Plan Review Notes
Plan Review Notes For Permit 04110228
Permit Number 04110228
Review Stop E
Sequence Number 2
Notes
Date Text
2005-04-15 00:00:00********** UNSAT 2ND REVIEW ***********
  
 REVIEW FOR "THE PLACE VIA CLEMATIS";
 PLEASE SEE PLANS ARE SUBMITTED FOR "PLAN
 REVIEW ONLY" AND NOT SUBMITTED FOR
 PERMIT.
  
 PLEASE SEE MANY COMMENTS FROM PREVIOUS
 REVIEW STTILL NEED TO BE ADDRESSED.
  
 PLEASE SEE NEW COMMENTS DUE TO MORE
 INFORMATIONPROVIDED FROM PREVIOUS SET
 OF PLANS.
 HOWEVER PLEASE SEE NEW COMMENT FOR PAGES
 MISSING. STILL UNABLE TO DO A FULL AND
 COMPLETE REVIEW DUE TO PLANS AND SPECS
 NOT BEING COMPLETE AT THIS TIME.
  
 1)NOTE: NOTE #1, NO, PLEASE SEE LETTER
 FOR ENGINEER TO BE SIGNED, DATED AND
 NOTORIZED FOR LEGAL SIGNATURE.
 TITLE BLOCKS "WHITED OUT" FOR FIRM NAME.
  
 2)NOTE: NOTE #2 NO, PLEASE SEE OUTWARD
 SWING IS NOW SHOWN, HOWEVER NOTE(S)
 REQUESTED ON PLANS FOR PANIC HARDWARE
 ETC WAS NOT ADDED.
  
 3)NOTE: NOTE #3 OK
  
 4)NOTE: NOTE #4 OK
  
 5)NOTE: NOTE #5 NO, PLEASE SEE 620.22-25
 PLEASE ALSO SEE LAYOUT FOR ELEV MACHINE
 ROOMS ARE MISSING ELECTRICAL EQUIPMENT.
 ETC.
  
 6)NOTE: NOTE #6 NO,PLEASE SEE PREVIOUS
 NOTES: MANY WERE ADDED HOWEVER THERE ARE
 STILL SOME MISSING, PLEASE SEE REDLLINED
 PLANS.210.52
  
 7)NOTE:NOTE #7 OK.
  
 8)NOTE: NOTE #8 OK.
  
 9)NOTE: NOTE #9 OK.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 OK.
  
 12)NOTE: NOTE#12 NO, PLEASE SEE SOME
 ROOM DESIGNATIONS WERE ADDED HOWEVER
 SOME AREAS ARE STYILL MISSING.
 PELASE ALSO SEE NEW COMMENTS PERTAINING
 TO "DINING AREA".
  
 13)NOTE: NOTE #13 NO, PLEASE SEE E-19
 WAS NOT SUBMITTED. PLEASE SEE NEW
 COMMENTS PERTAINING TO "NEW " SHEETS
 MISSING.
  
 14)NOTE: NOTE #14 NO, PLEASE SEE SOME
 STILL MISSING. REDLINED.
  
 15)NOTE: NOTE #15 NO.PLEASE SEE MANY
 AREAS RECEPTS ARE SHOWN IN AREAS OTHER
 THAN "DINING AREA". PLEASE SEE SOME ARE
 HALLWAYS, FOYERS, LIVING RMS? ETC.
 PLEASE SEE PREVIOUS COMMENT ABBOUT
 DEIGNATED AREAS.
  
 16)NOTE: NOTE #16, OK.
  
 17)NOTE: NOTE #17 OK.
  
 18)NOTE: NOTE #18 OK.
  
 19)NOTE: NOTE #19 OK, HOWEVER, PLEASE
 SEE NEW NOTES BELOW PERTAINING TO
 LABELING OF METER CENTERS. ETC.
  
 20)NOTE: NOTE #20 OK.
  
 21)NOTE: NOTE #21OK.
  
 22)NOTE: NOTE #22 OK, HOWEVER PLEASE SEE
 NEW NOTES PERTAINING TO LABELING AND
 ELECTRICAL ROOMS. SAME AS #19.
  
 23)NOTE: NOTE #23 NO.
  
 24)NOTE: NOTE #24 OK, PLEASE SEE NEW
 NOTES PERTAINING TO FIRE PUMP FEED FROM
 EM DP.
  
 25)NOTE: NOTE #25 OK.
  
 26)NOTE: NOTE #26 OK.
  
 27)NOTE: NOTE #27 NO.
  
 28)NOTE:NOTE #28 NO, PLEASE SEE
 INFORMATION FOR FIRE PUMP, FIRE PUMP
 CONTROLLER/ATS DISCONNECTIN MEANS WAS
 NOT SUPPLIED.
 PLEASE ALSO SEE NEW NOTES DUE TO FIRE
 PUMP FEED FROM EDP.
  
 29)NOTE: NOTE #29 NO, SPECS FOR
 GENERATOR WERE SUBMITTED , HOWEVER THEY
 DO NOT CORRELATE TO PLANS.
  
 30)NOTE: NOTE #30 NO, PLEASE SEE RISER.
  
 31)NOTE: NOTE #31 NO.
  
 32)NOTE: NOTE #32 NO.
  
 33)NOTE: NOTE #33 OK
  
 34)NOTE: NOTE #34 OK, HOWEVER SEE NEW
 NOTES PERTAINING TO EQUIPMENT GROUNDING.
  
 35)NOTE: NOTE #35, NO.
  
 36)NOTE: NOTE #36 OK.
  
 37)NOTE:NOTE #37 NO, PLEASE ALSO SEE
 NEW NOTES PERTAINING TO MISSING SHEETS.
  
 38)NOTE:NOTE #38 OK.
  
 39)NOTE: NOTE #39 NO, SEE NEW NOTES
 PERTAING TO MISSING SHEETS.
  
 40)NOTE: NOTE #40 RESPONSE NOT NEEDED,
 PLEASE SEE PLASN, ONCE AGAIN MOST AREAS
 REDLINED FOR ABOVE NOTES AND FOR NEW
 NOTES TO FOLLOW.
  
 41)NOTE: NOTE #41 NO RESPOSE NEEDED.
  
 42)NOTE: NOTE #42 NO, AS REQUESTED ON
 PREVIOUS REVIEW, PLEASE "REMOVE" ALL
 OLD/VOIDED SHEETS FROM SETSS AND ONLY
 INSERT NEW REVISED SHEETS INTO THREE
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SEE THESE SHEETS WERE NOTE
 REMOVED AND LEFT IN SETS.
  
 43)NOTE: NOTE #43 , NO RESPONSE NEEDED.
  
  
 ************** NEW NOTES *************
  
 1)NOTE: PLEASE SEE PANEL LOCATED ON
 BATHRM, UNIT L/WD-3.
  
 2)NOTE: PLEASE ALSO SEE SMALL APPLIANCE
 CIRCUIT SHOWN IN BATH. L/WD-3
 210.52C1
  
 3)NOTE: PLEASE SEE AREAS FOR DINING
 NEED TO BE CLARIFIED. PLEASE SEE
 PREVIOUS COMMENTS ABOUTAREAS WHICH
 SHOWDEVICES ON SAME CIRCUITS AS SMALL
 APPLIAANCE, HOWEVER SOME OF THESE AREAS
 ARE NOT AREA ALLOWED TO BE ON SM APPL
 CIRCUITS.
 PLEASE SEE NEC 210.52B
  
 4)NOTE: PLEASE SEE MANY LOCATION ON
 PLANS, EQUIPMENT IS LABEL AS MAIN, 1OF 2
 ETC YET, THEY ARE NOT MAINS.
 PLEASE SEE METER CENTERS WHICH ARE SHOWN
 AS MAINS, PLEASE SEE ELECTRICAL
 ROOM/AREA NEXT TO MAIN SWITCH GEAR WHICH
 SHOW ADDITIONAL MAINS ALSO.
 THE ATCUAL MAINS SHOULD BE THE ONLY
 EQUIPMENT LABELED AS SUCH. PLEASE
 RE-IDENTIFY ALL OTHER EQUIPMENT.
 215.5,230.2E ETC.
  
 5)NOTE: PLEASE CORRELATE A/C, AHU LOADS
 FOR UNITS. PLEASE SEE PANEL SCHEDULES
 AND ACTUAL LOAD CALCULATIONS.
 ONE SHOWS 7.5KW AND THE OTHER SHOWS
 10KW?
  
 6)NOTE: PLEASE SEE ELECTRICAL SYSTEMS
 FOR BLDG ELECTRICAL SEEMS TO ALL BE
 120/208V, HOWEVER, PLEASE SEE ELECTRICAL
 PANELS FOR UNIT SHOW 120/240V?
 PLEASE ADJUST.
  
 7)NOTE: PLEASE SEE MISSING SD IN L/WD-3.
  
 8)NOTE: PLEASE SEE SOME MISSING RECEPTS
 PER 210.52, 210.52C1, AS NOTED ON
 PREVIOUS COMMENT.
  
 9)NOTE: PLEASE SEE MISSING SHEETS FROM
 SETS. E-9,10 AND 19. PLEASE SEE ONNLY
 OLD/VOIDED SHEETS ARE IN SETS.
 UNABLE TO REVIEW THESE PAGES AT THIS
 TIME.
  
 10)NOTE:PLEASE VERIFY AIC RATINGS SHOWN
 ON PANEL SCHEDULESAND RISER. PLEASE
 SEE 110K ETC.
 THIS IS ONLY A NOTE AND SOME AIC RATINGS
 SEEM A LITTLE HIGH, HOWEVER THESE ARE
 PERMITTED. HOWEVER, IF SHOWN ON PLANS,
 THEN THESE WILL BE REQUIRED TO BE
 INSTALLED.
  
 11)NOTE: PLEASE SEE FPL VAULT IS NOT
 PERMITTED TO HAVE ANY ELECTRICAL IN ROOM
 WHICH IS PART OF BLDG ELECTRICAL .
 PLEASE SEE LTS, RECEPTS MUST BE REMOVED
 FROM PLANS.
 AS PER CONVERSATION WITH BILL HARTIGAN
 FROM FPL.
 PLEASE ALSO BE SURE TO CONTRACT FPL FOR
 SIZING OF FPL VAULT AND ANY OTHER
 REQUIREMENTS THERE MAY BE.
  
 12)NOTE: PLEASE SEE SOME ELEVATION
 DRAWINGS SHOW "OLD METER"??
 PLEASE CLARIFY?
 215.5
  
 13)NOTE: PLEASE SEE NOTES PERTAINING TO
 "SIGNS FOR ELEVATORS" MENTIONS HEIGHT
 REQUIREMENTS FOR LETTERING TO BE MIN OF
 1/8", PLEASE CLARIFY THIS. PLEASE SEE
 MIN SIGNAGE IN NFPA, LS 101, NEC ETC,
 ALL MENTIONS A MIN OF 1" LETTERS ON A
 CONTRASTING BACKGROUND.
  
 14)NOTE:PLEASE SEE PANEL HDP-3, WHICH
 SHOWS A FUTURE POOL PANEL, YET RISER
 SHOWS PANEL INSTALLED AT THIS TIME .
 PLEASE ALSO SEE ALL PLANS INDICATE POOL
 BEING BUILT WITH BLDG. PLEASE SEE EVEN
 THOUGH POOL IS REQUIRED UNDER SEPARATE
 PERMIT, ALL ELECTRICAL INFORMATION IS
 ALSO REQUIRED ON BASE BLDG PLANS.
 PLEASE PROVIDE INFORMATION FOR NEW PANEL
 HP. PLEASE PROVIDE FEED, OCP, CONDUIT
 ETC.
  
 15)NOTE: PLEASE CLARIFY TWO SEPARATE
 FEED TO SINGLE RTU'S. RISER SHOWS
 4-RTU'S, HOWEVER, RISER SHOWS POWER
 COMING FROM TWO DIFFERENT FEEDS AND
 EQUIPMENT.
  
 16)NOTE: PLEASE SEE SPECS AND CORRELATE
 WITH PLANS, THIS WAS NOTED ON PREVIOUS
 COMMENT ALSO.
  
 17)NOTE: PLEASE SEE DESIGN FOR FIRE PUMP
 HAS NOW COMPLETELY CHANGED. PLEASE SEE
 FIRE PUMP IS NOW BEING SHOWN BEING FED
 FROM FPL, DIRECTLY, WHICH IS FINE,
 HOWEVER FIRE PUMP IS NOW BEING FED FROM
 EDP?
 PLEASE SEE IF EDP IS SHUT DOWN IN BLDG
 DUE TO FIRE, THE FIRE PUMP WOULD NOW BE
 DISABLED DUE TO FEED COMING FROM EDP.
 PLEASE SEE 695 .
 PLEASE SEE ATS AT GENERATOR WOULD BE
 REQUIRED TO HAVE A MAIN. PLEASE SEE
 RISER ALSO INDICATES ATS AT GENERATOR
 HAVING A FEED DIRECTLY INTO FPL VAULT??
 RISER SHOWS TWO FEEDS FROM FPL TO FIRE
 PUMP AND EDP.
 PLEASE SEE THERE ARE TOO MANY ISSUES
 WITH THE WAY THE RISER SHOWS FEEDS TO
 TYPE IN A RESPONSE/PLANS REVIEW NOTES.
  
 PLEASE CALL OR MEET TO GO OVER THIS
 SCENERIO.
  
 18)NOTE: PLEASE SEE RISER INDICATES ALL
 FED INTO FPL VAULT AS OVER HEAD. PLEASE
 SEE AS PER NEC AND LOCAL AMENDMENTS, NO
 MORE THAN 8' OF "UNPROTECTED" CONDUCTORS
 MAY BE INSIDE BLDG. 230.70
 PLEASE SEE THESE APPEAR THEY MAY BE
 REQUIRED TO BE "INCASED IN CONCRETE"
 ETC.
  
 19)NOTE: PLEASE SEE ALL MAINS ARE SHOWN
 AS HAVING A SHUNT TRIP, PLEASE CLARIFY
 IF THESE MAINS ALSO CONTAIN A MANUAL
 MEANS OF DISC LOCATED ON THE OUTSIDE.
 230.76,230.79
  
 20)NOTE: PLEASE SEE ALL MAINS ARE SHOWN
 WITH GROUND FAULT PROTECTION ??
 PLEASE SEE 230.95,240.13THIS IS ONLY A
 NOTE:
  
 21)NOTE: PLEASE SEE 424.3B, OCP FOR
 AHU'S INT UNITS IS THE ONLY THING WHICH
 IS TO BE AT 125%, LOAD CALCS DO NOT HAVE
 TO BE SHOWN AT 125%.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
2005-04-14 00:00:00IN FOR REVIEW.