| 2004-12-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | FHA-98 DISIGN MANUAL |
| | |
| | 1) SHTS I-1 & I-2 FIRM LICENSE NUMBER |
| | REQUIRED ON THE TITLE BLOCK, SIGNATURE |
| | REQUIRED, AND PRINTED NAME REQUIRED. |
| | FAC |
| | 61G1-16.004(2)(5)(6, 61G1-16.003 AND FS |
| | 481.219. - SUBMIT PROOF OF LEGAL |
| | SIGNATURE IN THE FORM OF A DRIVERS |
| | LICENSE, VOTERS REG. CARD ECT., AND |
| | SUBMIT A SIGNED/SEALED/DATED NOTORIZED |
| | LETTER WITH YOUR LEGAL SIGNATURE FOR |
| | OUR |
| | FILES. |
| | 2)SHT I-1, AN RPZ BACKFLOW, INSTALLED |
| | BY |
| | A LICENSED PLUMBING CONTRACTOR IS |
| | REQUIRED FOR THE IRRIGATION SYSTEM. |
| | SHOW |
| | LOCATION ON PLANS. SECTIONS 608.13.2 |
| | AND |
| | 104.2.1 |
| | 3) SHTS A-11 & A-12 SHT INDEX STATES |
| | PARITAL 3RD-7TH FLOOR PLAN 1, BUT NOTE |
| | 5 |
| | STATES 3RD-5TH FLOOR PLAN. PLEASE |
| | CLARIFY. SECTION 104.2.1 |
| | 4) SHTS A-9, A-15 SUBMIT CALCULATIONS |
| | FOR PRIMARY AND SECONDARY ROOF DRAINS |
| | PER SECTIONS 1106, AND 1107 AND ALL SUB |
| | SECTIONS. SHOW SF OF EACH AREA WITH 1/2 |
| | AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS AND ROOF AREA FROM ABOVE THAT |
| | DRAINS ON TO THE ROOF ADDED TO THE |
| | CALCULATIONS. SHOW THE LOCATION OF ALL |
| | PRIMARY AND SECONDARY ROOF DRAINS AND |
| | THE SCUPPERS. ALSO SEE SHTS A-17 & |
| | A-18. |
| | THIS APPLIES TO THE ROOF DECK AREAS. |
| | 5) SHTS A-9 & A-15 SHOW THE LOCATION |
| | AND |
| | SIZE OF ALL SECONDARY ROOF DRAINS AND |
| | THE SCUPPERS. SECTION 104.2.1. |
| | 6) SHTS A-15 & A-16 SUBMIT CALCULATIONS |
| | FOR MINIMUM FACILITIES PER TABLES |
| | 1003.1 |
| | AND 403.1. SHOW THE SF OF EACH COMMON |
| | AREA AND TOTAL COMMON AREA IN |
| | CALCULATIONS. |
| | 7) ARCHITECTURAL SHEETS, THE DATE |
| | PREPARED AND THE PRINTED NAME OF THE |
| | PERSON RESPONSIBLE FOR THE DOCUMENT ARE |
| | REQUIRED PER FAC 61G1-16.004(4)(6) AND |
| | FS 481.2055 |
| | 8) SHTS A30, A-31, & A-32 INDICATE |
| | SPECIFICATION "A" OR "B" FOR EACH UNIT |
| | OR BATHROOM AS REQUIRED ON PAGE 7.35 |
| | FHA |
| | DESIGN MANUAL. |
| | 9) SHTS A30, A-31, & A-32 SHOW THE SIZE |
| | OF THE OPENINGS FOR ALL COVERED WATER |
| | CLOSETS. MINIMUM 33" REQUIRED. SEE |
| | PAGES |
| | 6.5 AND 6.7 FHA DESIGN MANUAL. - THE |
| | 18" |
| | FROM THE WALL TO THE CENTERLINE OF THE |
| | W/C IS AN ABSOLUTE MEASURMENT. SEE |
| | FIGS. |
| | PAGE 6.3 AND 6.5 |
| | 10) SHT A33 MENS & WOMENS RESTROOMS, |
| | SHOW CLEAR FLOOR SPACE FOR EACH |
| | ACCESSIBLE FIXTURE. SECTIONS 11-4.16.2, |
| | 11-4.19.E, & 11-4.22.3. THE TURNING |
| | AREA |
| | SHALL BE SHOWN IN THE TOILET ROOM, NOT |
| | IN THE ACCESSIBLE STALL. ALSO SHOW |
| | WATER |
| | CLOSED HEIGHT 11-4.16.3. GRAB HEIGHT |
| | MAX |
| | 36". SHOWN AS 48" ON DETAIL BEHIND W/C. |
| | SHOW FLUSH CONTROL 11-4.16.5. SHOW |
| | URINAL HEIGHT 11-4.18.2. THE CENTERLINE |
| | OF THE W/C SHALL BE 18" TO THE WALL, |
| | NOT |
| | 20" AS SHOWN. (SEE FIG 28). FOR THE |
| | LAVS |
| | SHOW KNEE CLEARANCE 11-4.19.2, FOR THE |
| | SHOWER SHOW CONTROLS 11-4.21.5, SHOWER |
| | UNIT 11-4.21.6, AND CURB 11-4.21.8. |
| | 12) SHT A33 DETAIL #1 IN BOTH MENS AND |
| | WOMENS RESTROOM. THE DOUBLE LAVS TO BE |
| | 34" IN HEIGHT AND HAVE A CLEARANCE OF |
| | 29". SEE FIG 31 - SECTION 11-4.19.2 |
| | 13) A DRINKING FOUNTAIN IS REQUIRED IN |
| | THE COMMON AREA. SUBMIT A DETAIL |
| | COMPLYING WITH SECTION 11-4.15 AND ALL |
| | SUBSECTIONS & 11-4.1.3(10)(A) FOR THOSE |
| | WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | 14) SHT A36 SHOW HEIGHT AND WIDTH OF |
| | SCUPPER OPENINGS ON THE DETAIL. |
| | 15) A PROFESSIONAL ENGINEER SHALL SIGN |
| | HIS NAME. INITIALS ARE NOT APPROVED PER |
| | THE RULING BY FBPE. SUBMIT AN EXAMPLE |
| | OF |
| | THE ENGINEERS LEGAL SIGNATURE BY WAY OF |
| | DRIVERS LICENSE, VOTERS REG. ECT, AND A |
| | SIGNED SEALED NOTORIZED LETTER |
| | INDICATING YOUR LEGAL SIGNATURE FOR OUR |
| | FILES. FAC 61G15.23.002(1)(2) AND FS |
| | 471.025. - THIS IS FOR ALL ENGINEERED |
| | SHEETS. |
| | 16) ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME, LICENSE NUMBER AND |
| | CERTIFICATE OF AUTHORIZATION NUMBER OF |
| | THE ENGINEERING BUSINESS ON EACH SHEET. |
| | FAC 61G15-23.002(2) |
| | 17) SHTS P-1 & P-2 PD'S SIZING AND |
| | PIPING SIZING NOT CORRECT FOR ALL PD'S. |
| | RECHECK SIZING PER TABLES 1106.2 & |
| | 1106.3 - SHOW ALL SF AND PIPE SIZES. |
| | 18) SUBMIT MANUF. SPECIFICATION SHEETS |
| | FOR ELEVATOR SUMP PUMPS AND THE STORM |
| | WATER SUMP PUMPS. PUMPS INFORMATION |
| | SHALL SHOW LISTING. SECTION 303.4 |
| | 19) SHTS P-3, & P-4 STORM PIPE SIZING |
| | NOT CORRECT AS WELL AS THE EMERGENCY |
| | ROOF DRAIN PIPING (SECONDARY ROOF |
| | DRAINS). SEE TABLES 1106.2 & 1106.3. NO |
| | SF SHOWN FOR PD'S AT COL. LINE 5/G-F1 |
| | AND COL. LINE 6/F-E2. PD BETWEEN COLS. |
| | 8.1 & 8.3 NORTH OF STAIRWAY #2 NO ADDED |
| | TO THE SYSTEM. DOUBLE CHECK ALL PIPE |
| | SIZES AND SHOW ADDITION OF ALL SF AS |
| | THEY ACCUMULATE IN THE STORM BLDG |
| | DRAIN. |
| | SECTION 104.2.1. |
| | 20) SHT P-3 MANY UNITS INDICATE 1-1/2" |
| | TRAP FOR THE W/M. MINIMUM 2" TRAP |
| | REQUIRED. TABLE 709.1 |
| | 21) SHT P-3 UNIT L/W-B-1 SHOWS 2" 2FU |
| | FROM KIT. SINK, BUT CHANGES TO 4" 91 FU |
| | DOWNSTREAM. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 22) SHT P-4 STORM RISER DIAGRAM, SF FOR |
| | PD AT COL. LINES 10/C2, 12/C2, 11/E2, & |
| | TRASH ROOM BY STAIR #3 NOT SHOWN. |
| | PLEASE |
| | INDICATE SF FOR EACH PER TABLES 1106.2 |
| | AND 1106.3. SECTION 104.2.1 |
| | 23) SHT P-4 UNITS L/W-E-2 & L/W-E-3 |
| | FITTING NOT INSTALLED PER SECTION |
| | 706.3. |
| | EACH UNIT SHOWS 76 FU, BUT FLOOR PLAN |
| | SHOWS 2 RISERS EACH UNIT ONE WITH 68 FU |
| | AND THE OTHER WITH 76 FT. PLEASE |
| | CLARIFY |
| | 24) SHT P-4 MOST W/M'S SHOW 1-1/2" |
| | TRAPS |
| | BUT TABLE 709.1 REQUIRES 2" TRAPS. |
| | 25) SHT P-4 UNABLE TO FIND SOME RISERS |
| | SHOWN ON THE FLOOR PLAN. PLEASE SUBMIT |
| | A |
| | SANT. RISER DIAGRAM FOR EACH RISER |
| | SHOWN |
| | ON THE FLOOR PLAN. SECTIONS 104.2.1 AND |
| | 104.3.1.1 |
| | 26) ALL AAV'S INSTALLED BELOW THE 5TH |
| | FLOOR SHALL HAVE A RELIEF VENT |
| | INSTALLED |
| | PER SECTION 607.3.2. (SHOW ON THE SANT. |
| | RISER DIAGRAM). |
| | 27) SHT P-5 CHECK ALL PIPE SIZING ON |
| | THE |
| | STORM SYSTEM AND SHOW ALL PIPE SIZES. |
| | SECTION 104.2.1 AND TABLES 1106.2 AND |
| | 1106.3. |
| | 28) SHT P-5 UNIT L/W-B-4 W/C NOT |
| | VENTED, |
| | AND UNIT L/W-B-5 W/C AND TUB NOT |
| | VENTED. |
| | SECTION 902.1. |
| | 29) SHT P-6 RECHECK ALL PIPE SIZES AND |
| | SHOW ALL PIPE SIZES ON PLANS. - UNITS |
| | L/W-B-4 AND L/W-A-1 W/C'S ARE NOT |
| | VENTED. SECTION 902.1. |
| | 30) ALL SHTS ALL AAV'S 4TH FLOOR AND |
| | BELOW REQUIRE A RELIEF VENT. SECTION |
| | 607.3.2. SHOW ON FLOOR PLAN AND SANT. |
| | RISER DIAGRAM. SECTION 607.3.2. |
| | 31) SHT P-8 UNIT C-5 W/C NOT VENTED 2ND |
| | BATH. SECTION 902.1 - SHOW ALL STORM |
| | PIPING SIZES. UNIT C-4L BATHROOM GROUP |
| | CONNECTED TO VENT STACK. SHALL BE |
| | CONNECTED TO DRAIN STACK. - STORM AT |
| | COL |
| | 10 BY THE M/B UNIT B-4 IS INCORRECTLY |
| | IDENTIFIED. SECTION 104.2.1. |
| | 32) SHT P-9 UNITS C-5 BATHROOM EITH |
| | SIDE |
| | OF STAIRWAY #2, W/C'S NOT VENTED AND |
| | LAVS/TUBS ARE CONNECTED TO THE VENT |
| | LINE |
| | NOT THE DRAIN STACK AS REQUIRED. |
| | 33) SHT P-10 UNITS C-5, C-6L &D-1A, W/C |
| | NOT VENTED SECTION 902.1. LAV/TUB |
| | CONNECTED TO THE VENT STACK, NOT THE |
| | WASTE STACK AS REQUIRED. |
| | 34) SHT P-11 AUXILLORY HORIZONTAL DRAIN |
| | PIPE SIZE NO SIZED CORRECTLY. TABLE |
| | 11106.3. |
| | 35) THE TRASH CHUTE REQUIRES AN "N36" |
| | VACUUM BREAKER FOR BACKFLOW PROTECTION. |
| | SECTION 608.13.6. |
| | 36) SHT P-12 AUXILLARY HORIZONTAL DRAIN |
| | PIPE SIZE PER 1106.3. |
| | 37) SHTS P-13, & P-14 AUXILLARY ROOF |
| | DRAIN NEAR POOL CAN NOT BE A TRIPPING |
| | HAZARD. PLEASE SUBMIT A DETAIL FOR S/27, |
| | S/28, S/29, & S/30 SECONDARY DRAINS. |
| | SECTION 104.2.1. |
| | 38) SHT P-22 NO WATER SUPPLY SHOWN TO |
| | THE TRASH ROOM FOR THE TRASH CHUTE. |
| | PLEASE SHOW ON PLANS. SECTION 104.2.1 |
| | 39) SHTS P-24, P-25, P-26, P-27, & P-28 |
| | DO NOT MEET CODE REQUIREMENTS. IN MANY |
| | CASES THESE ARE THE CODE ISSUES NOT |
| | ADDRESSED. |
| | A) OFFSET VENTS ARE REQUIRED WHEN |
| | HORIZONTAL OFFSETS ARE USED. SECTION |
| | 915 |
| | B) NO HORIZ. DRY VENTS. SECTION 905.3 |
| | C) STACK DRAIN SHALL CONNECT DOWNSTREAM |
| | OF THE BATHROOM GROUP FIXTURES. SECTION |
| | 909.1 |
| | D) KITCHEN SINK SHALL NOT DRAIN THROUGH |
| | THE WET VENT. SECTION 909.1. |
| | E) MAIN VENT REQUIRED AT TOP OF STACKS. |
| | SECTION 903.1. |
| | F) CLEANOUTS REQUIRED AT THE BASE OF |
| | EACH STACK. SECTION 708.3.4. |
| | G) HORIZONTAL BRANCH CONNECTION TO A |
| | HORIZONTAL STACK OFFSET. SECTIONS 711.2 |
| | & 711.3. |
| | H) VENTING REQUIRED 901.2.1 |
| | I) STACK INSTALLATION 910.2 |
| | THE RISERS ARE NOT CLEAR TO THEIR INTENT |
| | AND THE USE OF TEE FITTINGS AS SHOWN ON |
| | THE RISERS ARE NOT APPROVED. (BULL HEAD |
| | TEES ARE SHOWN WHERE THE SEWAGE IS NOT |
| | DIRECTED IN THE DIRECT OF FLOW. CHECK |
| | ALL RISERS FOR CODE REQUIREMENTS. |
| | 40) SHTS P-24, P-25, P-26, P-27, 7 P-28. |
| | SANITARY RISER DIAGRAMS DO NOT REFLECT |
| | THE FLOOR PLAN. THE FIXTURES FOR THE |
| | MEZZANINE LEVEL ARE SHOWN ABOVE THE |
| | MEZZANINE LEVEL WHEN THE PIPING WILL BE |
| | BELOW THE MEZZANINE LEVEL. FIXTURES FOR |
| | THE SECOND FLOOR ARE SHOWN ABOVE THE |
| | SECOND FLOOR WHEN THE PIPING WILL BE |
| | UNDER THE SECOND FLOOR. THE FIXTURES FOR |
| | THE THIRD THRU THE EIGHT FLOOR ARE SHOWN |
| | BELOW THE TERRACE FLOOR. SHOULD BE BELOW |
| | THE EIGHT FLOOR. SECTION 104.2.1 |
| | 41) NO INFORMATION CAN BE READ ON THE |
| | ENGINEER'S SEAL. THE SEAL SHALL BE AN |
| | IMPRESSION TYPE THAT IMPARTS THE |
| | REQUIRED INFORMATION ON THE PLANS. FAC |
| | 61G15-23.001(1) & FS 471.025 |
| | 42) SHTS P-28 & P-29 SANT. BLDG. DRAIN |
| | ISOMETRIC, SHOW ALL PIPE SIZES AND SHOW |
| | THE DFU'S AS THEY ACCUMULATE IN THE |
| | SYSTEM. SECTION 104.2.1 & TABLE |
| | 710.1(1) |
| | 43) SHT P-31 AIR CHAMBERS ARE NOT |
| | APPROVED. DELETE FROM ALL RISERS. WATER |
| | HAMMER ARRESTORS REQUIRED BY SECTION |
| | 604.9 SHALL BE LOCATED AT ALL QUICK |
| | CLOSING VALVES, (W/M, ICE MAKER, AND |
| | DISH WASHER), AND SHALL BE LOCATED NEAR |
| | THE FIXTURE. PDI-WH 201 & MANUF. |
| | INSTALLATION INSTRUCTIONS. |
| | 44) SHTS P-33 & P-34 AUXILLARY ROOF |
| | DRAINS ON SOME SYSTEMS ARE UNDERSIZED. |
| | PLEASE SIZE PER TABLE 1106.3. |
| | 45) SHT P-35 STORM DRAIN RISER III, SHOW |
| | ALL PIPE SIZES AND SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM. RECHECK ALL |
| | PIPE SIZES PER TABLES 1106.2 & 1106.3 AS |
| | SOME PIPE SIZES ARE NOT CORRECT. |
| | 46) SHT P-36 WATER HEATER DETAIL. |
| | THERMAL EXPANSION CONTROL IS REQUIRED |
| | PER SECTION 607.3.2. PLEASE INDICATE HOW |
| | THIS WILL BE ACCOMPLISHED. |
| | 47) SHT P-36 GENERAL PLUMBING NOTES: |
| | #2 1/4" FOR 2-1/2" & SMALLER PIPE. |
| | TABLE 704.1 INDICATE ON NOTE. |
| | #16 AIR CHAMBERS ARE NOT APPROVED. |
| | DELETE SYMBOL & REFERENCE. SECTIONS |
| | 604.9 AND 104.2.1. |
| | 48) SUBMIT A WATER RISER DIAGRAM IN |
| | ISOMETRIC FORM FOR THE BLDG WATER PIPING |
| | SHOWING ALL PIPE SIZES, VALVES, WATER |
| | HAMMER ARRESTORS, AND LOCATION OF ALL |
| | RISER CONNECTIONS TO THE DISTRIBUTION |
| | PIPING. |
| | 49) SUBMIT A CONDENSATE DRAIN ISOMETRIC |
| | WITH ALL PIPE SIZES, LOCATION OF RISER |
| | CONNECTIONS, RISERS, TERMINATION POINT |
| | OF THE RISERS (VENTS), AND INDICATE |
| | WHERE THE CONDENSATE DRAINS TO OUTSIDE |
| | OF THE BUILDING. SECTION 104.2.1. |
| | 50) SUBMIT RISERS AND BLDG ISOMETRIC FOR |
| | THE EMERGENCY T&P VALVE DISCHARGE LINE |
| | AND THE EMERGENCY PAN DRAIN LINE FOR THE |
| | WATER HEATER. SHOW ALL PIPE SIZE FOR ALL |
| | PIPING. SECTIONS 104.2.1 & 104.3.1.1. |
| | 51) PLANS DO NOT APPEAR TO BE 100% AND |
| | MORE COMMENTS MAY FOLLOW ON THE NEXT |
| | REVIEW DEPENDING ON THE RESPONSE OF THIS |
| | REVIEW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |