Notes
Date Text
2004-11-15 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 AND POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICALPLANS.
  
 2)NOTE: PLEASE SEE MISSING SIGN CIRCUIT
 REQUIRED PER 600.5
  
 3)NOTE: PLEASE HAVE RAISED SEAL FROM
 ARCH BE CLEAR AND VISABLE WITH ALL
 INFORMATION REQUIRED ON SEAL.
 FS 481.221
 PLEASE ALSO SEE FIRST NAME FOR ARCH
 APPEARS TO BE INITIALS. FS AND FAC
 REQUIRES LEGAL SIGNATURE. IF WHAT IS
 SHOWN IS LEGAL SIGNATURE, PLEASE PROVIDE
 AND SIGNED AND SEALED NOTORIZED LETTER
 FOR LEGAL SIGNATURE. THIS LETTER WILL BE
 PLACED IN OUR SIGNATURE FILE FOR ANY
 FUTURE REFERENCE.
 THIS VERIFICATION IS NEEDED DUE TO
 PROBLEMS WITH FORGERIES ON PREVIOUS
 PROJECTS.
 FAC 61G1-16.004, FS 481.221
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  