| Date |
Text |
| 2004-12-07 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04110183 |
| | ADD: 3900 N FLAGLER BLDG# 1 |
| | CONT: MANHATTEN CONSTRUCTION |
| | TEL: (813)927-0209 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1)PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2)THE FINISHED FLOOR LEVEL SHALL BE |
| | VERIFIED BY A SIGNED AND SEALED |
| | ELEVATION CERTIFICATE. LOCATED IN A |
| | FLOOD ZONE, THE MINIMUM FINISH FLOOR |
| | ELEVATION IN A A5 FLOOD ZONE IS7'-6". |
| | |
| | 3) 105.3** THE BUILDING OFICIAL MAY MAKE |
| | OR CAUSE TO HAVE A SPECIAL INSPECTOR |
| | PRESENT AT ALL TIMES THAT WORK IS IN |
| | PROGRESS FOR STRUCTURAL COMPONENTS. |
| | |
| | |
| | 4) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL |
| | IS NOT DEFINITLY KNOWN OR IS IN QUESTION |
| | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| | ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| | TO THE PERMISSIBLE SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL |
| | PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | |
| | 5) STRUCTURAL PLANS INDICATE THAT A |
| | SOILS REPORT SHALL REQUIRE 16" AUGER |
| | PILE, THE GEOTECHNICAL ENGINEER SHALL |
| | SUBMIT TO THE DESIGNER OF RECORD FOR |
| | REVIEW ALL DOCUMENTS BEFORE SUBMITING |
| | TO THE CITY. |
| | |
| | 6) ENCLOSED PARKING GARAGE, 411.4.2. |
| | TO PROVIDE 6 AIR CHANGES PER HR. UNDER |
| | NORMAL USE THE VENTILATION OFTHE AUTO |
| | MOBILE PARKING GARAGE SHALL COMPLY WITH |
| | |
| | THE VENTILATION REQUIREMENTS FOR 411.5. |
| | |
| | THIS REVIEW WILL CONTINUE WED 12-08-04JW |
| 2004-12-01 00:00:00 | ************ UNSAT ****************** |
| | |
| | THE FOLLOWING NOTES FOR 3900 N. FLAGLER |
| | BLUILDINGS 1-6 |
| | 04110182, |
| | 04110183, |
| | 04110184, |
| | 04110185 |
| | PLEASE SEE MANY OF THE FOLLOWING |
| | COMMENTS ARE TYPICAL FOR EACH BLDG. |
| | |
| | |
| | 1)NOTE: PLEASE SEE BLDG REVIEW |
| | COMMENTS: |
| | EACH BLDG TO BE UNDER SEPARATE PERMITS. |
| | MULTIPLE BLDGS UNDER ONE PERMIT MAY |
| | CREATE ISSUES WITH INSPECTIONS AND |
| | C.O.'S. |
| | |
| | 2)NOTE: PLEASE SEE FAC 61G1-16.004, FAC |
| | 61G15-23.002 FOR ALL REQUIRED |
| | INFORMATION ON TITLE BLOCKS. |
| | CERTIFICATE |
| | OF AUTHORIZATION #'S PER FS |
| | 481.219,471.023. |
| | THIS IS FOR ALL SHEETS AND FOR ALL |
| | TRADES WHEATHER OR NOT COMMENT IS MADE |
| | BY OTHER REVIEWER(S). |
| | |
| | 3)NOTE: PLEASE PROVIDE ROOM |
| | DESIGNATIONS |
| | ON PLANS. |
| | |
| | 4)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| | SPACING IN DWELLING UNITS. PLEASE SEE |
| | 2' |
| | OF WALL SPACE, W/IN 6' OF DOOR ETC. |
| | PLEASE SEE MANY OF THESE AREAS ARE |
| | REDLINED ON ONE OF THE SETS OF PLANS |
| | TURNED IN. |
| | |
| | 5)NOTE: PLEASE SEE 210.52H FOR MISSING |
| | HALLWAY RECEPT. |
| | |
| | 6)NOTE: PLEASE SEE 110.26 FOR SPACING |
| | ABOUT ELECTRICAL EQUIPMENT. |
| | WORKING SPACE FOR EQUIPMENT OPERATING |
| | AT |
| | 600 VOLTS, NOMINAL, OR LESS TO GROUND |
| | AND LIKELY TO REQUIRE EXAMINATION, |
| | ADJUSTMENT, SERVICING, OR MAINTENANCE |
| | WHILE ENERGIZED SHALL COMPLY WITH THE |
| | DIMENSIONS OF 110.26(A)(1), (2), AND |
| | (3) |
| | OR AS REQUIRED OR PERMITTED ELSEWHERE |
| | IN |
| | THIS CODE PLEASE SEE SOME UNITS APPEAR |
| | TO HAVE ROOMS TOO SMALL AND/OR ITEMS |
| | LIKE APPLIANCES IN REQUIRED SPACE. |
| | |
| | 7)NOTE: PLEASE SEE 210.8A6, ALL RECEPTS |
| | IN KITCHENS SERVING KITCHEN |
| | COUNTERSPACE |
| | ARE REQUIRED TO BE GFI/GFI PROTECTED. |
| | PLEASE INDICATE. |
| | PLEASE SEE SYMBOL LEGEND: SOME OF THESE |
| | RECEPTS AS SHOWN ON PLANS IN KITCHENS |
| | DO |
| | NOT APPEAR TO BE ON LEGEND? |
| | THIS SAME SYMBOL SHOWN FOR BATH |
| | RECETPS. |
| | |
| | THIS IS "ASSUMED" TO BE A "GFI". |
| | |
| | 8)NOTE: PLEASE SEE SMOKE DETECTORS IN |
| | UNITS: THESE ARE REQUIRED TO BE WIRED |
| | "IN-LINE" , YET SD'S ARE SHOWN ON |
| | MULTIPLE CIRCUITS, SOME AS MANY AS 5 |
| | CIRCUITS IN SOME UNITS.? |
| | THIS WOULD NOT WORK AS SHOWN. |
| | |
| | |
| | 9)NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | 20A #12 |
| | |
| | 10)NOTE: PLEASE SEE FIXTURE TYPE "J" AS |
| | SHOWN ON LEGEND FOR CLOSETS. |
| | PLEASE SEE 410.8, SOME OF THESE DO NOT |
| | SEEM TO MEET CLEARENCE REQUIREMNTS. |
| | THE VOLUME BOUNDED BY THE SIDES AND |
| | BACK |
| | CLOSET WALLS AND PLANES EXTENDING FROM |
| | THE CLOSET FLOOR VERTICALLY TO A HEIGHT |
| | OF 1.8 M (6 FT) OR THE HIGHEST |
| | CLOTHES-HANGING ROD AND PARALLEL TO THE |
| | WALLS AT A HORIZONTAL DISTANCE OF 600 |
| | MM |
| | (24 IN.) FROM THE SIDES AND BACK OF THE |
| | CLOSET WALLS, RESPECTIVELY, AND |
| | CONTINUING VERTICALLY TO THE CLOSET |
| | CEILING PARALLEL TO THE WALLS AT A |
| | HORIZONTAL DISTANCE OF 300 MM (12 IN.) |
| | OR THE WIDTH OF THE SHELF, WHICHEVER IS |
| | GREATER; FOR A CLOSET THAT PERMITS |
| | ACCESS TO BOTH SIDES OF A HANGING ROD, |
| | THIS SPACE INCLUDES THE VOLUME BELOW |
| | THE |
| | HIGHEST ROD EXTENDING 300 MM (12 IN.) |
| | ON |
| | EITHER SIDE OF THE ROD ON A PLANE |
| | HORIZONTAL TO THE FLOOR EXTENDING THE |
| | ENTIRE LENGTH OF THE ROD. |
| | PLEASE SEE SOME UNIT'S CLOSETS ARE MUCH |
| | SMALLER THAN OTHERS. |
| | |
| | 11)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR |
| | SD PLACEMENTS AND CLEARENCES FROM BATH |
| | DRS, KITCHEN DRS AND COOKING |
| | APPLIANCES. |
| | PLEASE ALSO SEE EXCEPTIONS. |
| | PLEASE PLACE NOTE ON PLANS FOR ABOVE. |
| | |
| | 12)NOTE:PLEASE SEE "DINING ROOM" RECEPT |
| | REQUIREMENTS FOR CIRCUITING. |
| | PLEASE SEE THESE RECEPTS MUST BE ON A |
| | 20A SM APPL CIRCUIT, 2 OR MORE. |
| | SOME SHOWN ON LIGHTINGCIRCUIT(S)? |
| | |
| | 13)NOTE: PLEASE SEE UNIT H-5, BEDRM |
| | SHOWN W/OUT DOORS? OPEN TO KITCHEN AND |
| | LIVING ROOM AREA?? |
| | |
| | 14)NOTE: PLEASE VERIFY LOADS FOR A/C, |
| | AHU'S. PLEASE SEE LOAD CALCULATIONS |
| | INDICATE SOME AT 15KW AND OTHERS AT |
| | 12KW |
| | ARE THESE SPLIT? AND IF SO PLEASE |
| | INDICATE LOAD ON INDIVIDUAL UNITS IN |
| | ORDER TO VERIFY OCP, AWG PER |
| | 424.3B,310.16. |
| | |
| | 15)NOTE: PLEASE SEE 694.4B(1) |
| | OVERCURRENT DEVICE SELECTION. |
| | THE OVERCURRENT PROTECTIVE DEVICE(S) |
| | SHALL BE SELECTED OR SET TO CARRY |
| | INDEFINITELY THE SUM OF THE |
| | LOCKED-ROTOR |
| | CURRENT OF THE FIRE PUMP MOTOR(S) AND |
| | THE PRESSURE MAINTENANCE PUMP MOTOR(S) |
| | AND THE FULL-LOAD CURRENT OF THE |
| | ASSOCIATED FIRE PUMP ACCESSORY |
| | EQUIPMENT |
| | WHEN CONNECTED TO THIS POWER SUPPLY. |
| | PLEASE VERIFY METHOD OF OVERCURRENT |
| | PROTECTION. PLEASE VERIFY IF OCP IS |
| | PROVIDED IN FIRE PUMP CONTROLLER OR |
| | DISCONNECT? |
| | TWO MEANS OF OCP ID NOT PERMITTED. |
| | PLEASE SUBMIT COMPLETE MANUFACTURE |
| | SPECS |
| | FOR FIRE PUMP, AND FIRE PUMP |
| | CONTROLLER. |
| | |
| | 16)NOTE: PLEASE SEE 220.16 SMALL |
| | APPLIANCE AND LAUNDRY LOADS ? DWELLING |
| | UNIT. |
| | PLEASE INDICATE THE SMALL APPL CIRCUITS |
| | ON PANEL SCHEDULE. |
| | SMALL APPLIANCE CIRCUIT LOAD IN EACH |
| | DWELLING UNITSHALL BE COMPUTED AT |
| | 1500 |
| | VOLT-AMPERES FOR EACH 2-WIRE |
| | SMALL-APPLIANCE BRANCH CIRCUIT REQUIRED |
| | BY 210.11(C)(1). |
| | |
| | 17)NOTE: PLEASE VERIFY LOCATIONS OF |
| | "SHUNT-TRIP" PUSHBUTTONS ON PLANS? |
| | PLEASE VERFIY IF MAINS IN METER BANKS |
| | CONTAIN DISCONNECTION MEANS PER |
| | 230.76,230.79? |
| | THE SERVICE DISCONNECTING MEANS FOR |
| | UNGROUNDED SERVICE CONDUCTORS SHALL |
| | CONSIST OF EITHER (1) A MANUALLY |
| | OPERABLE SWITCH OR CIRCUIT BREAKER |
| | EQUIPPED WITH A HANDLE OR OTHER |
| | SUITABLE |
| | OPERATING MEANS OR (2) A POWER-OPERATED |
| | SWITCH OR CIRCUIT BREAKER, PROVIDED THE |
| | SWITCH OR CIRCUIT BREAKER CAN BE OPENED |
| | BY HAND IN THE EVENT OF A POWER SUPPLY |
| | FAILURE. |
| | THE SERVICE DISCONNECTING MEANS SHALL |
| | HAVE A RATING NOT LESS THAN THE LOAD TO |
| | BE CARRIED, DETERMINED IN ACCORDANCE |
| | WITH ARTICLE 220. IN NO CASE SHALL THE |
| | RATING BE LOWER THAN SPECIFIED IN |
| | 230.79(A), (B), (C), OR (D). |
| | |
| | 18)NOTE: PLEASE SEE 250.104 |
| | THIS NOTE IS FOR ANY POSSIBLE "METAL" |
| | FIRE SPRINLER PIPE(S). |
| | THE METAL WATER PIPING SYSTEM SHALL BE |
| | BONDED AS REQUIRED IN (1), (2), (3), OR |
| | (4) OF THIS SECTION. THE BONDING |
| | JUMPER(S) SHALL BE INSTALLED IN |
| | ACCORDANCE WITH 250.64(A), (B), AND |
| | (E). |
| | THE POINTS OF ATTACHMENT OF THE BONDING |
| | JUMPER(S) SHALL BE ACCESSIBLE. |
| | METAL WATER PIPING SYSTEM(S) INSTALLED |
| | IN OR ATTACHED TO A BUILDING OR |
| | STRUCTURE SHALL BE BONDED TO THE |
| | SERVICE |
| | EQUIPMENT ENCLOSURE, THE GROUNDED |
| | CONDUCTOR AT THE SERVICE, THE GROUNDING |
| | ELECTRODE CONDUCTOR WHERE OF SUFFICIENT |
| | SIZE, OR TO THE ONE OR MORE GROUNDING |
| | ELECTRODES USED. THE BONDING JUMPER(S) |
| | SHALL BE SIZED IN ACCORDANCE WITH TABLE |
| | 250.66 EXCEPT AS PERMITTED IN |
| | 250.104(A)(2) AND (A)(3). |
| | |
| | 19)NOTE: PLEASE SEE FPL REQUIREMENST |
| | FOR |
| | ELECTRICAL SERVICE INSTALLATIONS. |
| | METERING EQUIPMENT "INDOORS" MAY BE A |
| | MAX OF 72"/6' AND A MIN OF 22" ABOVE |
| | FLR |
| | TO THE CENTELINE OF THE METER. |
| | PLEASE SEE RISER DIAGRAM APPEARS TO |
| | SHOW |
| | |
| | METER CENTERS ON THE FLOORS. |
| | |
| | 20)NOTE: PLEASE SEE 250.106 LIGHTNING |
| | PROTECTION SYSTEMS. |
| | THE LIGHTNING PROTECTION SYSTEM GROUND |
| | TERMINALS SHALL BE BONDED TO THE |
| | BUILDING OR STRUCTURE GROUNDING. |
| | ELECTRODE SYSTEM. |
| | PLEASE SEE IF ANY SYSTEM(S) ARE |
| | INSTALLED THEN THEY MUST MEET NFPA-780 |
| | |
| | 21)NOTE: PLEASE GIVE INDICATION OF THE |
| | ARC FAULT PROTECTION PER 2002 NEC |
| | 210.12, WHICH REQUIRES PROTECTION FOR |
| | ALL "OUTLETS", SD'S LTS, RECEPTS, FANS |
| | ETC. |
| | IT IS NOTED ON PANEL SCHEDULES ABOUT |
| | ARC |
| | FAULT PROTECTION, HOWEVER PLEASE ADD TO |
| | TO THE EXISTING NOTE. |
| | |
| | 22)NOTE: PLEASE SEE FIRE REVIEW, PLEASE |
| | SEE THAT A "KNOX-BOX" WILL BE REQUIRED |
| | FOR EACH BLDG. |
| | PLEASE SEE FIRE FOR SPECIFICS. |
| | |
| | 23)NOTE: PLEASE REMOVE ALL OLD/VOIDED |
| | SHEETS FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO THREE COMPLETE SETS |
| | |
| | FOR REVIEW AND STAMPING. |
| | |
| | 24)NOTE: PLEASE SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER REVIEWER(S) WHICH |
| | MAY AFFECT ELECTRICAL PLANS. |
| | |
| | |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2004-11-30 00:00:00 | IN ELECTRICAL FOR REVIEW,NOTES WILL |
| | FOLLOW. |