| Date |
Text |
| 2004-11-23 00:00:00 | *************** UNSAT ***************** |
| | |
| | PLEASE SEE THE FOLLOWING COMMENTS CAN |
| | ONLY BE BASED ON PLANS SUBMITTED. |
| | DUE TO PLANS AND SUBMITTAL PACKAGE NOT |
| | BEING COMPLETE AT THE TIME OF REVIEW, |
| | THERE MAY BE ADDITIONAL COMMENTS WHEN |
| | PLANS ARE RE-SUBMITTED. |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR |
| | MISSING REQUIRED INFORMATION ON TITLE |
| | BLOCK. |
| | PLEASE ALSO SEE FS 471.023 FOR |
| | REQUIREMENTS. |
| | PLEASE ALSO SEE FS 471.025 FOR "RAISED" |
| | SEAL TO BE CLEAR AND VISABLE WITH ALL |
| | INFORMATION ON SEAL. |
| | PLEASE PROVIDE A SIGNED,DATED AND SEALED |
| | NOTORIZED LETTER FOR VERIFICATION OF |
| | LEGAL SIGNATURE. PLANS APPEAR TO BE |
| | SIGNED WITH INITIALS WHICH ARE NOT |
| | PERMITTED UNDER FS 471.025. |
| | IF INDEED LEGAL SIGNATURE, PLEASE |
| | PROVIDE LETTER FOR "SIGNATURE FILE" FOR |
| | FUTURE REFERENCE. |
| | THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| | ALL TRADES WHEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE:PLEASE SEE 110.26 FOR ALL |
| | ELECTRICAL ROOMS AND DOOR REQUIREMENTS. |
| | PLEASE REVISE PLANS TO SHOW OUTWARD |
| | SWING AND PROVIDE NOTE FOR PANIC |
| | HARDWARE ETC. |
| | ** PLEASE SEE ANY EGRESSISSUE THAT MAY |
| | ARISE WITH DOOR SWING** THIS IS ONLY A |
| | NOTE:. |
| | |
| | 3)NOTE: PLEASE SEE THERE ARE NUMEROUS |
| | LOCATIONS WHERE "COMMON AREA" LIGHTING |
| | IS BEING CONTROLLED BY A WALL SWITCH. |
| | THIS WOULD CREATE A SAFTEY ISSUE DUE TO |
| | LTS IN ARE BEING TURNED OUT WHEN PERSONS |
| | ARE IN MODE OF EGRESS. |
| | *TYP* LTS IN COMMON AREAS ARE HARDWIRED |
| | TO SYSTEMS ELECTRICAL LIKE MANY OF THE |
| | OTHER COMMONAREAS? |
| | LS 101 5-8 |
| | |
| | 4)NOTE: PLEASE SEE SOME ELEVATOR LOBBY |
| | AREAS WHICH PLASN DO NOT CONTAIN ANY |
| | LIGHTING? ELEV 4 LOBBY) |
| | |
| | 5)NOTE: PLEASE SEE 620.24ABC FOR MISSING |
| | REQUIRED LTS/RECEPTS ETC. |
| | |
| | 6)NOTE: PLEASE SEE RECEPT SPACING IN |
| | NUMEROUS UNITS. PER 210.52 |
| | PLEASE SEE MANY ARE REDLINED AT |
| | LOCATIONS REQUIRED ON ONE SET OF PLANS |
| | SUBMITTED. PER 2',6',12' RULE. |
| | PLEASE ALSO SEE MEZZ AREAS. |
| | |
| | 7)NOTE: PLEASE SHOW CIRCUITING ON PLANS |
| | FOR ALL ELECTRICAL DEVICES SHOWN AND |
| | CORRELATE WITH THE SUBMITTED PANEL |
| | SCHEDULES. (SD'S ETC.) |
| | |
| | 8)NOTE: PLEASE SEE CIRCUITING OF SD'S ON |
| | BATH/KIT LT CIRCUITS WHICH IS OK, |
| | HOWEVER BATH /KIT LIGHTS WILL THEN |
| | REQUIRE ARC-FAULT PROTECTION. |
| | 2002 NEC 210.12 |
| | |
| | 9)NOTE: PLEASE SEE SOME CONDENSING UNITS |
| | SHOWN IN GARAGE ON E-5, PLEASE SHOW ALL |
| | DISC'S/CIRCUITING PER 440.11 |
| | PLEASE ALSO INCLUDE REQUIRED GFI PER |
| | 210.63 |
| | |
| | 10)NOTE: PLEASE SEE 210.52H FOR "HALL" |
| | AREA RECEPT SPACING. SOME UNITS UNITS ON |
| | TYPICAL FLRS. |
| | |
| | 11)NOTE: PLEASE SEE 700.16 FOR ALL |
| | ELECTRICAL/ELEVATOR/FIRE COMMAND RMS |
| | ETC |
| | FOR LIGHTING REQUIREMENTS. |
| | |
| | 12)NOTE: PLEASE PROVIDE ROOM |
| | DESIGNATIONS ON PLANS. |
| | |
| | 13)NOTE: PLEASE SEE LOCATIONS OF SD'S |
| | ARE TO BE INSTALLED PER NFPA-72 |
| | 8-1.4.1.6.2 AND 8-1.4.2 |
| | 3' OF BATH RM DOORS ETC. PLEASE REVISE |
| | NOTE ON E-19 WHICH MENTIONS SD'S OK TO |
| | INSTALL W/IN 20' OF COOKING APPLIANCE. |
| | THIS IS ONLY PERMITTED WITH EXCEPTIONS |
| | LISTED. |
| | |
| | 14)NOTE: PLEASE SEE SOME MISSING GFI |
| | RECEPTS REQUIRED IN SOME UNITS PER |
| | 210.52C1, GFI PER 210.8A6 |
| | |
| | 15)NOTE: PLEASE SEE CIRCUITING FOR |
| | DINING ROOM/AREA RECEPTS. PLEASE |
| | DESIGNATE AREA/RM. PLEASE SEE 210.52B1 |
| | |
| | 16)NOTE: PLEASE SEE UPPER ROOF LEVELS. |
| | PLEASE COMPLETE ELECTRICAL PLANS AS SOME |
| | OF THESE AREAS ON PLANS DO NOT INDICATE |
| | ANY ELECTRICAL.; LTS, RECEPTS ETC. |
| | RECEPTS REQUIRED W/IN 20' OF POOL. |
| | 680.22A1 |
| | |
| | 17)NOTE: PLEASE SEE ALL COND UNITS ON |
| | UPPER ROOF LEVEL. PLEASE INDICATE ALL |
| | REQUIRED DISCONNECTS PER 440.11 AND |
| | GFI'S PER 210.63,210.8 |
| | |
| | 18)NOTE:PLEASE SEE MISSING EGRESS |
| | LIGHTING FOR STAIRS ON ROOF PLANS. |
| | LS101 5-8. PLEASE SEE POSSIBLE COMMENTS |
| | FROM FIRE/BLDG REVIEW FOR THIS. |
| | |
| | 19)NOTE: PLEASE CORRELATE METER CENTER |
| | MAINS ON RISER/ PLANS / ELEVATION |
| | RISER. |
| | PLANS INDICATE 700A MAINS, HOWEVER OTHER |
| | AREAS INDICATE 1000A? |
| | 215.5 |
| | |
| | 20)NOTE: PLEASE 240.4C FOR SIZING OF ALL |
| | CONDUCTORS FOR DEVICES RATED OVER |
| | 800A'S |
| | PLEASE ALSO SEE 310.16,110.14 FOR RATING |
| | OF CONDUCTORS AND TEMP LIMITATIONS. |
| | |
| | 21)NOTE: PLEASE CORRELATE # OF |
| | CONDUCTORSIN THE # OF SETS AND # OF |
| | CONDUITS ON E-17 |
| | |
| | 22)NOTE: PLEASE SEE "SWITCH GEAR RM", |
| | PLEASE SHOW LAYOUT OF ROOM WITH LOCATION |
| | OF ALL ELECTRICAL EQUIPMENT AND MAINS. |
| | |
| | 23)NOTE: PLEASE CORRELATE RISER DIAGR |
| | AND PLANS WITH ELECTRICAL EQUIPMENT AND |
| | WHICH LEVEL EQUIPMENT IS ON. |
| | |
| | 24)NOTE: PLEASE SEE MAIN FOR EM POWER |
| | DISTRIBUTION IS REQUIRED TO BE GROUPED |
| | CLOSER THAN SHOWN ON PLANS. TRAVEL |
| | DISTANCE AND PLANS INDICATING THESE |
| | MAINS AND SHUT-DOWNS ON DIFFERENST |
| | LEVELS AND XX FEET APART WILL NOT BE |
| | APPROVED BY FIRE MARSHAL'S OFFICE OR |
| | ELECTRICAL PLAN REVIEW. |
| | PLEASE SEE 230.72,230.70,230.76,230.79 |
| | PLEASE BE AWARE "SHUNT-TRIPS" ARE NOT AN |
| | ACCEPTABLE METHOD FOR COMPLIANCE. |
| | |
| | 25)NOTE: PLEASE SEE E-6, PLEASE IDENTIFY |
| | WHAT APPEARS TO BE TWO PIECES OF EM |
| | ELECTRICAL EQUIPMENT. |
| | 215.5 |
| | |
| | 26)NOTE:PLEASE SEE PANEL SCHEDULES WERE |
| | SUBMITTED FOR MAINS 1,2,3 ON E-17, BUT |
| | NONE FOR MAINS 4,5 ? PLEASE SHOW |
| | 215.5 |
| | |
| | 27)NOTE:PLEASE SEE RISER DIAGRAM: PLEASE |
| | SEE OCP/LOCKED ROTOR FOR FIRE PUMP IS |
| | SHOWN TO BE A MIN OF 1085A'S, YET FUSES |
| | ARE INDICATED AS 1000A'S?? PLEASE SEE |
| | 695.4B1 |
| | |
| | 28)NOTE: PLEASE SEE RISER DIAGRAM |
| | INDICATES FIRE PUMP FEED COMING FROM FPL |
| | AND METER RM? PLEASE VERIFY WHICH ONE? |
| | AND WHERE FEED IS COMING FROM. |
| | PLEASE SUBMIT COMPLETE SPECS ON FIRE |
| | PUMP AND FIRE PUMP CONTROLLER. |
| | PLEASE BE SURE THIS IS ALL A LISTED |
| | UNIT. |
| | PLEASE BE SURE IT CONTAINS A MAN MEANS |
| | OF DISC AND RATED FOR LOAD SERVED AND |
| | MEETS 110.27, 230.76,230.79 |
| | PLEASE ALSO SEE VOLTAGES FOR LOCK ROTOR |
| | IN TABLE.430.151 |
| | |
| | 29)NOTE: PLEASE SUBMIT COMPLETE SPECS |
| | FOR GENERATOR AND TRANSFER SWITCH. |
| | PLEASE CORRELATE PLANS WITH SUBMITTALS. |
| | 215.5 |
| | |
| | 30)NOTE: PLEASE CORRELATE RISER, RISER |
| | EQUIPMENT SCHEDULE AND GENERATOR NOTES |
| | FOR TRANSFER SWITCH SIZE AND VOLTAGE. |
| | ONE SHOWS 1200A, THE OTHER 3500A ETC. |
| | |
| | 31)NOTE: PLEASE CORRELATE RISER WITH |
| | GENERATOR NOTES FOR GENERATOR, SHOWS TWO |
| | DIFFERENT SIZES ETC.875KVA , 1200 KVA |
| | ETC |
| | PLEASE SEE PLANS ARE CALLING FOR TWO |
| | DIFFERENT VOLTAGES FOR SAME EQUIPMNET? |
| | 215.5 |
| | |
| | 32)NOTE: PLEASE SEE ELECTRICAL RISER |
| | DIAGRAM EQUIPMENT SCHEDULE NOTES: ONLY |
| | SHOWS NOTES 1-5 YET PLANS/RISER DIAGRAM |
| | SHOWS MANY MORE AREAS LABELED TO SEE |
| | NOTES ON EQUIPMENT SCHEDULE. #'S 8,9,18 |
| | ETC ETC. |
| | |
| | 33)NOTE: PLEASE LABEL EDP ON RISER WITH |
| | EQUIPMENT SCHEDULE NOTES.; |
| | 215.5 |
| | |
| | 34)NOTE: PLEASE SEE ELEVATOR DISC/ |
| | EQUIPMENT ON RISER WHICH IS SHOWN ON THE |
| | ROOF AND COMING DIRECTLY FROM TANSFORMER |
| | VAULT??? MAINS? GROUPING ? OVERCURRENT- |
| | PROTECTION ETC. |
| | 230.72,230.70,230.76,.230.79,215.5 |
| | |
| | 35)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS ON RISER AND OTHER |
| | AREAS WHICH ARE REQUIRED PER |
| | 250.110,250.24, SIZED PER 250.122 |
| | |
| | 36)NOTE: PLEASE SEE 2002 NEC FOR |
| | GROUNDING ELECTRODE SYSTEM. 250.50, |
| | 250.66. |
| | |
| | 37)NOTE: PLEASE SEE THERE ARE NUMEROUS |
| | LOCATIONS ON PLANS WHICH GIVE REFERENCE |
| | TO CODES FROM 1996/1999 NEC. |
| | PLEASE SEE WE ARE UNDER THE 2002 NEC. |
| | JUST A NOTE: 2002 NEC WAS ADOPTED BY THE |
| | STATE 7/1/2003 |
| | PLEASE ADJUST ALL LOCATION ON PLANS. |
| | |
| | 38)NOTE: PLEASE SEE PLANS REFERENCE THE |
| | SOUTH FLORIDA BLDG CODE. |
| | PLEASE SEE WE ARE UNDER 2001 FBC WITH |
| | REVISIONS. |
| | |
| | 39)NOTE: PLEASE SEE LOCAL AMENDMENST FOR |
| | COLOR CODING 215.5 FOR 277/480V SYSTEMS |
| | ETC. |
| | |
| | 40)NOTE: PLEASE SEE PLANS HAVE BEEN |
| | REDLINED WITH MOST OF THE ABOVE ITEMS |
| | AND AREAS OF COMMENTS. |
| | |
| | 41)NOTE: PLEASE SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER REVIEWER(S) WHICH |
| | MAY HAVE AN AFFECT ON ELECTRICAL PLANS. |
| | |
| | 42)NOTE: PLEASE REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | 43)NOTE: PLEASE SEE BLDG REVIEW |
| | COMMENTS: THIS IS A THRESHOLD BLDG AND |
| | THREE SETS OF PLANS ARE REQUIRED. |
| | |
| | |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| 2004-11-18 00:00:00 | IN ELECTRICAL FOR REVIEW. |
| | NOTES TO FOLLOW. |