| Notes |
| Date |
Text |
| 2006-06-16 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1. SHT P210 REV. 2 UNIT D6 NOT CLOUDED | | | AT SAN/3. PLEASE CLOUD CHANGES | | | | | | 2. SHT P210 REV. 3 UNIT E6 NO CHANGE | | | NOTED. PLEASE CLARIFY. SECTION 104.2.1. | | | | | | 3. SHT P210 REV. 3 UNIT F6 TUB NOT | | | VENTED AT SAN/10. SECTION 901.2.1. | | | | | | 4. SHT P301 REV. 3 SAN/10 TUB NOT | | | VENTED. SECTION 901.2.1. | | | | | | 5. SHT P301 RISER DIAGRAM SAN/1 CHANGED | | | ON FLOOR PLAN UNIT F6 & K6 BUT NOT | | | CHANGED ON RISER DIAGRAM. SAN/1 DID NOT | | | CHANGE FOR UNIT D6, SO PLEASE INDICATE | | | HOW REVISION FOR SAN/1 WILL BE DONE WITH | | | TWO DIFFERENT FLOOR PLANS. SECTION | | | 104.2.1. | | | | | | 6. SHTS P206, P208, & P211 SHALL BE | | | SUBMITTED UNDER THE CORRECT PERMIT FOR | | | THOSE SHEETS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|