| 2005-02-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | A) FROM PREVIOUS REVIEW: | | | 1) A TITLE BLOCK MUST CONTAIN THE | | | FOLLOWING INFORMATION. | | | 61G1-16.004(2)(6) | | | THE FIRM LICENSE NUMBER, AND THE | | | PRINTED | | | NAME OF THE PERSON SEALING THE | | | DOCUMENT. | | | ALSO THE CERTIFICATE OF AUTHORIZATION | | | OF | | | THE FIRM. SEE SHEETS L1 THRU L6 AND | | | SHEETS I-1 THRU I-3. | | | **************NEW COMMENT************* | | | 1B) SHT P202 BUILDING 1 STORM RISER | | | DIAGRAM. MAXIMUM 730 SF @ 1% SLOPE. 4" | | | PIPE REQUIRED ON THE HORIZONTAL PIPING | | | OR INDICATE 4% SLOPE. INDICATE ON | | | PLANS. | | | TABLE 1106.3. | | | 2B) SHT P202 SCUPPERS THRU THE MANSARD | | | ROOF REQUIRES A MINIMUM OF 21.195 SQ IN | | | 6" PIPE IS REQUIRED. TABLE 1106.3 AND | | | SECTION 1107.3. | | | 3B) SHT P204 MINIMUM 4" PIPE REQUIRED | | | ON | | | STORM RISER HORIZONTAL PIPING. TABLE | | | 1106.3. | | | 4B) SHT P204 MINIMUM 6" PIPE REQUIRED | | | ON | | | THE SCUPPER DRAINS. SECTION 1107.3 | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|