| 2006-05-17 00:00:00 | ******** UNSAT ********* |
| | |
| | |
| | 1) NOTE: PLEASE SEE COMMENTS FROM |
| | PREVIOUS REVIEW AS THE SD'S ARE STILL |
| | SHOWN BEING WIRED TO MORE THAN ONE |
| | CIRCUIT IN A SINGLE UNIT?? |
| | PLEASE KNOW, THE SD'S ARE REQUIRED TO |
| | WIRED "INLINE", WHICH AS SHOWN ON |
| | MULTIPLE CIRCUITS IS NOT PERMITTED. |
| | THESE MAY BE WIRED TO THE ARC FAULT |
| | PROTECTED BEDRM CIRCUIT, HOWEVEER THESE |
| | CAN ONLY BE ON ONE CIRCUIT. |
| | NFPA-72 8-1.4.1.6.2, |
| | |
| | 2) NOTE: PLEASE SEE SEC'S HAVE NOW BEEN |
| | DOWN SIZED TO 3/0'S FOR ONE FIRE PUMP |
| | SERVICE, AND 4/0'S FOR THE OTHER. |
| | PLEASE SEE THAT THE SEC'S SHALL ME SIZED |
| | ACCORDINGLY TO THE OCP, HP, AND THE SIZE |
| | OF THE FPC. |
| | PLEASE SEE 310.16, AS 3/0'S ARE ONLY |
| | RATED AT 200A'S AND THE 4/0'S ARE ONLY |
| | RATED FOR 225A'S. PLEASE SEE |
| | 240.4,310.16. |
| | THE OCP SHOWN ON MAIN IS 250A'S. |
| | (LOOCKED ROTOR SHOULD BE SET AND PART OF |
| | THE FPC AND MUST BE 6X THE FLA'S. |
| | 695.4/695.5 |
| | |
| | ** NOTE ** |
| | PLEASE KNOW, IT HAS COME TO THE |
| | ATTENTION OF THIS OFFICE THAT SOME OF |
| | THE SLIDING GLASS DOORS ON PLANS ARE |
| | ACTUALLY "FIXED GLASS PANELS" PLEASE SEE |
| | 210.52 AS "FIXED GLASS" IS CONSIDERED |
| | WALL SPACE. |
| | PLEASE SEE PLANS IN MANY PLACES STILL |
| | INDICATE MANY OF THESE AS SLIDING GLASS |
| | DOORS?? AS REVIEWED ON PREVIOUS PLANS. |
| | ANY INSTALLATION OF FIXED GLASS PANELS, |
| | WILL BE VERIFIED IN THE FIELD AND PLANS |
| | SHALL BE REVISED ACCORDING TO ACTUAL |
| | WALL SPACE CONSTRUCTED. |
| | |
| | |
| | PLEASE REVISE AND SUBMIT THE ABOVE |
| | INFORMATION FOR REVIEW. IF THERE ARE ANY |
| | QUESTIONS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |