| 2005-12-09 00:00:00 | ****** UNSAT ******* |
| | |
| | 1)NOTE: PLEASE SEE NOTE ON ALL PLANS |
| | INDICATE SD'S ARE TO BE WIRED TO |
| | HALL/FOYER CIRCUITS, HOWEVER CIRCUITING |
| | ON PLANS WAS NOT CHANGED. |
| | PLEASE BE SURE THAT IF THESE SD'S ARE |
| | NOW GOING TO CHANGE TO HALL/FOYER LTS, |
| | THEN THESE CIRCUITS WILL ALSO NOW BE |
| | REQUIRED TO BE ARC FAULT.210.12 |
| | PLEASE ALSO SEE CIRCUITING FOR SD'S HAS |
| | GONE BACK TO THE SD'S OF THE SAME UNIT |
| | BEING WIRED TO MORE THAN ONE CIRCUIT. |
| | SMOKE DETECTORS ARE REQUIRED TO BE WIRED |
| | INLINE AND THIS WILL NOT WORK ON MORE |
| | THAN ONE CIRCUIT. |
| | PLEASE ADJUST ALL CIRCUITING. |
| | |
| | 2)NOTE: PLEASE SEE FIRE PUMP |
| | FEEDERS/SEC'S FROM THE FPL TRANSFORMER |
| | TO THE METER AND FROM THE METER TO THE |
| | FIRST MEANS OF DISCONNECT IS NOTED AS |
| | HAVING AN EQUIPMENT GROUNDING CONDUCTOR. |
| | PLEASE REVISE SCHEDULE. |
| | THESE ARE ONLY INSTALLED AFTER THE FIRST |
| | MEANS OF DISCONNECT. |
| | |
| | 3)NOTE: PLEASE SEE 302 WHICH DOES NOT |
| | INDICATE ANY REVISONS, HOWEVER TITLE |
| | BLOCK DOES INDICATE THIS. |
| | |
| | 4)NOTE: PLEASE SEE 620.23 A SEPARATE |
| | BRANCH CIRCUIT SHALL SUPPLY THE MACHINE |
| | ROOM OR CONTROL ROOM/MACHINERY SPACE OR |
| | CONTROL SPACE LIGHTING AND |
| | RECEPTACLE(S). |
| | |
| | PLEASE MAKE THE ABOVE CORRECTIONS AND |
| | SUBMIT FOR REVIEW. IF THERE ARE ANY |
| | QUESTIONS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |