Plan Review Notes
Plan Review Notes For Permit 04110228
Permit Number 04110228
Review Stop Z
Sequence Number 1
Notes
Date Text
2004-11-24 00:00:001. FIRST FLOOR IS EXCEEDING THE MAXIMUM
 20 FEET FROM FINISHED FLOOR TO FINISHED
 FLOOR ALLOWED BY ART. IV SECTION 94-113
 (A)(6). PLEASE MODIFY DIMENSION OR
 PROCEED FOR DAC VARIANCE.
 2.PLEASE CONFIRM MEZZANINES ARE IN
 COMPLIANCE WITH PEMISSIBLE PERCENTAGE OF
 FLOOR AREA ACCORDING WITH THE CITY'S
 BUILDING CODE.
 3.PLEASE REVISE LOCATION OF PROPERTY ON
 SITE PLAN AND LANDSCAPE DRAWING TO
 CONFIRM COMPLIANCE WITH MAXIMUM 5 FEET
 SETBACK; AND OVERHANG OF BALCONIES ON
 ROW.
 4.SIDEWALK SHALL BE A MINIMUM OF 8 FEET.
 PLEASE CONFIRM COMPLIANCE WITH THIS
 REQUIREMENT.
 5.PLEASE PROVIDE A TABLE TO SPEFIFY THE
 NUMBER OF RESIDENTIAL UNITS AND THE
 NUMBER OF PARKING SPACES PROVIDED.
 6. TRAVEL LANES IN PARKING GARAGE SHALL
 BE 24 FEET WIDE MINIMUM.
 7. NORTH ELEVATION WAS NOT INCLUDED WITH
 SUBMITTED DRAWINGS.
 8.PLEASE PROVIDE A TABLE TO CONFIRM
 COMPLIANCE WITH OPEN SPACE REQUIREMENT.
 9.OPEN SPACE SHALL BE DESIGN ACCORDING
 WITH OPEN SPACE DESIGN GUIDELINE; AND
 SHALL INCLUDE SEATING AREA FOR THE
 PUBLIC, LIGHTING AND AT LEAST ONE
 DRINKING FOUNTAIN.
 10.PLEASE PROVIDE A TABLE TO CONFIRM
 COMPLIANCE WITH 15% LANDSCAPE
 REQUIREMENT FOR THE ROOFTOP TERRACE.
 11.ON ROOFTOP TERRACE, CLIMATE
 CONTROLLED STRUCTURES ARE LIMITED TO THE
 MINIMUM AREA NECESSARY TO ACCOMODATE
 STRUCTURES THAT ARE SECONDARY AND
 INCIDENTAL TO THE PRIMARY ROOFTOP
 AMENITY.
 11. TREES PLANTED ON ROSEMARY AVENUE
 SHALL BE CONISTENT WITH EXISTING TREES
 ON THE SAME STREET. RECOMMENDED SPECIE:
 CATHEDRAL OR HIGH RISE LIVE OAK.
 12. BANYAN BOULEVARD SHALL PROVIDE SHADE
 TREES ALONG THE SIDEWAK. RECOMMENDED
 SPECIE: DAHOON HOLLY.
 13.ARCHITECTURAL DESIGN GUIDELINES:
 - DOOR OR WINDOWS SHALL BE CENTERED WITH
 THE ASSOCIATED BALCONY.
 - FISR FLOOR WINDOWS SHALL HAVE A KICK
 PLATE BETWEEN 18 AND 42 INCHES MINIMUM.
 - ARCHES ON THE TOP FLOOR ARE NOT
 CONSISTENT WITH THE OVERALL BUILDING
 DESIGN.
 - CANTILEVERED BALCONIES SHALL EXTEND NO
 MORE THAN 3 FEET FROM THE BUILDING
 FACADE AND SHALL BE VISIBLY SUPPORTED BY
 BRACKETS.
 - ALL WINDOWS SHALL BE OPERABLE AS HUNG
 OR CASEMENT.
  
  
  