| Date |
Text |
| 2005-04-28 00:00:00 | DENIED: |
| | RESPONSE TO COMMENTS DATED 12-06-04: |
| | COMMENT #1 - INDICATE MAKEUP AIR FOR THE |
| | GARAGE EXHAUST.PLANS INDICATE |
| | CALCULATIONS BUT DO NOT ANNOTATE OR |
| | IDENTIFY HOW THE MAKE-UP AIR WILL BE |
| | ACHIEVED. |
| | |
| | COMMENT #5 - PLAN SHEET M-3, DUCT |
| | REDUCES IN RISER ONLY PLEASE CLARIFY. NO |
| | CLARFICATION GIVEN AND DUCT SIZE DID NOT |
| | CHANGE. |
| | |
| | COMMENT #9 - PLAN SHEET M-5, MAKE UP AIR |
| | TO STAIR #1 WAS EXTENDED OUT BUT IS |
| | STILL LOCATED AT THE GARAGE ENTRANCE. |
| | PROVIDE ELEVATION OF THE FRESH AIR |
| | INTAKE. |
| | |
| | COMMENT #12 - PROVIDE ELEVATION FOR THE |
| | TERMINATION OF THE MUFFLER EXHAUST. |
| | INDICATE DISTANCE FROM DOORS, WINDOWS |
| | AND FRESH AIR INTAKES. |
| | |
| | COMMENT #13 - PROVIDE DETAIL AND |
| | INFORMATION FOR THE FUEL PIPING AND |
| | STORAGE TANK.PLEASE INDICATE WHERE |
| | THIS ADDRESSED.INDICATE ON THE PLAN |
| | LOCATION AND PIPE SIZING. |
| | |
| | COMMENT #16 - PLANS SHEETS M-3 THROUGH |
| | M-6, STILL INDICATE THE DRYER & BATHROOM |
| | EXHAUST IN THE RETURN AIR PLENUM.PER |
| | 2001 FBC/M 601.3 EXHAUST DUCTS UNDER |
| | POSTITIVE PRESSURE SALL NOT EXTEND INTO |
| | OR PASS THROUGH PLENUMS. |
| | |
| | NEW COMMENTS: |
| | 1.PLAN SHEET M-5 8"X 6" SUPPLY AIR |
| | DUCT TO SECURITY OFFICE PENETRATES A 2 |
| | HOUR RATED WALL.INDICATE COMPLIANCER |
| | WITH 2001 FBC/M 607.1.3 #3 OR A FIRE |
| | DAMPER WILL BE REQUIRED IN ACCORDANCE |
| | WITH 2001 FBC/M 607.1.2. |
| | |
| | 2.PLAN SHEET M-11 THROUGH M-17 ARE |
| | VOIDED BUT THE REPLACEMENT SHEETS WERE |
| | NOT SUBMITTED.PLEASE CLARIFY. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |