Plan Review Notes
Plan Review Notes For Permit 04110228
Permit Number 04110228
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-23 00:00:00*************** UNSAT *****************
  
 PLEASE SEE THE FOLLOWING COMMENTS CAN
 ONLY BE BASED ON PLANS SUBMITTED.
 DUE TO PLANS AND SUBMITTAL PACKAGE NOT
 BEING COMPLETE AT THE TIME OF REVIEW,
 THERE MAY BE ADDITIONAL COMMENTS WHEN
 PLANS ARE RE-SUBMITTED.
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 MISSING REQUIRED INFORMATION ON TITLE
 BLOCK.
 PLEASE ALSO SEE FS 471.023 FOR
 REQUIREMENTS.
 PLEASE ALSO SEE FS 471.025 FOR "RAISED"
 SEAL TO BE CLEAR AND VISABLE WITH ALL
 INFORMATION ON SEAL.
 PLEASE PROVIDE A SIGNED,DATED AND SEALED
 NOTORIZED LETTER FOR VERIFICATION OF
 LEGAL SIGNATURE. PLANS APPEAR TO BE
 SIGNED WITH INITIALS WHICH ARE NOT
 PERMITTED UNDER FS 471.025.
 IF INDEED LEGAL SIGNATURE, PLEASE
 PROVIDE LETTER FOR "SIGNATURE FILE" FOR
 FUTURE REFERENCE.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE:PLEASE SEE 110.26 FOR ALL
 ELECTRICAL ROOMS AND DOOR REQUIREMENTS.
 PLEASE REVISE PLANS TO SHOW OUTWARD
 SWING AND PROVIDE NOTE FOR PANIC
 HARDWARE ETC.
 ** PLEASE SEE ANY EGRESSISSUE THAT MAY
 ARISE WITH DOOR SWING** THIS IS ONLY A
 NOTE:.
  
 3)NOTE: PLEASE SEE THERE ARE NUMEROUS
 LOCATIONS WHERE "COMMON AREA" LIGHTING
 IS BEING CONTROLLED BY A WALL SWITCH.
 THIS WOULD CREATE A SAFTEY ISSUE DUE TO
 LTS IN ARE BEING TURNED OUT WHEN PERSONS
 ARE IN MODE OF EGRESS.
 *TYP* LTS IN COMMON AREAS ARE HARDWIRED
 TO SYSTEMS ELECTRICAL LIKE MANY OF THE
 OTHER COMMONAREAS?
 LS 101 5-8
  
 4)NOTE: PLEASE SEE SOME ELEVATOR LOBBY
 AREAS WHICH PLASN DO NOT CONTAIN ANY
 LIGHTING? ELEV 4 LOBBY)
  
 5)NOTE: PLEASE SEE 620.24ABC FOR MISSING
 REQUIRED LTS/RECEPTS ETC.
  
 6)NOTE: PLEASE SEE RECEPT SPACING IN
 NUMEROUS UNITS. PER 210.52
 PLEASE SEE MANY ARE REDLINED AT
 LOCATIONS REQUIRED ON ONE SET OF PLANS
 SUBMITTED. PER 2',6',12' RULE.
 PLEASE ALSO SEE MEZZ AREAS.
  
 7)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 FOR ALL ELECTRICAL DEVICES SHOWN AND
 CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES. (SD'S ETC.)
  
 8)NOTE: PLEASE SEE CIRCUITING OF SD'S ON
 BATH/KIT LT CIRCUITS WHICH IS OK,
 HOWEVER BATH /KIT LIGHTS WILL THEN
 REQUIRE ARC-FAULT PROTECTION.
 2002 NEC 210.12
  
 9)NOTE: PLEASE SEE SOME CONDENSING UNITS
 SHOWN IN GARAGE ON E-5, PLEASE SHOW ALL
 DISC'S/CIRCUITING PER 440.11
 PLEASE ALSO INCLUDE REQUIRED GFI PER
 210.63
  
 10)NOTE: PLEASE SEE 210.52H FOR "HALL"
 AREA RECEPT SPACING. SOME UNITS UNITS ON
 TYPICAL FLRS.
  
 11)NOTE: PLEASE SEE 700.16 FOR ALL
 ELECTRICAL/ELEVATOR/FIRE COMMAND RMS
 ETC
 FOR LIGHTING REQUIREMENTS.
  
 12)NOTE: PLEASE PROVIDE ROOM
 DESIGNATIONS ON PLANS.
  
 13)NOTE: PLEASE SEE LOCATIONS OF SD'S
 ARE TO BE INSTALLED PER NFPA-72
 8-1.4.1.6.2 AND 8-1.4.2
 3' OF BATH RM DOORS ETC. PLEASE REVISE
 NOTE ON E-19 WHICH MENTIONS SD'S OK TO
 INSTALL W/IN 20' OF COOKING APPLIANCE.
 THIS IS ONLY PERMITTED WITH EXCEPTIONS
 LISTED.
  
 14)NOTE: PLEASE SEE SOME MISSING GFI
 RECEPTS REQUIRED IN SOME UNITS PER
 210.52C1, GFI PER 210.8A6
  
 15)NOTE: PLEASE SEE CIRCUITING FOR
 DINING ROOM/AREA RECEPTS. PLEASE
 DESIGNATE AREA/RM. PLEASE SEE 210.52B1
  
 16)NOTE: PLEASE SEE UPPER ROOF LEVELS.
 PLEASE COMPLETE ELECTRICAL PLANS AS SOME
 OF THESE AREAS ON PLANS DO NOT INDICATE
 ANY ELECTRICAL.; LTS, RECEPTS ETC.
 RECEPTS REQUIRED W/IN 20' OF POOL.
 680.22A1
  
 17)NOTE: PLEASE SEE ALL COND UNITS ON
 UPPER ROOF LEVEL. PLEASE INDICATE ALL
 REQUIRED DISCONNECTS PER 440.11 AND
 GFI'S PER 210.63,210.8
  
 18)NOTE:PLEASE SEE MISSING EGRESS
 LIGHTING FOR STAIRS ON ROOF PLANS.
 LS101 5-8. PLEASE SEE POSSIBLE COMMENTS
 FROM FIRE/BLDG REVIEW FOR THIS.
  
 19)NOTE: PLEASE CORRELATE METER CENTER
 MAINS ON RISER/ PLANS / ELEVATION
 RISER.
 PLANS INDICATE 700A MAINS, HOWEVER OTHER
 AREAS INDICATE 1000A?
 215.5
  
 20)NOTE: PLEASE 240.4C FOR SIZING OF ALL
 CONDUCTORS FOR DEVICES RATED OVER
 800A'S
 PLEASE ALSO SEE 310.16,110.14 FOR RATING
 OF CONDUCTORS AND TEMP LIMITATIONS.
  
 21)NOTE: PLEASE CORRELATE # OF
 CONDUCTORSIN THE # OF SETS AND # OF
 CONDUITS ON E-17
  
 22)NOTE: PLEASE SEE "SWITCH GEAR RM",
 PLEASE SHOW LAYOUT OF ROOM WITH LOCATION
 OF ALL ELECTRICAL EQUIPMENT AND MAINS.
  
 23)NOTE: PLEASE CORRELATE RISER DIAGR
 AND PLANS WITH ELECTRICAL EQUIPMENT AND
 WHICH LEVEL EQUIPMENT IS ON.
  
 24)NOTE: PLEASE SEE MAIN FOR EM POWER
 DISTRIBUTION IS REQUIRED TO BE GROUPED
 CLOSER THAN SHOWN ON PLANS. TRAVEL
 DISTANCE AND PLANS INDICATING THESE
 MAINS AND SHUT-DOWNS ON DIFFERENST
 LEVELS AND XX FEET APART WILL NOT BE
 APPROVED BY FIRE MARSHAL'S OFFICE OR
 ELECTRICAL PLAN REVIEW.
 PLEASE SEE 230.72,230.70,230.76,230.79
 PLEASE BE AWARE "SHUNT-TRIPS" ARE NOT AN
 ACCEPTABLE METHOD FOR COMPLIANCE.
  
 25)NOTE: PLEASE SEE E-6, PLEASE IDENTIFY
 WHAT APPEARS TO BE TWO PIECES OF EM
 ELECTRICAL EQUIPMENT.
 215.5
  
 26)NOTE:PLEASE SEE PANEL SCHEDULES WERE
 SUBMITTED FOR MAINS 1,2,3 ON E-17, BUT
 NONE FOR MAINS 4,5 ? PLEASE SHOW
 215.5
  
 27)NOTE:PLEASE SEE RISER DIAGRAM: PLEASE
 SEE OCP/LOCKED ROTOR FOR FIRE PUMP IS
 SHOWN TO BE A MIN OF 1085A'S, YET FUSES
 ARE INDICATED AS 1000A'S?? PLEASE SEE
 695.4B1
  
 28)NOTE: PLEASE SEE RISER DIAGRAM
 INDICATES FIRE PUMP FEED COMING FROM FPL
 AND METER RM? PLEASE VERIFY WHICH ONE?
 AND WHERE FEED IS COMING FROM.
 PLEASE SUBMIT COMPLETE SPECS ON FIRE
 PUMP AND FIRE PUMP CONTROLLER.
 PLEASE BE SURE THIS IS ALL A LISTED
 UNIT.
 PLEASE BE SURE IT CONTAINS A MAN MEANS
 OF DISC AND RATED FOR LOAD SERVED AND
 MEETS 110.27, 230.76,230.79
 PLEASE ALSO SEE VOLTAGES FOR LOCK ROTOR
 IN TABLE.430.151
  
 29)NOTE: PLEASE SUBMIT COMPLETE SPECS
 FOR GENERATOR AND TRANSFER SWITCH.
 PLEASE CORRELATE PLANS WITH SUBMITTALS.
 215.5
  
 30)NOTE: PLEASE CORRELATE RISER, RISER
 EQUIPMENT SCHEDULE AND GENERATOR NOTES
 FOR TRANSFER SWITCH SIZE AND VOLTAGE.
 ONE SHOWS 1200A, THE OTHER 3500A ETC.
  
 31)NOTE: PLEASE CORRELATE RISER WITH
 GENERATOR NOTES FOR GENERATOR, SHOWS TWO
 DIFFERENT SIZES ETC.875KVA , 1200 KVA
 ETC
 PLEASE SEE PLANS ARE CALLING FOR TWO
 DIFFERENT VOLTAGES FOR SAME EQUIPMNET?
 215.5
  
 32)NOTE: PLEASE SEE ELECTRICAL RISER
 DIAGRAM EQUIPMENT SCHEDULE NOTES: ONLY
 SHOWS NOTES 1-5 YET PLANS/RISER DIAGRAM
 SHOWS MANY MORE AREAS LABELED TO SEE
 NOTES ON EQUIPMENT SCHEDULE. #'S 8,9,18
 ETC ETC.
  
 33)NOTE: PLEASE LABEL EDP ON RISER WITH
 EQUIPMENT SCHEDULE NOTES.;
 215.5
  
 34)NOTE: PLEASE SEE ELEVATOR DISC/
 EQUIPMENT ON RISER WHICH IS SHOWN ON THE
 ROOF AND COMING DIRECTLY FROM TANSFORMER
 VAULT??? MAINS? GROUPING ? OVERCURRENT-
 PROTECTION ETC.
 230.72,230.70,230.76,.230.79,215.5
  
 35)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS ON RISER AND OTHER
 AREAS WHICH ARE REQUIRED PER
 250.110,250.24, SIZED PER 250.122
  
 36)NOTE: PLEASE SEE 2002 NEC FOR
 GROUNDING ELECTRODE SYSTEM. 250.50,
 250.66.
  
 37)NOTE: PLEASE SEE THERE ARE NUMEROUS
 LOCATIONS ON PLANS WHICH GIVE REFERENCE
 TO CODES FROM 1996/1999 NEC.
 PLEASE SEE WE ARE UNDER THE 2002 NEC.
 JUST A NOTE: 2002 NEC WAS ADOPTED BY THE
 STATE 7/1/2003
 PLEASE ADJUST ALL LOCATION ON PLANS.
  
 38)NOTE: PLEASE SEE PLANS REFERENCE THE
 SOUTH FLORIDA BLDG CODE.
 PLEASE SEE WE ARE UNDER 2001 FBC WITH
 REVISIONS.
  
 39)NOTE: PLEASE SEE LOCAL AMENDMENST FOR
 COLOR CODING 215.5 FOR 277/480V SYSTEMS
 ETC.
  
 40)NOTE: PLEASE SEE PLANS HAVE BEEN
 REDLINED WITH MOST OF THE ABOVE ITEMS
 AND AREAS OF COMMENTS.
  
 41)NOTE: PLEASE SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 42)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 43)NOTE: PLEASE SEE BLDG REVIEW
 COMMENTS: THIS IS A THRESHOLD BLDG AND
 THREE SETS OF PLANS ARE REQUIRED.
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2004-11-18 00:00:00IN ELECTRICAL FOR REVIEW.
 NOTES TO FOLLOW.