RESPONSE NOED.
 49) SUBMIT A CONDENSATE DRAIN ISOMETRIC
 WITH ALL PIPE SIZES, LOCATION OF RISER
 CONNECTIONS, RISERS, TERMINATION POINT
 OF THE RISERS (VENTS), AND INDICATE
 WHERE THE CONDENSATE DRAINS TO THE
 OUTSIDE OF THE BUILDING. SECTION
 104.2.1.
 50) SUBMIT RISERS AND BLDG ISOMETRIC FOR
 THE EMERGENCY T&P VALVE DISCHARGE LINE
 AND EHT EMERGENCY PAN DRAIN LINE FOR THE
 WATER HEATERS. SHOW ALL PIPE SIZES FOR
 ALL PIPING. SECTIONS 104.2.1, &
 104.3.1.1.
 51) PLANS DO NOT APPEAR TO BE 100% AND
 MORE COMMENTS MAY FOLLOW ON THE NEXT
 REVIEW DEPENDING ON THE RESPONSE OF THIS
 REVIEW. - PLANS STILL ARE NOT 100% AND
 MORE COMMENTS MAY FOLLOW.
 **************NEW COMMENTS**************
 1B) NEW FLOOR LAYOUTS, NEW REVIEW
 2B) SHTS A27 THRU A32 ALL TYPICAL UNITS
 SHOW CLEAR FLOOR SPACE FOR W/C'S PER
 PAGE 7.43 FHA DESIGN MANUAL. SEE MINIMUM
 CLEAR FLOOR SPACE SIZE REQUIREMENTS. -
 SHOWER CLEAR FLOOR SPACE SHALL BE
 PARALLEL AND FLUSH WITH THE CONTROL
 WALL. SEE PAGE 7.56.
 3B) SHTS A27 THRU A32 ALL TYPICAL UNITS
 WATER CLOSETS SHALL BE 18" OFF WALL TO
 CENERLINE OF FIXTURE. SEE PAGES 6.5,
 7.43, 7.44 & 7.45. THIS IS WHEN THE W/C
 IN NEXT TO A WALL.
 4B) SHTS A27 THRU A32 ALL TYPICAL UNITS
 SHALL SHOW THE DIMENSIONS FOR THE W/C
 OPENINGS. MINIMUM 33" REQUIRED. SEE
 PAGES 7.43 THRU 7.45
 5B) SHT A1 DRAWING INDEX DOES NOT
 REFLECT DRAWING SHEETS. SECTION 104.2.1.
 6B) SHT P-3 8" PD(8393SF) TURNS INTO 8"
 PD(8818SF) IN UNIT L/W-D-1, COL. LINE 6
 THEN BACK TO 8" PD(8393SF). CLARIFY.
 SECTION 104.2.1.
 7B) MANY SHEETS ON FLOOR PLAN AND RISERS
 FOR MANY UNITS STATES "ISLEND VENT SEE
 DETAIL ON SHEET P-36 OR SHEET P-42. NO
 NEW SHT 36 SUBMITTED, AND NO SHT 42
 SUBMITTED. PLEASE CLARIFY. SECTION
 104.2.1.
 8B) SHT P-3 15" REQUIRED FOR SANITARY
 BLDG. DRAIN (3907 FU), 10" REQUIRED ON
 SANITARY BLDG. DRAIN (1507 FU) COL. LINE
 5/I, 5" MIN. (231 FU) UNIT L/W-C-1.
 TABLE 701.1(1). - STORM AND AUXILLARY
 PIPING SIZE IS NOT CORRECT IN MANY
 AREAS. CHECK PIPE SIZE PER TABLES 1106.2
 AND 1106.3.
 7B) SHT P-4 STORM DRAIN RISERS S14.2,
 S14.3, & S14.4 NO PIPING TO STORM DRAIN
 SHOWN. SECTION 104.2.1. STORM &
 AUXILLARY PIPE SIZES INCORRECT, AND SOME
 PIPE SIZES ARE NOT SHOWN. TABLES 1106.2
 & 1106.3 AND SECTION 104.2.1.
 8B) SHT P-4 UNITS L/W-E-2 & L/W-E-3
 WATER CLOSETS ARE NOT VENTED, AND
 KITCHEN SINK AND FIXTURES FROM UPPER
 FLOORS SHALL NOT DRAIN THROUGH BATHROOM
 FIXTURES. SECTIONS 901.2.1 & 909.1
 9B) THE FOLLOWING SHEETS HAVE BEEN
 VOIDED, BUT NO NEW SHEETS HAVE BEEN
 SUBMITTED. P-1, P-2, P-11 THRU P-22,
 P-32, P-36, P-37, & P-42. PLANS
 INCOMPLETE. SECTION 104.2.1.
 10B) SHT P-5 6" REQUIRED FROM PD(3080SF)
 - 6" REQUIRED FROM PD(3719SF) - 6"
 REQUIRED FROM PD(3361SF) - RISER 10, 11,
 16, 10.1, SHOW RISER DESIGNATION NUMBER
 ON PLAN. TABLE 1106.3 & SECTION 104.2.1.
 UNIT L/W-B-1 WASH MACHINE SHALL NOT
 DRAIN INTO THE WET VENT FOR THE BATHROOM
 FIXTURES. SECTION 909.1
 11B) SHT P-6 5" MINIMUM REQUIRED PD
 (2343SF), 6" REQUIRED PF(3080SF) SHOW
 PIPING FOR PD(3061SF). TABLE 1106.3 AND
 SECTION 104.2.1. - UNIT L/W-B-1 WASH
 MACHINE SHALL NOT DRAIN INTO THE WET
 VENT FOR THE BATHROOM FIXTURES. SECTION
 909.1. - RISER DIAGRAM DESIGNATION 56 IS
 POINTING TO CONDENSATE LINE, NOT SANT.
 RISER. - FLOOR PLAN DOES NOT REFLECT THE
 RISER DIAGRAM (100). SECTION 104.2.1.
 12B) SHT P-7 6" REQUIRED ON AUXILLARY
 DRAIN LINES AT RISERS S/28, & S/29. 5"
 REQUIRED ON AUXILLARY DRAIN LINE BETWEEN
 COL. LINES 5 & 7/D & C. 8" REQUIRED ON
 AUXILLARY DRAINS S/8 & S/12. SHOW RISERS
 70 & 98 LOCATIONS ON FLOOR PLAN. - PIPE
 SIZES NOT SHOWN FOR ROOF DRAINS, PRIMARY
 AND SECONDARY FOR COMMON PATIO AND
 PRIVATE LANAI AREAS. SECTION 104.2.1 AND
 TABLE 1106.3. - UNITS C-3L MAX. 4 FU ON
 2" WET VENT TABLE 909.3.
 13B) SHT P-8 6" REQUIRED ON AUXILLARY
 DRAINS S/26 & S/29. 8" REQUIRED ON
 AUXILLARY DRAINS S/14, & S/18. SHOW ALL
 PIPE SIZES FOR ROOM PRIMARY & SECONDARY
 DRAINS AT COMMON PATIO AND PRIVATE LANAI
 AREAS. TABLES 1106.2 & 1106.3.
 14B) SHT P-10 UNIT C-3L MAX. 4 FU ON 2"
 WET VENT. TABLE 909.3 - BLDG DRAIN
 ISOMETRIC ON VOID SHT P-28 HAS BEEN
 DELETED. NEW SHEET DO NOT HAVE ALL THE
 BLDG. DRAIN ISOMETRIC SHOWN AND IS
 INCOMPLETE. SUBMIT A COMPLETE BLDG.
 DRAIN ISOMETRIC AS REQUIRED IN SECTION
 104.3.1.1. SHOW ALL PIPE SIZES,
 CLEANOUTS, RISERS ECT. SECTION 104.2.1.
 15B) SHT P-23 RISERS INDICATE TYPICAL
 3RD THRU 8TH FLOORS, BUT 3RD THRU 7TH
 FLOORS ARE DIFFERENT FROM 8TH FLOOR AS
 THE 8TH FLOOR SHOWS THE REVENTING. THIS
 IS NOT TYPICAL ON 3RD THRU 7TH FLOORS.
 SECTION 104.2.1.
 16B) ALL RISERS THAT SHOW RELIEF VENTS,
 RELEIF VENTS ARE ONLY REQUIRED IN SOIL &
 WASTE STACKS IN BUILDINGS HAVING MORE
 THAN 10 BRANCH INTERVALS. THESE ARE NOT
 REQUIRED. PLEASE DELETE FROM RISERS.
 SECTIONS 104.2.1 & 914.1.
 17B) SHT P-23 RISER 3,4,5,6 DOES NOT
 REFLECT THE FLOOR PLAN. SHT P-3 SHOWS
 RISER 6 CONNECTING TO RISER 345 ON THE
 FIRST FLOOR NOT AT THE MEZZ. LEVEL AS
 SHOWN ON THE RISER. SECTION 104.2.1. -
 SHT P-5 SHOWS ONLY RISER #8 WITH RISERS
 3,4,5,6 CONNECTING TO THIS RISER.
 CORRELATE RISERS AND FLOOR PLAN.
 18B) SHT P-23 RISER #7 DOES NOT REFLECT
 FLOOR PLAN ON SHT P-5 AT LAV. - RISER
 #10/11/10.1 STARTS OFF ON THE FLOOR PLAN
 SHT P-3 AS RISER 10/11/16, THEN CHANGES
 TO 10/11/10.1. PLEASE CLARIFY. WHY WAS
 10.1 NOT SHOWN AT BASE OF RISER, & WHY
 WAS RISER 16 NOT INDICATED ON SHT P-5 OR
 ON SHT P-23 RISER DESIGNATION? SECTION
 104.2.1.
 19B) SHT P-23 RISER 16 SHOWS NOTHING, &
 STOPS AT 2ND FLOOR. PLEASE CLARIFY.
 RISER 10/11/16/10.1 SHOWS VENT RISER #7.
 PLEASE CLARIFY. RISER DOES NOT REFLECT
 FLOOR PLAN AT RISER 10 ON THE 2ND FLOOR.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
 20B) TITLE BLOCK ON SOME SHEETS HAS
 WHITE OUT ON THEM AND THIS IS NOT
 APPROVED. SECTION 104.2.1.3
 21B) SHTS P-23, P-24, P-25, P-26, P-27,
 P-29, P-30, & P-31 CHECK ALL RISERS FOR
 COMPLIANCE WITH SECTIONS 903.1, 903.4,
 915, MAKE SURE THEY REFLECT THE FLOOR
 PLAN, 909.1, 909.3, RELIEF VENTS NOT
 REQUIRED 914, 905.3, 708.3.4, 711.2,
 711.3, 901.2.1. 910.2 AS THERE ARE
 NUMEROUS CODE VIOLATIONS AND ALL RISERS
 HAVE NOT BEEN CHECKED ON REVIEW. PLANS
 ARE MISSING FLOOR PLAN FOR NUMEROUS
 RISERS AND CAN NOT BE CHECKED TO SEE IF
 THEY REFLECT THE FLOOR PLAN. THESE WILL
 ALL BE CHECKED NEXT SUBMITTAL.
 22B) SHT P-34 W/C NOT VENTED AT UNITS
 L/W-E-2 & L/W-E-3 AND RISERS 96, 97,
 97.1, & 98 AND KITCHEN SINKS SHALL NOT
 DRAIN THROUGH THE WET VENT OF THE
 BATHROOM FIXTURES. 909.1
 23B) SHT P-35 SHOW ALL PIPE SIZES,
 DELETE AIR CHAMBERS, & SHOW ALL WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9. SECTION 104.2.1.
 24B) SHT P-38 AIR CHAMBERS NOT APPROVED.
 DELETE FROM MENS AND WOMENS TOILET ROOMS
 ON ROOF TERRACE LEVEL. 604.9
 25B) SHTS P-39, P-40, P-41, & P-41.1,
 CHECK ALL AUXILLARY DRAINS FOR CORRECT
 SIZE. TABLE 1106.3 @ 4.5"/HR.
 ****************************************
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION. -
 NO RESPONSE TO THIS REQUIRES LAST
 SUBMITTAL.
  