| 2004-12-15 00:00:00 | 1) PLEASE INDICATE LOCATION OF FIRE |
| | COMMAND CENTER ON PLANS. |
| | |
| | 2) KNOX-BOXES WILL BE REQUIRED. |
| | |
| | 3) BUILDING IS TO MEET HIGH-RISE |
| | REQUIREMENTS OF THE APPLICABLE |
| | BUILDING AND FIRE CODES. |
| | |
| | 4) A TWO-HOUR FIRE SEPARATION IS |
| | REQUIRED BETWEEN THE PARKING AND OTHER |
| | AREAS OF THE BUILDING. |
| | |
| | 5) S-3 DOOR NEAR LOADING ZONE 2. PLEASE |
| | EXPLAIN. |
| | |
| | 6) S-2 DOOR NEAR ALLEY. PLEASE EXPLAIN. |
| | |
| | 7) TACTILE SIGNAGE REQUIRED AT EXIT |
| | DOORS. |
| | |
| | 8) ALL SHAFTS THAT ARE LARGE ENOUGH |
| | FOR PERSONS TO FALL INTO MUST |
| | BE MARKED SHAFTWAY IN 6" LETTERS. |
| | |
| | 9) THE FIRE ALARM SYSTEM MUST MEET |
| | THE REQUIREMENTS FOR CENTRAL STATION |
| | SERVICE. |
| | |
| | 10) TWO FIRE DEPARTMENT CONNECTIONS |
| | ARE REQUIRED FOR THE BUILDING SINCE |
| | IT IS A HIGH-RISE BUILDING. |
| | |
| | 11) ALL NEW STAIRS AND RAMPS SHALL |
| | HAVE HANDRAILS ON BOTH SIDES. |
| | |
| | 12) LOCKING KNOX-BOX CAPS ARE REQUIRED |
| | ON THE FIRE DEPARTMENT CONNECTIONS. |
| | |
| | 13) PLEASE PROVIDE PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS FOR HANDRAILS |
| | AND GUARDRAILS. |
| | |
| | 14) PLEASE PROVIDE OCCUPANT LOADS |
| | FOR POOL DECK AND COMMON PATIO. |
| | |
| | 15) PLEASE DISPLAY ALL EXISTING OR |
| | NEW FIRE HYDRANTS ON SITE. |
| | |
| | 16) PARKING SPACES SURROUND STAIR # 1 |
| | ON PAGE A-3. PLEASE EXPLAIN ACCESS. |
| | |
| | 17) PARKING SPACES SURROUND STAIR # 3 |
| | ON PAGE A-4. PLEASE EXPLAIN ACCESS. |
| | |
| | 18) BUILDING LOCATED IN FIRE LIMITS. |
| | CERTAIN RESTRICTIONS APPLY. PLEASE |
| | SEE APPENDIX F, LOCAL AMENDMENTS. |
| | |
| | 19) EXIT SIGN PLACEMENT SHALL NOT |
| | EXCEED 100 FEET. |
| | |
| | 20) ENSURE THAT ALL DOOR SWINGS ARE |
| | INCORRECT. |
| | |
| | 21) THE DOOR APPEARS TO BE MISSING |
| | FROM STAIR # 1ON PAGE A-7. |
| | |
| | 22) PLEASE EXPLAIN EXITING FROM |
| | MEZZANINE LEVEL. |
| | |
| | 23) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATIONS FOR WALLS AND CEILINGS. |
| | |
| | 24) SIGNS REQUIRED IN STAIRWELLS |
| | INDICATING TOP, BOTTOM, FLOOR NUMBER, |
| | ROOF ACCESS, AND THE IDENTITY. |
| | |
| | 25) WOOD TRELLIS NOTED ON ROOF |
| | TERRACE. AGAIN LOCATED IN FIRE LIMITS. |
| | |
| | 26) ARE THE DOORS AT THE MAIN LOBBY |
| | ROOF TERRACE SWINGING IN THE PROPER |
| | DIRECTION. |
| | |
| | 27) IS THE WALKWAY TO THE EXITS ON ROOF |
| | TERRACE SLIP RESISTANT. |
| | |
| | 28) BUILDING ADDRESS REQUIRED. A MINIMUM |
| | |
| | OF AT LEAST 6" HIGH NUMBERS ARE |
| | REQUIRED. |
| | |
| | 29) CANVAS AWNINGS REQUIRED TO BE |
| | FLAME RETARDANT. |
| | |
| | 30) PLEASE DISPLAY FIRE SPRINKLER |
| | LOCATIONS IN TRASH CHUTE SECTION. |
| | |
| | 31) SMOKE DETECTORS ARE REQUIRED ON |
| | EVERY LEVEL OF RESIDENTIAL UNITS. |
| | |
| | 32) PLEASE INDICATE ON PLANS THAT |
| | ALL SMOKE DETECTORS SHALL BE PLACED |
| | NO CLOSER THAN THREE FEET FROM |
| | AIR CONDITIONER DIFFUSERS. |
| | |
| | 33) PLEASE INDICATE STRETCHER |
| | ACCESSIBLE |
| | ELEVATORS IN THE BUILDING. |
| | |
| | 34) PLEASE VERIFY STANDBY POWER |
| | REQUIREMENTS. |
| | |
| | 35) ELEVATOR WARNING SIGNS REQUIRED. |
| | |
| | 36) LIFE SAFETY ROUTES ON PAGE A-38 |
| | ARE GOING THRU PARKING SPACES. PLEASE |
| | EXPLAIN RATIONALE. |
| | |
| | 37) PLEASE PROVIDE WATER COLUMN |
| | REQUIREMENTS FOR THE STAIRWELL |
| | PRESSURIZATION SYSTEMS. |
| | |
| | 38) THERE ARE NOT ENOUGH EXIT SIGNS |
| | SHOWN. |
| | |
| | 39) THE CORRIDORS NEED MORE EXIT |
| | SIGNS. |
| | |
| | 40) PLEASE INDICATE WHAT THE VOICE |
| | EVACUATION MESSAGE OF THE FIRE ALARM |
| | SYSTEM WILL SAY. |
| | |
| | 41) ELECTRONIC SWITCHES REQUIRED ON |
| | FIRE LINE BACKFLOW DEVICE. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |