| 2005-04-15 00:00:00 | ********** UNSAT 2ND REVIEW *********** |
| | |
| | REVIEW FOR "THE PLACE VIA CLEMATIS"; |
| | PLEASE SEE PLANS ARE SUBMITTED FOR "PLAN |
| | REVIEW ONLY" AND NOT SUBMITTED FOR |
| | PERMIT. |
| | |
| | PLEASE SEE MANY COMMENTS FROM PREVIOUS |
| | REVIEW STTILL NEED TO BE ADDRESSED. |
| | |
| | PLEASE SEE NEW COMMENTS DUE TO MORE |
| | INFORMATIONPROVIDED FROM PREVIOUS SET |
| | OF PLANS. |
| | HOWEVER PLEASE SEE NEW COMMENT FOR PAGES |
| | MISSING. STILL UNABLE TO DO A FULL AND |
| | COMPLETE REVIEW DUE TO PLANS AND SPECS |
| | NOT BEING COMPLETE AT THIS TIME. |
| | |
| | 1)NOTE: NOTE #1, NO, PLEASE SEE LETTER |
| | FOR ENGINEER TO BE SIGNED, DATED AND |
| | NOTORIZED FOR LEGAL SIGNATURE. |
| | TITLE BLOCKS "WHITED OUT" FOR FIRM NAME. |
| | |
| | 2)NOTE: NOTE #2 NO, PLEASE SEE OUTWARD |
| | SWING IS NOW SHOWN, HOWEVER NOTE(S) |
| | REQUESTED ON PLANS FOR PANIC HARDWARE |
| | ETC WAS NOT ADDED. |
| | |
| | 3)NOTE: NOTE #3 OK |
| | |
| | 4)NOTE: NOTE #4 OK |
| | |
| | 5)NOTE: NOTE #5 NO, PLEASE SEE 620.22-25 |
| | PLEASE ALSO SEE LAYOUT FOR ELEV MACHINE |
| | ROOMS ARE MISSING ELECTRICAL EQUIPMENT. |
| | ETC. |
| | |
| | 6)NOTE: NOTE #6 NO,PLEASE SEE PREVIOUS |
| | NOTES: MANY WERE ADDED HOWEVER THERE ARE |
| | STILL SOME MISSING, PLEASE SEE REDLLINED |
| | PLANS.210.52 |
| | |
| | 7)NOTE:NOTE #7 OK. |
| | |
| | 8)NOTE: NOTE #8 OK. |
| | |
| | 9)NOTE: NOTE #9 OK. |
| | |
| | 10)NOTE: NOTE #10 OK. |
| | |
| | 11)NOTE: NOTE #11 OK. |
| | |
| | 12)NOTE: NOTE#12 NO, PLEASE SEE SOME |
| | ROOM DESIGNATIONS WERE ADDED HOWEVER |
| | SOME AREAS ARE STYILL MISSING. |
| | PELASE ALSO SEE NEW COMMENTS PERTAINING |
| | TO "DINING AREA". |
| | |
| | 13)NOTE: NOTE #13 NO, PLEASE SEE E-19 |
| | WAS NOT SUBMITTED. PLEASE SEE NEW |
| | COMMENTS PERTAINING TO "NEW " SHEETS |
| | MISSING. |
| | |
| | 14)NOTE: NOTE #14 NO, PLEASE SEE SOME |
| | STILL MISSING. REDLINED. |
| | |
| | 15)NOTE: NOTE #15 NO.PLEASE SEE MANY |
| | AREAS RECEPTS ARE SHOWN IN AREAS OTHER |
| | THAN "DINING AREA". PLEASE SEE SOME ARE |
| | HALLWAYS, FOYERS, LIVING RMS? ETC. |
| | PLEASE SEE PREVIOUS COMMENT ABBOUT |
| | DEIGNATED AREAS. |
| | |
| | 16)NOTE: NOTE #16, OK. |
| | |
| | 17)NOTE: NOTE #17 OK. |
| | |
| | 18)NOTE: NOTE #18 OK. |
| | |
| | 19)NOTE: NOTE #19 OK, HOWEVER, PLEASE |
| | SEE NEW NOTES BELOW PERTAINING TO |
| | LABELING OF METER CENTERS. ETC. |
| | |
| | 20)NOTE: NOTE #20 OK. |
| | |
| | 21)NOTE: NOTE #21OK. |
| | |
| | 22)NOTE: NOTE #22 OK, HOWEVER PLEASE SEE |
| | NEW NOTES PERTAINING TO LABELING AND |
| | ELECTRICAL ROOMS. SAME AS #19. |
| | |
| | 23)NOTE: NOTE #23 NO. |
| | |
| | 24)NOTE: NOTE #24 OK, PLEASE SEE NEW |
| | NOTES PERTAINING TO FIRE PUMP FEED FROM |
| | EM DP. |
| | |
| | 25)NOTE: NOTE #25 OK. |
| | |
| | 26)NOTE: NOTE #26 OK. |
| | |
| | 27)NOTE: NOTE #27 NO. |
| | |
| | 28)NOTE:NOTE #28 NO, PLEASE SEE |
| | INFORMATION FOR FIRE PUMP, FIRE PUMP |
| | CONTROLLER/ATS DISCONNECTIN MEANS WAS |
| | NOT SUPPLIED. |
| | PLEASE ALSO SEE NEW NOTES DUE TO FIRE |
| | PUMP FEED FROM EDP. |
| | |
| | 29)NOTE: NOTE #29 NO, SPECS FOR |
| | GENERATOR WERE SUBMITTED , HOWEVER THEY |
| | DO NOT CORRELATE TO PLANS. |
| | |
| | 30)NOTE: NOTE #30 NO, PLEASE SEE RISER. |
| | |
| | 31)NOTE: NOTE #31 NO. |
| | |
| | 32)NOTE: NOTE #32 NO. |
| | |
| | 33)NOTE: NOTE #33 OK |
| | |
| | 34)NOTE: NOTE #34 OK, HOWEVER SEE NEW |
| | NOTES PERTAINING TO EQUIPMENT GROUNDING. |
| | |
| | 35)NOTE: NOTE #35, NO. |
| | |
| | 36)NOTE: NOTE #36 OK. |
| | |
| | 37)NOTE:NOTE #37 NO, PLEASE ALSO SEE |
| | NEW NOTES PERTAINING TO MISSING SHEETS. |
| | |
| | 38)NOTE:NOTE #38 OK. |
| | |
| | 39)NOTE: NOTE #39 NO, SEE NEW NOTES |
| | PERTAING TO MISSING SHEETS. |
| | |
| | 40)NOTE: NOTE #40 RESPONSE NOT NEEDED, |
| | PLEASE SEE PLASN, ONCE AGAIN MOST AREAS |
| | REDLINED FOR ABOVE NOTES AND FOR NEW |
| | NOTES TO FOLLOW. |
| | |
| | 41)NOTE: NOTE #41 NO RESPOSE NEEDED. |
| | |
| | 42)NOTE: NOTE #42 NO, AS REQUESTED ON |
| | PREVIOUS REVIEW, PLEASE "REMOVE" ALL |
| | OLD/VOIDED SHEETS FROM SETSS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO THREE |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SEE THESE SHEETS WERE NOTE |
| | REMOVED AND LEFT IN SETS. |
| | |
| | 43)NOTE: NOTE #43 , NO RESPONSE NEEDED. |
| | |
| | |
| | ************** NEW NOTES ************* |
| | |
| | 1)NOTE: PLEASE SEE PANEL LOCATED ON |
| | BATHRM, UNIT L/WD-3. |
| | |
| | 2)NOTE: PLEASE ALSO SEE SMALL APPLIANCE |
| | CIRCUIT SHOWN IN BATH. L/WD-3 |
| | 210.52C1 |
| | |
| | 3)NOTE: PLEASE SEE AREAS FOR DINING |
| | NEED TO BE CLARIFIED. PLEASE SEE |
| | PREVIOUS COMMENTS ABOUTAREAS WHICH |
| | SHOWDEVICES ON SAME CIRCUITS AS SMALL |
| | APPLIAANCE, HOWEVER SOME OF THESE AREAS |
| | ARE NOT AREA ALLOWED TO BE ON SM APPL |
| | CIRCUITS. |
| | PLEASE SEE NEC 210.52B |
| | |
| | 4)NOTE: PLEASE SEE MANY LOCATION ON |
| | PLANS, EQUIPMENT IS LABEL AS MAIN, 1OF 2 |
| | ETC YET, THEY ARE NOT MAINS. |
| | PLEASE SEE METER CENTERS WHICH ARE SHOWN |
| | AS MAINS, PLEASE SEE ELECTRICAL |
| | ROOM/AREA NEXT TO MAIN SWITCH GEAR WHICH |
| | SHOW ADDITIONAL MAINS ALSO. |
| | THE ATCUAL MAINS SHOULD BE THE ONLY |
| | EQUIPMENT LABELED AS SUCH. PLEASE |
| | RE-IDENTIFY ALL OTHER EQUIPMENT. |
| | 215.5,230.2E ETC. |
| | |
| | 5)NOTE: PLEASE CORRELATE A/C, AHU LOADS |
| | FOR UNITS. PLEASE SEE PANEL SCHEDULES |
| | AND ACTUAL LOAD CALCULATIONS. |
| | ONE SHOWS 7.5KW AND THE OTHER SHOWS |
| | 10KW? |
| | |
| | 6)NOTE: PLEASE SEE ELECTRICAL SYSTEMS |
| | FOR BLDG ELECTRICAL SEEMS TO ALL BE |
| | 120/208V, HOWEVER, PLEASE SEE ELECTRICAL |
| | PANELS FOR UNIT SHOW 120/240V? |
| | PLEASE ADJUST. |
| | |
| | 7)NOTE: PLEASE SEE MISSING SD IN L/WD-3. |
| | |
| | 8)NOTE: PLEASE SEE SOME MISSING RECEPTS |
| | PER 210.52, 210.52C1, AS NOTED ON |
| | PREVIOUS COMMENT. |
| | |
| | 9)NOTE: PLEASE SEE MISSING SHEETS FROM |
| | SETS. E-9,10 AND 19. PLEASE SEE ONNLY |
| | OLD/VOIDED SHEETS ARE IN SETS. |
| | UNABLE TO REVIEW THESE PAGES AT THIS |
| | TIME. |
| | |
| | 10)NOTE:PLEASE VERIFY AIC RATINGS SHOWN |
| | ON PANEL SCHEDULESAND RISER. PLEASE |
| | SEE 110K ETC. |
| | THIS IS ONLY A NOTE AND SOME AIC RATINGS |
| | SEEM A LITTLE HIGH, HOWEVER THESE ARE |
| | PERMITTED. HOWEVER, IF SHOWN ON PLANS, |
| | THEN THESE WILL BE REQUIRED TO BE |
| | INSTALLED. |
| | |
| | 11)NOTE: PLEASE SEE FPL VAULT IS NOT |
| | PERMITTED TO HAVE ANY ELECTRICAL IN ROOM |
| | WHICH IS PART OF BLDG ELECTRICAL . |
| | PLEASE SEE LTS, RECEPTS MUST BE REMOVED |
| | FROM PLANS. |
| | AS PER CONVERSATION WITH BILL HARTIGAN |
| | FROM FPL. |
| | PLEASE ALSO BE SURE TO CONTRACT FPL FOR |
| | SIZING OF FPL VAULT AND ANY OTHER |
| | REQUIREMENTS THERE MAY BE. |
| | |
| | 12)NOTE: PLEASE SEE SOME ELEVATION |
| | DRAWINGS SHOW "OLD METER"?? |
| | PLEASE CLARIFY? |
| | 215.5 |
| | |
| | 13)NOTE: PLEASE SEE NOTES PERTAINING TO |
| | "SIGNS FOR ELEVATORS" MENTIONS HEIGHT |
| | REQUIREMENTS FOR LETTERING TO BE MIN OF |
| | 1/8", PLEASE CLARIFY THIS. PLEASE SEE |
| | MIN SIGNAGE IN NFPA, LS 101, NEC ETC, |
| | ALL MENTIONS A MIN OF 1" LETTERS ON A |
| | CONTRASTING BACKGROUND. |
| | |
| | 14)NOTE:PLEASE SEE PANEL HDP-3, WHICH |
| | SHOWS A FUTURE POOL PANEL, YET RISER |
| | SHOWS PANEL INSTALLED AT THIS TIME . |
| | PLEASE ALSO SEE ALL PLANS INDICATE POOL |
| | BEING BUILT WITH BLDG. PLEASE SEE EVEN |
| | THOUGH POOL IS REQUIRED UNDER SEPARATE |
| | PERMIT, ALL ELECTRICAL INFORMATION IS |
| | ALSO REQUIRED ON BASE BLDG PLANS. |
| | PLEASE PROVIDE INFORMATION FOR NEW PANEL |
| | HP. PLEASE PROVIDE FEED, OCP, CONDUIT |
| | ETC. |
| | |
| | 15)NOTE: PLEASE CLARIFY TWO SEPARATE |
| | FEED TO SINGLE RTU'S. RISER SHOWS |
| | 4-RTU'S, HOWEVER, RISER SHOWS POWER |
| | COMING FROM TWO DIFFERENT FEEDS AND |
| | EQUIPMENT. |
| | |
| | 16)NOTE: PLEASE SEE SPECS AND CORRELATE |
| | WITH PLANS, THIS WAS NOTED ON PREVIOUS |
| | COMMENT ALSO. |
| | |
| | 17)NOTE: PLEASE SEE DESIGN FOR FIRE PUMP |
| | HAS NOW COMPLETELY CHANGED. PLEASE SEE |
| | FIRE PUMP IS NOW BEING SHOWN BEING FED |
| | FROM FPL, DIRECTLY, WHICH IS FINE, |
| | HOWEVER FIRE PUMP IS NOW BEING FED FROM |
| | EDP? |
| | PLEASE SEE IF EDP IS SHUT DOWN IN BLDG |
| | DUE TO FIRE, THE FIRE PUMP WOULD NOW BE |
| | DISABLED DUE TO FEED COMING FROM EDP. |
| | PLEASE SEE 695 . |
| | PLEASE SEE ATS AT GENERATOR WOULD BE |
| | REQUIRED TO HAVE A MAIN. PLEASE SEE |
| | RISER ALSO INDICATES ATS AT GENERATOR |
| | HAVING A FEED DIRECTLY INTO FPL VAULT?? |
| | RISER SHOWS TWO FEEDS FROM FPL TO FIRE |
| | PUMP AND EDP. |
| | PLEASE SEE THERE ARE TOO MANY ISSUES |
| | WITH THE WAY THE RISER SHOWS FEEDS TO |
| | TYPE IN A RESPONSE/PLANS REVIEW NOTES. |
| | |
| | PLEASE CALL OR MEET TO GO OVER THIS |
| | SCENERIO. |
| | |
| | 18)NOTE: PLEASE SEE RISER INDICATES ALL |
| | FED INTO FPL VAULT AS OVER HEAD. PLEASE |
| | SEE AS PER NEC AND LOCAL AMENDMENTS, NO |
| | MORE THAN 8' OF "UNPROTECTED" CONDUCTORS |
| | MAY BE INSIDE BLDG. 230.70 |
| | PLEASE SEE THESE APPEAR THEY MAY BE |
| | REQUIRED TO BE "INCASED IN CONCRETE" |
| | ETC. |
| | |
| | 19)NOTE: PLEASE SEE ALL MAINS ARE SHOWN |
| | AS HAVING A SHUNT TRIP, PLEASE CLARIFY |
| | IF THESE MAINS ALSO CONTAIN A MANUAL |
| | MEANS OF DISC LOCATED ON THE OUTSIDE. |
| | 230.76,230.79 |
| | |
| | 20)NOTE: PLEASE SEE ALL MAINS ARE SHOWN |
| | WITH GROUND FAULT PROTECTION ?? |
| | PLEASE SEE 230.95,240.13THIS IS ONLY A |
| | NOTE: |
| | |
| | 21)NOTE: PLEASE SEE 424.3B, OCP FOR |
| | AHU'S INT UNITS IS THE ONLY THING WHICH |
| | IS TO BE AT 125%, LOAD CALCS DO NOT HAVE |
| | TO BE SHOWN AT 125%. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| 2005-04-14 00:00:00 | IN FOR REVIEW. |