| Plan Review Notes For Permit 04110182 |
| Permit Number |
04110182 |
|
| Review Stop |
P |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2006-06-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1. SHT P206 VENT REQUIRED AT URINAL. | | | SECTION 901.2.1. | | | | | | 2. SHT P208 TUB NOT VENTED AS PIPED. | | | VENT REQUIRED FOR TUB. SECTION 901.2.1. | | | | | | 3. SHTS P210 & P211 SHALL BE SUBMITTED | | | UNDER THE CORRECT PERMIT NUMBER. SECTION | | | 104.2.1. | | | | | | 4. SHT P310 SAN/10 RISER, TUB NOT | | | VENTED. SECTION 901.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|