2004-12-06 00:00:00DENIED:
 1.INDICATE HOW THE MAKE AIR FOR THE
 GARAGE AREA WILL BE ACHIEVED.
  
 2.PLAN SHEET M-1 THROUGH M-5,
 ELEVATOR LOBBY SUPPLY AIR FROM ABOVE.
 PLAN DOES NOT INDICATE ANY FIRE SMOKE
 DAMPERS OR SHAFT.PER 2001 FBC(M)607.6,
 SPECIFIC LOCATION OF FIRE DAMPERS & FIRE
 DOORS ARE TO BE IDENTIFIED ON PLANS.
 DETAIL OF FIRE DAMPERS & ACCESS DOORS
 ARE ALSO REQUIRED.
  
 3.PLEASE CLARIFY CONDENSING UNITS
 LOCATED IN THE GARAGE AREA UNDER A ROOF
 WITH NO CROSS VENTILATION.
  
 4.M-1 ELEVATOR 2 & 3 LOBBY AREA FLEX
 DUCT IS INDICATED AT THE RATED
 PENETRATION. PER 2001 FBC(M)607.1.3
 EXCEPTION #3 ITEMS 1 THROUGH 4 SHALL
 APPLY.
  
 5.DUCT FOR THIS RISER REDUCES
 DOWNWARD UNIT THE 1ST FLOOR AND THEN
 INCREASES AGAIN, PLEASE CLARIFY.
  
 6.M-2 EF5 & EF6 LOCATED AT THE FLOOR
 LEVEL IN COMPACT CAR SPACES.
 PROTECTION FROM DAMAGE REQUIRED PER
 2001
 FBC(M)303.4.
  
 7.M-3 EF-7 IS LOCATED THAT THE
 EXHAUST WILL BE RECIRCULATED BACK INTO
 THE GARAGE ENTRANCE IN VIOLATION OF
 501.3.
  
 8.M-3 EF-2,3,4,7, & 8 TERMINATING AT
 THE ALLEY.PER 2001 FBC(M)705.1.THIS
 APPLIES FOR OPENINGS INTO THE ALLEY
 WAY.
  
 9.M-5 SF-1 TO STAIR #1 MAKE-UP AIR
 SHALL NOT BE TAKEN FROM PARKING AREAS,
 STREETS OR ALLEYS PER 2001
 FBC(M)401.5.1.
  
 10. M-6 EMERGENCY GENERATOR ROOM, A
 FIRE
 DAMPER IS INDICATED ON THE GENERATOR
 INTAKE TO THE RADIATOR.PROVIDE THE
 MANUFACTURER APPROVAL FOR THIS
 APPLICATION.
  
 11. M-6 PLEASE CLARIFY 6" MUFFLER
 EXHAUST.NOTATION INDICATES 6" PIPE
 UNDER SLAB.WILL THIS BE POURED INTO
 THE SLAB BETWEEN THE FPL VAULT OR
 PENETRATING THROUGH THE VAULT
 UNDERGROUND?
  
 12. PROVIDE ELEVATION FOR THE
 TERMINATION OF THE MUFFLER EXHAUST.
 PROVIDE DISTANCE FROM THE TERMINATION
 TO
 WINDOWS AND AIR INTAKES.
  
 13. PROVIDE DETAIL FOR THE FILL PIPING
 AND LOCATION OF THE FILL FOR THE FUEL
 OIL TO THE GENERATOR.
  
 14. M-3 THROUGH M-6 INDICATE DRYER &
 TOILET EXHAUST TERMINATING INTO THE
 GARAGE.PER 2001 FBC(M)501.3, EXHAUST
 SHALL DISCHARGE OUTDOORS WHERE IT WILL
 NOT CREATE A NUISANCE OR BE
 RECIRCULATED
 BY THE VENTILATION SYSTEM.EXHAUST
 SHALL NOT BE DIRECTED ONTO WALKWAYS PER
 2001 FBC(M)401.5.2.
  
 15. M-9 & M-10 INDICATE SHEET 9 OF 21
 AND 10 OF 21.THERE ARE ONLY 17
 MECHANICAL SHEETS.
  
 16. RETURN AIR MISSING FROM UNIT
 L/WB-4.
 CERTIAN UNITS INDICATE RETURN AIR
 PLENUMS.PER 2001 FBC(M)602.2.1, NO
 COMBUSTIBLES ALLOWED ABOVE THE CEILING
 IN THE RETURN AIR PLENUM.
  
 17. M-11 INDICATE ACCESS AND CLEARANCES
 FOR THE DUCTWORK INSTALLED UNDER THE
 POOL.WILL THIS BE INSULATED?
  
 18. M-11 & M-12 CONDENSING UNITS
 LOCATED
 ON THE ROOF OR ARE THEY ENCLOSED?
 PLEASE NOTE, CONDENSING UNITS LOCATED
 ON
 THE ROOF SHALL COMPLY WITH 2001 FBC
 1511.7 FOR THE CLEARANCE BETWEEN THE
 ROOF SURFACE AND THE BOTTOM OF THE
 SUPPORT RAIL.
  
 19. M-15 CORRIDOR PRESSURIZATION DETAIL
 SHOWS 2" FIRE RATED CHASE.SHOULD THIS
 READ 2 HOUR FIRE RATED CHASE?
  
 20. M-16 RTU SCHEDULE INDICATES ALL
 UNITS 60 TONS, THIS IS COMBINED.THE
 PLAN INDICATES 2 EACH 10.5 TON & 2 EA
 13
 TON UNITS.DUCT SMOKE DETECTORS ARE
 REQUIRED IN ACCORDANCE WITH 2001
 FBC(M)606.
  
 21.M-16 SPECIFIC DRYERS INDICATED ON
 DRYER SCHEDULE - SOME MODELS WOULD
 STILL
 EXCEED THE 25 FT MAXIMUM REQUIREMENT.
 SPECIFIC DRYERS ARE TO BE INSTALLED FOR
 FINAL INSPECTION.
  
 22. M-17 PRIMARY AIR CHASE DETAIL SHOWS
 ACCESS DOOR.FIRE/SMOKE DAMPERS &
 ACCESS DOORS SHALL ALSO BE LOCATED ON
 THE PLAN PER 2001 FBC(M)607.6.
  
 23. PROVIDE OUTSIDE AIR CALCULATIONS
 FOR
 ALL AREAS, RESIDENCE, COMMON AREAS,
 EQUIPMENT RMS, MECH, ELEC, PUMP RMS,
 STORAGE RMS.SHOW COMPLIANCE WITH 2001
 FBC(M)402 OR TABLE 403.3.
  
 24. M-16 SMOKE CONTROL SEQUENCE OF
 OPERATION.SMOKE CONTROL SHALL COMPLY
 WITH ONE OF THE ITEMS DESCRIBED IN
 412.5
 OF THE 2001 FBC.INDICATE WHICH
 PROCESS
 WILL BE USED FOR REMOVAL OF PRODUCTS OF
 COMBUSTION.
  
 25. PROVIDE MANUAL J CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC CHAPTER 13.
  
 26. PROVIDE DETIAL FOR THE CONDENSATE.
 INDICATE TERMINATION.
  
 PLEASE NOTE, ADDITIONAL COMMENTS NOT
 ADDRESSED IN THIS REVIEW MAY OCCUR ON
 RESUBMITTAL DUE TO THE REPONSE TO
 COMMENTS AND THE INCOMPLETION OF PLANS
 SUBMITTED.
  