Plan Review Notes
Plan Review Notes For Permit 04110228
Permit Number 04110228
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-12-15 00:00:001) PLEASE INDICATE LOCATION OF FIRE
 COMMAND CENTER ON PLANS.
  
 2) KNOX-BOXES WILL BE REQUIRED.
  
 3) BUILDING IS TO MEET HIGH-RISE
 REQUIREMENTS OF THE APPLICABLE
 BUILDING AND FIRE CODES.
  
 4) A TWO-HOUR FIRE SEPARATION IS
 REQUIRED BETWEEN THE PARKING AND OTHER
 AREAS OF THE BUILDING.
  
 5) S-3 DOOR NEAR LOADING ZONE 2. PLEASE
 EXPLAIN.
  
 6) S-2 DOOR NEAR ALLEY. PLEASE EXPLAIN.
  
 7) TACTILE SIGNAGE REQUIRED AT EXIT
 DOORS.
  
 8) ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST
 BE MARKED SHAFTWAY IN 6" LETTERS.
  
 9) THE FIRE ALARM SYSTEM MUST MEET
 THE REQUIREMENTS FOR CENTRAL STATION
 SERVICE.
  
 10) TWO FIRE DEPARTMENT CONNECTIONS
 ARE REQUIRED FOR THE BUILDING SINCE
 IT IS A HIGH-RISE BUILDING.
  
 11) ALL NEW STAIRS AND RAMPS SHALL
 HAVE HANDRAILS ON BOTH SIDES.
  
 12) LOCKING KNOX-BOX CAPS ARE REQUIRED
 ON THE FIRE DEPARTMENT CONNECTIONS.
  
 13) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR HANDRAILS
 AND GUARDRAILS.
  
 14) PLEASE PROVIDE OCCUPANT LOADS
 FOR POOL DECK AND COMMON PATIO.
  
 15) PLEASE DISPLAY ALL EXISTING OR
 NEW FIRE HYDRANTS ON SITE.
  
 16) PARKING SPACES SURROUND STAIR # 1
 ON PAGE A-3. PLEASE EXPLAIN ACCESS.
  
 17) PARKING SPACES SURROUND STAIR # 3
 ON PAGE A-4. PLEASE EXPLAIN ACCESS.
  
 18) BUILDING LOCATED IN FIRE LIMITS.
 CERTAIN RESTRICTIONS APPLY. PLEASE
 SEE APPENDIX F, LOCAL AMENDMENTS.
  
 19) EXIT SIGN PLACEMENT SHALL NOT
 EXCEED 100 FEET.
  
 20) ENSURE THAT ALL DOOR SWINGS ARE
 INCORRECT.
  
 21) THE DOOR APPEARS TO BE MISSING
 FROM STAIR # 1ON PAGE A-7.
  
 22) PLEASE EXPLAIN EXITING FROM
 MEZZANINE LEVEL.
  
 23) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 24) SIGNS REQUIRED IN STAIRWELLS
 INDICATING TOP, BOTTOM, FLOOR NUMBER,
 ROOF ACCESS, AND THE IDENTITY.
  
 25) WOOD TRELLIS NOTED ON ROOF
 TERRACE. AGAIN LOCATED IN FIRE LIMITS.
  
 26) ARE THE DOORS AT THE MAIN LOBBY
 ROOF TERRACE SWINGING IN THE PROPER
 DIRECTION.
  
 27) IS THE WALKWAY TO THE EXITS ON ROOF
 TERRACE SLIP RESISTANT.
  
 28) BUILDING ADDRESS REQUIRED. A MINIMUM
  
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 29) CANVAS AWNINGS REQUIRED TO BE
 FLAME RETARDANT.
  
 30) PLEASE DISPLAY FIRE SPRINKLER
 LOCATIONS IN TRASH CHUTE SECTION.
  
 31) SMOKE DETECTORS ARE REQUIRED ON
 EVERY LEVEL OF RESIDENTIAL UNITS.
  
 32) PLEASE INDICATE ON PLANS THAT
 ALL SMOKE DETECTORS SHALL BE PLACED
 NO CLOSER THAN THREE FEET FROM
 AIR CONDITIONER DIFFUSERS.
  
 33) PLEASE INDICATE STRETCHER
 ACCESSIBLE
 ELEVATORS IN THE BUILDING.
  
 34) PLEASE VERIFY STANDBY POWER
 REQUIREMENTS.
  
 35) ELEVATOR WARNING SIGNS REQUIRED.
  
 36) LIFE SAFETY ROUTES ON PAGE A-38
 ARE GOING THRU PARKING SPACES. PLEASE
 EXPLAIN RATIONALE.
  
 37) PLEASE PROVIDE WATER COLUMN
 REQUIREMENTS FOR THE STAIRWELL
 PRESSURIZATION SYSTEMS.
  
 38) THERE ARE NOT ENOUGH EXIT SIGNS
 SHOWN.
  
 39) THE CORRIDORS NEED MORE EXIT
 SIGNS.
  
 40) PLEASE INDICATE WHAT THE VOICE
 EVACUATION MESSAGE OF THE FIRE ALARM
 SYSTEM WILL SAY.
  
 41) ELECTRONIC SWITCHES REQUIRED ON
 FIRE LINE BACKFLOW DEVICE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910