| 2004-12-02 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04110228 |
| | ADD: TO BE DECIDED |
| | "THE PLACE VIA CLEMATIS" |
| | CONT:PLAN REVIEW |
| | CONTACT: BLUE MOON DEV |
| | TEL: (786)554-0900 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT |
| | NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES |
| | BETWEEN THE LOTS WHICH COMBINE TO FORM |
| | 'THE SITE'.A 'UNITY OF TITLE' SHALL |
| | BE |
| | RECORDED AT THE COUNTY COURTHOUSE. |
| | SUBMIT A COPY OF THE RECORDED 'UNITY OF |
| | OF TITLE' DOCUMENT SO THAT FBC TABLE |
| | 600 |
| | BOUNDARY LINE REQUIREMENTS MAY BE |
| | DEEMED |
| | NOT APPLICABLE. |
| | |
| | 3)FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL |
| | IS NOT DEFINITLY KNOWN OR IS IN |
| | QUESTION |
| | THE BUILDING OFFICIAL MAY REQUIRE |
| | EXPLOR |
| | ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| | TO THE PERMISSIBLE SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL |
| | PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA.SUPPLY (3) REPORTS. |
| | |
| | 4) FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY |
| | OCCUPAN |
| | CY CLASSIFICATION AS DEINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | SRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL |
| | INSPEC |
| | TION PLAN PREPARED BY THE ENGINEER OF |
| | RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING |
| | AGEN- |
| | CY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A |
| | THRESH- |
| | OLD BUILDING. THE PURPOSE OF THE |
| | SRUCTUR |
| | AL INSPECTION PLAN IS TO PROVIDE |
| | SPECIF- |
| | IC INSPECTION PROCEDURES AND SCHEDULES |
| | SO THAT THE BUILDING CAN BE ADEQUATELY |
| | INSPECTED FOR COMPLIANCE WITH THE |
| | PERMITTED DOCUMENTS. |
| | |
| | 5) WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 6) W.P.B. AMENDMENT 105.13.4.4 ALL |
| | PLANS |
| | FOR THE BUILDING WHICH ARE REQUIRED TO |
| | BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR |
| | ENGINEER OF RECORD CON- TAIN A |
| | STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR |
| | ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS |
| | DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 7) FBC* F102.2.7ARCHITECTURAL TRIM, |
| | ON |
| | BUILDINGS LOCATED IN THE FIRE DISTRICT, |
| | SHALL BE CONSTRUCTED OF APPROVED |
| | NON-COMBUSTIBLE MATERIALS OR FIRE |
| | RETARDANT TREATED WOOD.ANNOTATE THE |
| | PLANS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 8) FBC* F102.2.8PERMANENT CANOPIES/ |
| | AWNINGS AND THEIR SUPPORTS, ON |
| | BUILDINGS |
| | LOCATED IN THE FIRE DISTRICT, SHALL BE |
| | OF NON-COMBUSTIBLE MATERIAL, FIRE |
| | RETARDANT TREATED WOOD, WOOD OF TYPE |
| | III |
| | SIZES OR OF 1-HOUR RESISTANT |
| | CONSTRUCTION.ANNOTATE THE PLANS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 9) FBC* F102.2.4ROOF COVERINGS, ON |
| | BUILDINGS LOCATED IN THE FIRE DISTRICT, |
| | SHALL CONFORM TO THE REQUIREMENTS OF |
| | CLASS A OR B ROOF COVERINGS, AS DEFINED |
| | IN FBC 1505.ANNOTATE THE PLANS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 10) THE PLANS DO NOT PROVIDE |
| | INFORMATION FOR WORK TO BE COMPLETED IN |
| | THE PUBLIC PROPERTY. SEE CHAPTER 33, |
| | WHERE COVERED WALKWAYS WILL BE REQUIRED |
| | 3304, CONSTRUCTION OF WALKWAYS, FENCES |
| | AND PROTECTIVE COVERINGS. |
| | |
| | 11) PROVIDE INFORMATION ON THE SHEET |
| | PILING, EXCAVATION ,DENSAFICATION OF |
| | SOILS AND IF SOIL NAILS ARE GOING TO |
| | BEREQUIRED AND DEWATERING. DEPENDING ON |
| | THE SEQUENCE OF EVENTS THERE IS |
| | POSSIBILITIES OF THE SHEET PILE GIVING |
| | WAY BECAUSE OF SOILS VIBRAFLOTATION. |
| | |
| | 12) PROPERTY LINES- ON THE NORTH SIDE |
| | OF THE BUILDING SHEET A.5/A.6 INDICATE |
| | FRONT ENTRY DOORS SWINGING PAST THE |
| | PROPERTY LINE. 3203.1 DOORS SHALL NOT |
| | OPEN OR PROJECT UPON PUBLIC PROPERTY. |
| | |
| | 13) SOUTH SIDE OF THE BUILDING SHEET |
| | A.5/A.6 CURB IS PAST THE PROPERTY LINE. |
| | |
| | 14) BOTH SETS OF PLANS ARE MISSING THE |
| | A-19 SHEET WHICH DEPICTS THE SOUTH |
| | ELEVATION OF THE BUILDING. CONCERNS |
| | THAT TABLE 600 ISSUES EXIST SINCE THE |
| | BUILDING IS ON THE PROPERTY LINE AND |
| | THE ALLEY IS ONLY 14' WIDE. SINCE THE |
| | STRUCTURE IS DIRECTLY ON THE PROPERTY |
| | LINE TABLE 600 ISSUES OCCUR. |
| | 14A) THE WALL SECTION THAT IS 6'-0" |
| | AWAY |
| | FROM THE PROPERTY LINECAN HAVE 20% |
| | OPENINGS & REQUIRES A 3 HR WALL.!/2 OF |
| | ALLEY OR 7'+6'= 13' OR 20% ALLOWABLE |
| | OPENINGS, PER FLOOR!SEE 705.1.1.2 FOR |
| | OPENINGS LESS THAN 15' FROM THE |
| | PROPERTY LINE. |
| | 14B) THE WALL SECTIONS THAT ARE RIGHT |
| | ON THE PROPERTY LINE(0'-3') HAVE NO |
| | ALLOWABLE OPENINGS AND REQUIRE A 4 HR |
| | WALL. |
| | 14C) PROVIDE THE EQUIVALENT THICKNESS |
| | REQUIRED FOR BEARING AND NONBEARING |
| | CONCRETE BLOCK. SEE 709.3.1. DO NOT |
| | PROVIDE A UL RATING BUT THE ACTUAL |
| | EQUIVALENT THICKNESS FROM THE BLOCK |
| | MANUFACTURE FOR2HR, 3 HR & 4HR WALLS. |
| | |
| | 15) SHEET A-27 MEZANINES, THE AREA OF |
| | THE MEZZANINES IS OVER THE 1/3 OF THE |
| | ROOM IN WHICH IT IS LOCATED. SEE |
| | 503.2.3.2. ENCLOSED SPACE UNDER A |
| | MEZZANINE SHALL NOT BE INCLUDED IN A |
| | DETERMINATION OF THE SIZE OF THE ROOM |
| | OR SPACE IN WHICH THE MEZANINE IS |
| | LOCATED. RECALCULATE AREAS. |
| | |
| | 16)A.5 WALL LEGEND INDICATES VARIOUS |
| | BLOCK OR SOLID CONCRETE WALL AND THEIR |
| | RESPECTIVE HR. RATING. PROVIDE THE |
| | EQUIVALENT THICKNESS AS DESCRIBED IN |
| | TABLE 709.3.1. NOTE ALSO NO 3HR WALLS |
| | PROVIDED 0'-3' REQUIRES A 3HR RATED |
| | WALL. THE BLOCK INFORMATION SHOULD COME |
| | FROM THE BLOCK MANUFACTURER NOT A |
| | UL LISTING. |
| | |
| | 17) A.5/A.6 SEE STAIRWAYS, 1007.1.5 |
| | ENCLOSED EXIT STAIRWAYS THAT CONTINUE |
| | BEYOND THE FLOOR OF DISCHARGE SHALL BE |
| | INTERRUPTED AT THE FLOOR OF DISCHARGE |
| | BY PARTITIONS, DOORS OR OTHER EFFECTIVE |
| | MEANS. |
| | |
| | 18) SEE DOOR SCHEDULE A.35 IS MISSING |
| | PROTECTION OF OPENINGS IN INTERIOR |
| | WALLS,( 705.1.2) SEE TABLE 705.1.2 FOR |
| | THE REQUIRED RATINGS. |
| | |
| | 19) TRASH ROOM SEE A.6/A.35 MISSING THE |
| | |
| | DOOR RATING FOR THE TRASH TERMINATION |
| | ROOM. SEE 705.2.4.4. |
| | |
| | 20) THE VARIOUS FLOORS (2-8) INCLUDE |
| | THE |
| | |
| | PHRASE TRASH ROOM (EXAMPLEROOM 103 ON |
| | A.10). THISDETAIL DOESN'T PROVIDE AN |
| | ACCURATE DETAIL WITH THE WORD ROOM, AT |
| | BEST IT IS A VESTIBULE, THE CODE DOES |
| | REQUIRE A ACCESS ROOM. THE SWING DOOR |
| | THAT IS NOT NUMBERED OR LABELED WILL |
| | MEET THE INTENT OF THE CODE IF THE |
| | 3/4 HR RATING IS MET SEE 705.2.4.2. |
| | |
| | 21)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | THERE IS A SPACE BETWEEN THE TRASH |
| | ROOM, |
| | STAIRWELL# 3, THAT IS NOT LABELED, WHAT |
| | WILL THIS AREA BE USED FOR? IF IT IS A |
| | CHASE PROVIDE A 2 HR RATED ASSEMBLY.SEE |
| | A.10, A.12, A.14 & A.16. |
| | |
| | 22) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | THERE IS ALSO 2 AREAS ON EACH SIDE OF |
| | STAIRWELL# 2 THAT IS NOT CLEAR WHAT |
| | THIS |
| | AREA MAY BE USED FOR, IT IS DIRECTLY |
| | FOUND ON A.9, A.11 & A.13. |
| | |
| | 23) INDICATE COMPLIANCE WITH 3003.4.1 |
| | LEVATOR STRETCHER REQUIREMENTS. |
| | |
| | 24) 1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR |
| | PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | 1) GLAZED OPENINGS LOCATED WITHIN 30 |
| | FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST.SEE COPY OF CITY OF |
| | W.P.B. INTERPRETATION OF HURRICANE |
| | STANDARDS FOR LARGE PROJECTS. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS- FIXED OR OPERATABLE |
| | B) PANELWALL-STOREFRONT |
| | C) GLAZED EXTERIOR DOORS |
| | D) SOLID EXTERIOR DOORS |
| | E) MULLIONS |
| | F) VENTS |
| | G) STRUCTURAL COMPONENTS- TRUSS |
| | ANCHORS |
| | CONCRETE ADMIXTURES, RAILINGS |
| | H) ROOFING PRODUCTS- AND INSULATION. |
| | THE ABOVE IS MENTIONED AS TO |
| | REQUIREMENTS TO OBTAIN A BUILDING |
| | PERMIT. THE NOTES FOUND ON A.35 NOTE |
| | FOR |
| | WINDOWS AND STOREFRONT ARE TO BE UNDER |
| | A |
| | SEPERATE PERMIT. AT WHAT TIME WILL |
| | THESE ITEMS BE ADDRESSED? SHOULD THE |
| | BUILDING BE CLASSIFIED AS OPEN OR |
| | PARTIALLY OPEN SINCE NO TIME FACTOR IS |
| | MENTIONED TO WHEN THEY WILL BE |
| | INSTALLED? |
| | |
| | 25) THE OTHER ISSUE THAT NEEDS TO BE |
| | CLARIFIED, THERE CAN ONLY BE ONE |
| | CLASSIFICATION FOR A BUILDING OR |
| | STRUCTURE EITHER OPEN, PARTIALLY |
| | ENCLOSED OR ENCLOSED. . SEE ASCE 7-98 |
| | 6.5.9.4. SHEET S-4.1 WIND DESIGN |
| | INDICATES THAT YOU ARE DESIGNING TO A |
| | HIGH VELOCITY ZONE "C", AND EXPOSURE |
| | OF 146 MPH. S5.2 INDICATESE PARTIALLY |
| | ENCLOSED BUT COEFICIENTS FOUND ON S4.1 |
| | INDICATEA CLOSED BUILDING 0.18+-, |
| | PLEASE INDICATE FINAL ANALYSIS? |
| | |
| | 26) A-37 DETAILS 6 & 7, SOFFITS, DROP |
| | CEILINGS, OR TRAY CEILINGS ALL INDICATE |
| | THE SAME PHRASE," TO BE PROPERLY |
| | ANCHORED TOTHEUNDERSIDE OF STRUCTURE" |
| | BUT THE DESIGN TEAM LACKS INDICATING HOW |
| | TO ACHIEVE THIS TASK? |
| | 104.2.1 W.P.B. ADMINISTRATIVE CODE |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR |
| | OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. |
| | SUCH INFORMATION SHALL BE SPECIFIC AND |
| | THE TECHNICAL CODES "SHALL NOT BE CITED |
| | AS A WHOLE OR IN PART, NOR THE TERM |
| | "LEGAL" OR ITS RQUIVALENT BE USED AS A |
| | SUBSTITUTE FOR SPECIFIC INFORMATION". |
| | |
| | 27) TYPE II CONSTRUCTION 604 REQUIRES |
| | STRUCTURAL MEMBERS TO BE NON |
| | COMBUSTIBLE. |
| | A.15 WOOD TRELLIS EIGHTHFLOOR TO BE |
| | NONCOMBUSTIBLE, F102.2.7 FIRE DISTRICT |
| | A.20 THE POOL HOUSE, STAIR AND |
| | ELEVATION |
| | SHEETS INDICATE WOOD RAFTERS. |
| | A.24 WALL SECTIONS A&D INDICATE THE USE |
| | OF 5/8" CDX PLYWOOD FOR ROOF SHEATHING. |
| | ALSO 2X6 WOOD FACIA OVER 1X8????? |
| | |
| | 28) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | FOR THE POOL HOUSE AND ASSOCIATED |
| | STRUCTURES ATOP THE BUILDING, NO |
| | INFORMATION WAS SUBMITTED TO BE ABLE TO |
| | DO A THROUGH PLAN REVIEW!!!!!!!! |
| | S-1.6A/S-1.6B POOL DECK PLANS DO NOT |
| | INDICATE STRUCTURAL DETAILS FOR THE POOL |
| | STRUCTURE, SPA NOR THE COLUMN FRAMING |
| | FOR THE BREEZEWAYS. |
| | |
| | 29) A.15 THERE HAS BEEN NO INFORMATION |
| | SUBMITTED FOR AN ELEVATOR LOBBY FOR |
| | NONE |
| | OF THE ELEVATORS ON THE ROOF TERRACE |
| | LEVEL.SEE 412.6. |
| | |
| | 30) THE FIRE SPRINKLER PLANS DO NOT |
| | INDICATE THE USE OF FIRE SPRINKLERS FOR |
| | THE STRUCTURES ON THE ROOF TERRACE |
| | LEVEL. SEE ATTACHMENT NFPA 13 8.14.7 |
| | EXTERIOR ROOFS OR CANOPIES, INDICATE |
| | HOW |
| | TO ACHIEVE CODE COMPLIANCE. |
| | |
| | 31) ASSUMPTION: FIRE SPRINKLERS FOR THE |
| | |
| | POOL ROOF TERRACE LEVEL NOR THE POOL |
| | DECK LEVEL, ISIT ASSUMED THAT AREA OF |
| | RESCUE WILL BE PROVIDED UNDER SECTION |
| | 11-4.3.11? |
| | |
| | 32) A-24 INDICATES THE USE OF CAST |
| | STONE |
| | WITH A THICKNESS OF 1"-6". SHOW |
| | COMPLIANCE WITH 1403.2.7. |
| | |
| | 33) STAIRWELLS INDICATE HOW PLANS ARE TO |
| | COMPLY WITH 11-4..4.2 HEADROOM. |
| | |
| | 34) A-23 DROP OFF ZONE 11-4.6.5 |
| | PASSENGER LOADING ZONE PROVIDE THE |
| | VEHICLE ACCESS ROUTE WITHREQUIRED HEAD |
| | ROOM FROM THE ENTRY TO LOADING ZONE BACK |
| | TO THE EXIT. |
| | |
| | 35) A-5 ACCESSIBLE PATH, ACCESS AISLE IS |
| | THERE A CURB @ COLUMN LINE 7/F1AND |
| | DROP OFF POINT? |
| | |
| | 36) POOL STRUCTURE: POOL TO BE UNDER A |
| | SEPERATE PERMIT, THE STURTURAL WALLS |
| | WILL BE BUILT WITH THE BUILDING, THIS |
| | AGAIN IS AN ASSUMPTION. TO COMPLY WITH |
| | 424. PUBLIC POOLS : |
| | A) DOES THE POOL OFFER SUNKEN SEATING |
| | OR IS THIS STAIRS? SEE 424.1.2.5.3 FOR |
| | STAIRS, 424.1.2.5.4. |
| | |
| | 37) A-34 THE DOORS LEADING INTO THE POOL |
| | AREA DOOR 12 & 16 SHALL COMPLY WITH SELF |
| | CLOSING AND SELF LATCHING REQUIREMENTS, |
| | SEE 424.1 DOH 64E-9.002(6) EFFECTIVE |
| | BARRIER. |
| | |
| | 38) A-36 DETAIL # 23 EXTERIOR |
| | GUARDRAIL; |
| | 1015.2 HEIGHT. GUARDRAILS SHALL FORM |
| | A VERTICAL PROTECTIVE BARRIER NOT LESS |
| | THAN 42" HIGH. |
| | 1015.3 OPENINGS. OPEN GUARDRAILS |
| | SHALL HAVE INTERMEDIATE RAILS OR ORNA- |
| | MENTAL PATTERNS SUCH AS A 4" DIAMETER |
| | SPHERE CAN NOT PASS THROUGH. A BOTTOM |
| | RAIL OR CURB SHALL BE PROVIDED THAT WILL |
| | REJECT THE PASSAGE OF 2" DIAMETER |
| | SPHERE. |
| | |
| | 39) A-36 EXTERIOR GUARDRAILS TO COMPLY: |
| | 1608.2.3 THE GUARDRAIL SYSTEM SHALL BE |
| | DESIGNED AND CONSTRUCTED TO RESIST A 200 |
| | LB CONCENTRATED HORIZONTAL LOAD APPLIED |
| | ON A 1 SQ FT AREA AT ANY POINT IN THE |
| | SYSTEM INCLUDING INTERMEDIATE RAILS OR |
| | OTHER ELEMENTS SERVING THIS PURPOSE. |
| | |
| | 40) A-5 RAMP DOWN TO 9'-4" NOTE |
| | INDICATESA 12" WIDE CONCRETE CURB SEE |
| | |
| | DETAILS 6/A-46? NO SUCH PLAN?STOPS AT |
| | 40 |
| | |
| | 41) 411.4.2 6 AIR CHANGES PER HR/ |
| | LEVEL. |
| | M-3 INDICATES A 15,000 CFM FAN |
| | EXHAUSTING , CENTERED IN A 50"-0" |
| | OPENING. PLANS DO NOT INDICATE ANY MAKE |
| | UP AIR, THIS EXHAUST WILL BE PULLED |
| | RIGHT BACK INTO THE GARAGE, EXPLAIN |
| | RATIONAL? |
| | |
| | 42) SHOW COMPLIANCE WITH 412.5 SMOKE |
| | CONTROL, M-16 SMOKE ZONE CONTROLS/ ZONE |
| | II, PLANS INDICATE THE USE OF |
| | PRESSURIZATION, THIS STILL DOESN'T |
| | REMOVE SMOKE, SEE 412.5. |
| | |
| | 43) M-6 EMERGENCY GENERATOR INDICATES A |
| | 6" EXHAUST PIPE W/ 1 1/2" CALCIUM |
| | SILICATE WRAP THROUGH THE 2HR RATED |
| | FLOOR SLAB. 705.6.1 PROVIDE THE |
| | ASSEMBLY |
| | APPROVED FOR THIS APPLICATION. |
| | PENETRATIONS OF HORIZONTAL ASSEMBLIES. |
| | |
| | 44) A-7 AUTO RAMP TO THE MEZZANINE FLOOR |
| | PLAN INDICATES OPENSIDED RAMP, PROVIDE |
| | INFORMATION FOR COMPLIANCE WITH |
| | 1608.2.3. PARKING GAURDRAILS, IMPACT |
| | GAURDRAILS, AND BOLLARDS. BOLLARDS |
| | INDICATE A SECTION )/A-000.????? |
| | |
| | 45) A-8 PROVIDE FLOOR SLOPES AT THE |
| | HANDICAPED PARKING AT THE EAST END OF |
| | THE BLDG. DRAINAGE GRATE IN THE MIDDLE |
| | OF THE HANDICAPPED SPACE? |
| | |
| | 46) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | A-9/A-10 NO INFORMATION IS PROVIDED FOR |
| | WALLS AND GATES OF PRIVATE LANAI? |
| | |
| | 47)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | PLANS ARE NOT COMPLETE AND THE ANSWERS |
| | TO THE QUESTIONS MAY RESULT IN |
| | ADDITIONAL COMMENTS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |