| 2004-12-03 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04110227 |
| | ADD: 325 CLEMATIS ST |
| | CONT: FRANCON INC |
| | TEL: (954)444-1189 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT |
| | NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 1) PLANS INDICATE A 2HR TENANT |
| | SEPERATION WALL WITH A NOTE THROUGH |
| | PENETRATIONS 1 HR. SEE 705.1.2 AND |
| | TABLE |
| | 705.1.2. FOR RATING. |
| | |
| | 2) EXISTING LOBBY, INDICATE LOCATION OF |
| | ELEVATOR AND STAIRS & RATING. PROVIDE |
| | THE RATING OF STORAGE BELOW STAIRS. |
| | |
| | 3) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO |
| | THE |
| | AUTHORITY HAVING JURISDICTION. SUCH |
| | IDEN |
| | TIFICATION SHALL BE ABOVE ANY |
| | DECORATIVE |
| | CEILING CEILING AND IN CONCEALED |
| | SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 4) CORRECT GENERAL NOTE# 2 SEE FLAME |
| | SPREAD & SMOKE DEVELOPMENT FOR |
| | MERCANTILE UNSPRINKLERED , EXITS AND |
| | EXIT ACCESS TABLE 803.3 |
| | |
| | 5) THE REAR EXITING OF THE UNIT AND EXIT |
| | ACCESS CORRIDOR DO NOT MEET : |
| | 1012.1.4. DURING ITS SWING, ANY DOOR IN |
| | A MEANS OF EGRESS SHALL LEAVE |
| | UNOBSTRUCTED AT LEAST 1/2 OF THE REQUIRE |
| | REQUIRED WIDTH OF AN AISLE, CORRIDOR, |
| | PASSAGEWAY, OR LANDING, NOR PROJECT MORE |
| | THAN 7" INTO THE REQUIRED WIDTH. |
| | THE DOORS LEADING FROM UPS AND THE DOORS |
| | OFTHE LANDLORD DO NOT MEET THIS CODE |
| | REQUIREMENT. SEE CODE REQUIREMENT FOR |
| | 180 DEGREE HINGES. |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |