2004-12-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) A TITLE BLOCK MUST CONTAIN THE
 FOLLOWING INFORMATION. 61G1-16.004(2)
 FIRM LICENSE NUMBER. FS 481.219
 2) SEE BLDG REVIEW FOR INFORMATION ABOUT
 SEPARATE PERMITS FOR EACH BUILDING AND
 C.O.'S - 6 BLDGS - 4 PERMITS.
 3) SHTS A104, A108, 120, P202, & P204
 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 AND 1107 AND ALL SUBSECTIONS. SHOW THE
 SF FOR ALL ROOFS, 1/2 AREA OF ALL
 VERTICAL WALLS, INCLUDING PARAPETS AND
 ALL AREAS OF ROOFS THAT DRAIN ONTO THE
 ROOF AREA FROM ABOVE.
 4) SHT A106 UNITS A1A & A1B MASTER BATH
 TOILET ROOMS A1A.14 & A1B.14. THE
 MANEUVERING SPACE WITHIN THE BATHROOM TO
 PERMIT A PERSON TO ENTER THE ROOM, CLOSE
 THE DOOR AND REOPEN THE DOOR AND EXIT IS
 REQUIRED. SEE PAGE 7.33 FHA DESIGN
 MANUAL, USABLE BATHROOM(4). IT APPEARS
 THE DOOR WILL BE BLOCKED WHEN THE
 WHEELCHAIR ENTERS. PLEASE CLARIFY.
 5) SHT A110 MASTER BATH BOTH UNITS,
 TOILET ROOMS B2.14 & A2.15 SEE NOTE #4.
 THE SAME ISSUE OCCURS WITH THE DOOR.
 6) SHTS P201, P206 & P207 ALL TRASH
 CHUTES SHALL HAVE BACKFLOW PROTECTION ON
 THE WATER LINES THAT SPRAY THE CHUTES.
 SECTION 608.13.6
 7) SHT A701 DETAIL #10 W/C SHALL BE M OF
 18" OFF THE WALL TO THE CENTERLINE OF
 THE FIXTURE. SEE PAGE 6.5 FIRST
 PARAGRAPH.
 8) SHT P704 DETAIL #3 MINIMUM OPENING
 FOR THE W/C SHALL BE 33" SEE PAGE 7.43
 9) SUBMIT MANUF. SPECIFICATION SHEETS
 FOR THE DOMESTIC PUMPS AND THE INSTANT
 WATER HEATER. SECTION 303.4
 10) SHT P201 BUILDING 1 PLUMBING PLAN
 GARAGE LEVEL SAYS "3/4 IN. COLD WATER TO
 EXT. HOSE BIBB", BUT NO COLD WATER LINE
 IS SHOWN. PLEASE CLARIFY. SECTION
 104.2.1.
 11) SHT P205 BLDG. 3 PLUMBING PLAN
 GARAGE LEVEL.:
 INDICATES RWL IN 2 LOCATIONS, BUT RWL
 RISER AND PIPING ARE NOT SHOWN.
 LEVEL 2 & 4 RWL'S ARE NOT SHOWN.
 COLD WATER LINE FROM DOMESTIC PUMP
 SHOWS 1-1/2" CW, THEN CHANGES TO 2"
 DOWNSTREAM. - PLEASE CLARIFY SECTION
 104.2.1.
 12) SHT P301 SANT. RISER #2 STANDPIPES
 ARE REQUIRED AT W/M. SECTION 1002.1 -
 SANT. RISER #5 S-1 SINK NOT VENTED AND
 PIPED AS SUCH CREATES AN "S" TRAP
 SECTION 1002.3(5). PLEASE INDICATE WHAT
 A S-1 SINK IS AS IT IS NOT SHOWN ON THE
 FIXTURE SCHEDULE. SECTION 104.2.1. -
 SANT. RISER DIAGRAM #6 S-X & S-1 SINKS
 ARE NOT VENTED AND PIPED AS SUCH CREATE
 AN "S" TRAP. SECTION 1002.3(5). PLEASE
 INDICATE WHAT A S-X AND A S-1 SINK ARE
 AS THEY ARE NOT SHOWN ON THE FIXTURE
 SECHEDULE. SECTION 104.2.1. - SANT.
 RISER #8 BT-1 NOT VENTED. SECTION
 901.2.1. - SANT. RISER #1 DOES NOT
 REFLECT THE FLOOR PLAN. NOT ALL THE
 PIPING FOR SANT. RISER #1 IS THE SAME ON
 EACH FLOOR PLAN. EACH RISER SHALL
 REFLECT THE FLOOR PLAN PIPING. SECTION
 104.2.1.
 13) SUBMIT A STORM RISER DIAGRAM FOR ALL
 RISERS AND BUILDING STORM DRAINS. SHOW
 ALL PIPE SIZES AND SQUARE FOOTAGE AS IN
 ACCUMULATES IN THE SYSTEMS. SECTION
 104.3.1.1.
 14) SUBMIT A CONDENSATE RISER AND BLDG
 CONDENSATE DRAIN ISOMETRIC SHOWING ALL
 PIPE SIZES AND CONNECTION POINT FOR EACH
 RISER. SECTION 104.3.1.1.
 15) SUBMIT A WATER DISTRIBUTION
 ISOMETRIC SHOWING ALL PIPE SIZES, POINTS
 ON CONNECTION FOR EACH RISER, VALVES,
 WATER HAMMER ARRESTORS ECT. FOR EACH
 BUILDING. SECTION 104.3.1.1,
 16) RPZ BACKFLOW REQUIRED FOR WATER
 SERVICE TO POOL.
 17) SEPARATE PERMIT REQUIRED FOR THE
 POOL.
 18) SUBMIT ISOMETRIC RISER DIAGRAM FOR
 THE WATER HEATER P&T VALVE DISCHARGE
 LINES AND EMERGENCY PAN DRAIN LINES.
 SHOW ALL PIPE SIZES AND THE TERMINATION
 POINT FOR EACH SYSTEM. SECTION
 104.3.1.1.
 19) SHT 401 DETAIL #8 WATER SHOWS A
 FLOOR DRAIN NOT SHOWN ON THE RISER
 DIAGRAM. PLEASE CLARIFY. SECTION
 104.2.1
 20) FLOOR DRAINS ARE NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. SECTIONS 802.3
 AND 802.3.2.
  
  
  
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]