| 2005-02-14 00:00:00 | *** NOTES *** |
| | THIS IS FOR BLDGS: 1,2,5 AND 6. |
| | THIS COMMENT DOES NOT AFFECT BLDGS: 3 OR |
| | 4. |
| | |
| | 1)NOTE:PLEASE SEE NFPA-20 IN REFERENCE |
| | TO FIRE PUMP ELECTRICAL SERVICE |
| | LOCATION. |
| | PLEASE SEE SERVICE SHALL BE LOCATED AS |
| | NOT TO BE AFFECTED IN CASE OF FIRE / |
| | EXPLOSION ETC WITH MAIN ELECTRICAL |
| | SERVICE. |
| | THIS FIRE PUMP SERVICE SHOULD STILL BE |
| | LOCATED IN CLOSE PROXIMITY TO MAIN |
| | ELECTRICAL RM. |
| | PLEASE SEE NFPA-20, 6.2.1 |
| | 6-2.1 SERVICE. |
| | WHERE POWER IS SUPPLIED BY A SERVICE, IT |
| | SHALL BE LOCATED AND ARRANGED TO |
| | MINIMIZE THE POSSIBILITY OF DAMAGE BY |
| | FIRE FROM WITHIN THE PREMISES AND |
| | EXPOSING HAZARDS. |
| | NFPA-70 695 |
| | THE CONNECTION SHALL BE LOCATED AND |
| | ARRANGED SO AS TO MINIMIZE THE |
| | POSSIBILITY OF DAMAGE BY FIRE FROM |
| | WITHIN THE PREMISES AND FROM EXPOSING |
| | HAZARDS. |
| | MOST IMPORTANT IN 695.3(A)(2) IS THE |
| | REQUIREMENT THAT A FIRE IN ONE SOURCE |
| | NOT AFFECT THE RELIABILITY OF ANOTHER |
| | SOURCE. |
| | |
| | THIS WAS NOT IN ORIGINAL REVIEW NOTES. |
| | |
| | PLEASE MAKE THE ABOVE CHANGES AND SUBMIT |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CONTACTING. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |