2005-12-02 00:00:00DENIED:
 1.MECHANICAL PLANS SUBMITTED FOR
 REVISION INDICATE THE UNITS ARE BEING
 REDUCED BY A 1/2 TO 1 TON OF AIR.
 CONDENSER UNITS ARE ALSO REDUCED (UNITS
 214, 224, & 234) ARE THE AHU'S ALSO
 BEING REDUCED?UNIT NUMBERS FOR THE AHU
 DO NOT MATCH THE CONDENSING UNIT
 NUMBERS.THE CONDO UNITS ARE MARKED A1,
 C3, ETC.PLEASE CORRELATE.
  
 2.PLEASE NOTE ENERGY & MANUAL J
 CALCULATIONS SUBMITTED ARE THE MINIMUM.
 THE REVISED A/C PLANS DO NOT CORRELATE
 WITH THE ENERGY CALCULATIONS. A/C
 SYSTEMS SHALL NOT BE LESS THAN WHAT IS
 DICTATED BY THE ENERGY & MANUAL J CALCS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.