| Plan Review Notes For Permit 04110185 |
| Permit Number |
04110185 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-06-23 00:00:00 | REVISION DENIED | | | | | | 1. SHTS P205 & P209 MORE INFORMATION IS | | | REQUIRED FOR REVISION. ARE DOWNSPOUTS | | | BEING DELETED? IF SO A REVISION WILL BE | | | REQUIRED SHOWING THE DOWNSPOUTS BEING | | | DELETED ON THE ARCHITECTURAL SHEETS. | | | SECTION 104.2.1. | | | 2. SHTS P205 & P209 REVISIONS 2 & 3 WERE | | | NOT FOUND. LAST REVISION ON THE STAMPED | | | ISSUED SET OF PLANS WAS REVISION 1. | | | PLEASE CLOUD AND NUMBER ALL REVISIONS. | | | SECTION 104.2.1. | | | 3. SHT P207 INDICATE SQUARE FOOTAGE OF | | | EACH DOWNSPOUT AND COMBINED SF FOR | | | HORIZONTAL SITE STORM LINE WHERE THE 2 | | | DOWNSPOUTS ARE NOW CONNECTING TOGETHER. | | | ALSO SHOW PIPE SIZE FOR THE HORIZONTAL | | | SIET STORM LINE. TABLE 1106.3 (THIS IS | | | THE RISER DIAGRAM FOR SHT P209) | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|