| 2004-12-02 00:00:00 | DENIED: |
| | 1.PLANS INDICATE SOME ROOMS OFF THE |
| | ENCLOSED GARAGE ARE USING THE AIR IN |
| | THE GARAGE FOR MAKE-UP OR OUTSIDE AIR. |
| | PER 2001 FBC(M)401.5, FRESH AIR/MAKE-UP |
| | AIR SHALL NOT BE LOCATED 10 FT FROM |
| | NOXIOUS CONTAMINANTS SUCH AS PARKING |
| | LOTS OR LOADING DOCKS. |
| | |
| | 2.A MINIMUM OF 4" CLEARANCE REQUIRED |
| | AROUND THE AHU IN ACCORDANCE WITH 2001 |
| | FBC(M)603.1.3. |
| | |
| | 3.PLEASE PROVIDE A SCHEMATIC |
| | INDICATING ELECTRICAL WIRING SHOWING |
| | HOW THE BOOSTER FAN FAILURE WILL |
| | PROHIBIT THE DRYER FROM FUNCTIONING. |
| | PLEASE NOTE, SUBMITTAL FOR THE BOOSTER |
| | FANS SHALL BE SUMITTED TO THE BUILDING |
| | OFFICIAL AS ALTERNATE MEANS & METHODS, |
| | FOR HIS APPOVAL. |
| | |
| | 4.PLAN SHEET M202 THE CONDENSING UNIT |
| | RACK, THE MINIMUM CLEARANCE BETWEEN THE |
| | ROOF SURFACE AND BOTTOM OF THE SUPPORT |
| | RAIL SHALL COMPLY WITH 2001 FBC 1511.7. |
| | PLEASE INDICATE CLEARANCE ON THE PLAN. |
| | |
| | 5.RETURN AIR JUMPERS FOR THE MASTER |
| | SUITE ARE NOT SIZED PROPERLY.PER 2001 |
| | FBC(M)601.4 EXCEPTION #1 & 3, RETURN |
| | AIR |
| | JUMPERS SHALL BE A MINIIMUM OF 1 1/2 |
| | TIMES THE SQUARE INCHES OF THE SUPPLY. |
| | ALL AIR INTO THE MASTER SUITE IS TO BE |
| | INCLUDED FOR THE TOTAL AIR SUPPLIED TO |
| | THE SUTIE, THE R/A JUMPER SHALL BE 1 |
| | 1/2 |
| | TIMES THE TOTAL SUPPLY AIR INTO THE |
| | SUITE. |
| | |
| | 6.PLEASE NOTE CONDENSATE SHALL NOT |
| | TERMINATE INTO THE SANATARY PER CITY |
| | CODE SECTION 90-125 (5). |
| | |
| | 7.PROVIDE OUTSIDE AIR CALUCALTIONS FOR |
| | ALL AREAS - RESIDENTIAL, GARAGE, AND ALL |
| | COMMON AREAS.2001 FBC(M)403.3. |
| | |
| | 8.PLEASE PROVIDE CALUCLATIONS FOR |
| | GARAGE VENTILATION SHOWING COMPLIANCE |
| | WITH 2001 FBC411.4. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |