2004-11-18 00:00:00BUILDING PLAN REVIEW PROVISO:
  
 OWNER MUST APPLY FOR STORM PANEL PERMIT
 & HAVE THEM INSTALLED BEFORE THE FINAL
 INSPECTION ON THE WINDOWS.
2004-11-05 00:00:00BUILDING PLAN REVIEW FAILED:
  
 1. SUBMIT A DRAWING SHOWING LOCATION OF
 WINDOWS TO BE REPLACED.DRAWING MUST
 SHOW BEDROOM LOCATIONS & SIZES OF
 WINDOWS TO MEET MEANS OF EGRESS CODE.
  
 2. FLORIDA BUILDING CODE REQUIRES STORM
 PANEL PROTECTION OF WINDOWS BEING
 REPLACED WHEN MORE THAN 25% OF THE
 OPENINGS ARE BEING REPLACED.SUBMIT
 STORM PANEL PROTECTION .
  
  
 3.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 WWW.FLORIDABUILDING.ORG
  
 NEED FLORIDA PRODUCT APPROVALS FOR THE
 WINDOWS AND STORM PANELS.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713