| Plan Review Notes For Permit 04110183 |
| Permit Number |
04110183 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-04-25 00:00:00 | **REDLINED ** | | | | | | 1) NO EQUIPMENT GROUNDING CONDUCTORS | | | FROM TRANSFORMER TO METER OR METER TO | | | FIRST MEANS OF DISCONNECT. | | | 250.6,250.24 | | | EQUIPMENT GROUNDING CONDUCTORS SHOWN TO | | | FIRE PUMP SHALL NOT BE INSTALLED. | | | | | | ALL 12 ROLLS STAMPED FOR ELECTRICAL. | | | NO REVISION NEEDED. |
|