Plan Review Notes
Plan Review Notes For Permit 04110227
Permit Number 04110227
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-11-12 00:00:001) IS THE EXISTING OFFICE SPACE THE
 SAME OR A DIFFERENT TENANT SPACE.
  
 2) PLEASE EXPLAIN SECURITY GATE. WHEN
 IS IT DOWN, WHEN IS IT UP. WHEN
 DOWN CAN IT BE OPENED QUICKLY IN THE
 EVENT OF AN EMEREGNCY.
  
 3) PLEASE EXPLAIN CLASS C FLAMESPREAD
 IN A NON SPRINKLER OCCUPANCY. USUALLY
 EXITS SHALL BE CLASS A OR B IN EXITS,
 AND EXIT ACCESS AREAS. PLEASE EXPLAIN.
  
 4) THERE APPEARS TO BE AN EXISTING DOOR
 WHEN OPENED BLOCKS THE EXITWAY.
  
 5) PLEASE EXPLAIN NIGHT LOBBY.
  
 6) WHAT FIRE RATING IS PRESENT FOR
 THE EXISTING LOBBY (ELEVATOR AND STAIR
 NOT SHOWN )
  
 7) WHAT RATING IS PRESENT FOR THE
 STORAGE AREA LOCATED UNDERNEATH
 THE STAIRS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910