Plan Review Notes
Plan Review Notes For Permit 04110182
Permit Number 04110182
Review Stop M
Sequence Number 1
Notes
Date Text
2004-12-02 00:00:00DENIED:
 1.PLANS INDICATE SOME ROOMS OFF THE
 ENCLOSED GARAGE ARE USING THE AIR IN
 THE GARAGE FOR MAKE-UP OR OUTSIDE AIR.
 PER 2001 FBC(M)401.5, FRESH AIR/MAKE-UP
 AIR SHALL NOT BE LOCATED 10 FT FROM
 NOXIOUS CONTAMINANTS SUCH AS PARKING
 LOTS OR LOADING DOCKS.
  
 2.A MINIMUM OF 4" CLEARANCE REQUIRED
 AROUND THE AHU IN ACCORDANCE WITH 2001
 FBC(M)603.1.3.
  
 3.PLEASE PROVIDE A SCHEMATIC
 INDICATING ELECTRICAL WIRING SHOWING
 HOW THE BOOSTER FAN FAILURE WILL
 PROHIBIT THE DRYER FROM FUNCTIONING.
 PLEASE NOTE, SUBMITTAL FOR THE BOOSTER
 FANS SHALL BE SUMITTED TO THE BUILDING
 OFFICIAL AS ALTERNATE MEANS & METHODS,
 FOR HIS APPOVAL.
  
 4.PLAN SHEET M202 THE CONDENSING UNIT
 RACK, THE MINIMUM CLEARANCE BETWEEN THE
 ROOF SURFACE AND BOTTOM OF THE SUPPORT
 RAIL SHALL COMPLY WITH 2001 FBC 1511.7.
 PLEASE INDICATE CLEARANCE ON THE PLAN.
  
 5.RETURN AIR JUMPERS FOR THE MASTER
 SUITE ARE NOT SIZED PROPERLY.PER 2001
 FBC(M)601.4 EXCEPTION #1 & 3, RETURN
 AIR
 JUMPERS SHALL BE A MINIIMUM OF 1 1/2
 TIMES THE SQUARE INCHES OF THE SUPPLY.
 ALL AIR INTO THE MASTER SUITE IS TO BE
 INCLUDED FOR THE TOTAL AIR SUPPLIED TO
 THE SUTIE, THE R/A JUMPER SHALL BE 1
 1/2
 TIMES THE TOTAL SUPPLY AIR INTO THE
 SUITE.
  
 6.PLEASE NOTE CONDENSATE SHALL NOT
 TERMINATE INTO THE SANATARY PER CITY
 CODE SECTION 90-125 (5).
  
 7.PROVIDE OUTSIDE AIR CALUCALTIONS FOR
 ALL AREAS - RESIDENTIAL, GARAGE, AND ALL
 COMMON AREAS.2001 FBC(M)403.3.
  
 8.PLEASE PROVIDE CALUCLATIONS FOR
 GARAGE VENTILATION SHOWING COMPLIANCE
 WITH 2001 FBC411.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.