| Plan Review Notes For Permit 04110227 |
| Permit Number |
04110227 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-12 00:00:00 | 1) IS THE EXISTING OFFICE SPACE THE | | | SAME OR A DIFFERENT TENANT SPACE. | | | | | | 2) PLEASE EXPLAIN SECURITY GATE. WHEN | | | IS IT DOWN, WHEN IS IT UP. WHEN | | | DOWN CAN IT BE OPENED QUICKLY IN THE | | | EVENT OF AN EMEREGNCY. | | | | | | 3) PLEASE EXPLAIN CLASS C FLAMESPREAD | | | IN A NON SPRINKLER OCCUPANCY. USUALLY | | | EXITS SHALL BE CLASS A OR B IN EXITS, | | | AND EXIT ACCESS AREAS. PLEASE EXPLAIN. | | | | | | 4) THERE APPEARS TO BE AN EXISTING DOOR | | | WHEN OPENED BLOCKS THE EXITWAY. | | | | | | 5) PLEASE EXPLAIN NIGHT LOBBY. | | | | | | 6) WHAT FIRE RATING IS PRESENT FOR | | | THE EXISTING LOBBY (ELEVATOR AND STAIR | | | NOT SHOWN ) | | | | | | 7) WHAT RATING IS PRESENT FOR THE | | | STORAGE AREA LOCATED UNDERNEATH | | | THE STAIRS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|