| 2005-02-17 00:00:00 | DENIED: | | | 1.AS PER CONVERSATION WITH JIM MULLEN, | | | DRYER SUBMITTAL TO BE CHANGED AND THE | | | PLANS WILL BE REVISED DELETING THE | | | BOOSTER FANS INSTALLED IN THE DRYER | | | EXHAUST DUCT.SPECIFIC DRYERS ARE TO BE | | | INSTALLED BY FINAL INSPECTION. | | | | | | 2.PLAN SHEET M203 THE TRASH CHUTE ROOM | | | DOES NOT INDICATE A C0 SENSOR AS | | | REQUIRED PER PREVIOUS REVIEW. | | | | | | 3.PLEASE NOTE IN THE RESIDENTIAL UNITS | | | AS WELL AS COMMON AREAS, SYSTEMS THAT | | | HAVE THE DESIGN CAPAPCITY TO PRODUCE | | | GREATER THAN 2,000 CFM, DUCT SMOKE | | | DETECTORS WILL BE REQUIRED IN THE SUPPLY | | | AIR DUCT.AS AN ALTERNATE TO THE DUCT | | | SMOKE DETECTORS, THE UPON ACTIVATION OF | | | A SMOKE DETECTOR, THE A/C UNIT WILL SHUT | | | DOWN. 2001 FBC(M)606.2.1, 606.2.2 AND | | | 606.4. | | | | | | 4.FAN SHUTDOWN SHALL HAVE NOTIFICATION | | | PER 2001 FBC(M)606.4.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|