| 2005-12-23 00:00:00 | REVISION DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1. SHTS P201, P205, P206, P207, P208, |
| | 209, & 210 SHALL BE SUBMITTED FOR |
| | REVISION UNDER THE APPROPRIATE PERMIT |
| | NUMBER FOR THOSE SHEETS. SECTION |
| | 104.2.1. |
| | 2. SHTS P205 & 209 REVISION REQUIRED FOR |
| | THE ARCHITECTURAL SHEETS SHOWING THE |
| | DELETION OF THE SCUPPERS. SEE COMMENT #1 |
| | FROM LAST REVISION SUBMITTAL (6-23-5). |
| | 3. SHT P210 LEVEL 2-4. LEVEL 2 IS |
| | DIFFERENT THAN LEVELS 3 & 4. REVISE |
| | SEPARATELY. INDICATE UNIT DESIGNATION ON |
| | EACH SHEET. SECTION 104.2.1. |
| | - E6 OPP. REVISION REQUIRED FOR THE |
| | FLOOR PLAN. ONLY E6 FLOOR PLAN HAS BEEN |
| | REVISIED. IF FLOOR PLAN NOT REVISED, |
| | SUBMIT A RISER DIAGRAM TO REFLECT |
| | UNCHANGED FLOOR PLAN. SECTION 104.3.1.1. |
| | - G6 TUB NOT VENTED. WHAT RISER HAS BEEN |
| | REVISED TO REFLECT THIS CHANGE? |
| | - H6 INDICATE RISER NUMBER TO REFLECT |
| | CHANGE. |
| | - K6 2ND FLOOR INDICATE RISERS FOR |
| | THESE CHANGES. |
| | - F6 3RD & 4TH FLOORS |
| | 4. SHT P301 WHERE IS WATER HEATER DRAIN |
| | PAN - WASTE WATER DETAIL? HAVE THE WATER |
| | HEATERS BEEN DELETED? DETAIL TO BE SHOWN |
| | ON REVISION. |
| | - WHERE IS RISERS SAN/6 & SAN/9? THESE |
| | ARE STILL SHOWN ON THE FLOOR PLANS. |
| | - SAN/7 DOES NOT REFLECT THE FLOOR |
| | PLAN. |
| | - UNIT B-2 MASTER BATH SANT FITTINGS |
| | SHALL BE INSTALLED TO GUIDE SEWAGE AND |
| | WASTE IN THE DIRECTION OF FLOW. SECTION |
| | 706.3. |
| | - UNIT E-5/6 MASTER BATH, SHOW ALL PIPE |
| | SIZES. MAX 4FU ON 2" WET VENT. SECTION |
| | 104.2.1 AND TABLE 909.3. |
| | |