Plan Review Notes
Plan Review Notes For Permit 04110182
Permit Number 04110182
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110183
 ADD: 3900 N FLAGLER BLDG# 1
 CONT: MANHATTEN CONSTRUCTION
 TEL: (813)927-0209
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)THE FINISHED FLOOR LEVEL SHALL BE
 VERIFIED BY A SIGNED AND SEALED
 ELEVATION CERTIFICATE. LOCATED IN A
 FLOOD ZONE, THE MINIMUM FINISH FLOOR
 ELEVATION IN A A5 FLOOD ZONE IS7'-6".
  
 3) 105.3** THE BUILDING OFICIAL MAY MAKE
 OR CAUSE TO HAVE A SPECIAL INSPECTOR
 PRESENT AT ALL TIMES THAT WORK IS IN
 PROGRESS FOR STRUCTURAL COMPONENTS.
  
  
 4) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 5) STRUCTURAL PLANS INDICATE THAT A
 SOILS REPORT SHALL REQUIRE 16" AUGER
 PILE, THE GEOTECHNICAL ENGINEER SHALL
 SUBMIT TO THE DESIGNER OF RECORD FOR
 REVIEW ALL DOCUMENTS BEFORE SUBMITING
 TO THE CITY.
  
 6) ENCLOSED PARKING GARAGE, 411.4.2.
 TO PROVIDE 6 AIR CHANGES PER HR. UNDER
 NORMAL USE THE VENTILATION OFTHE AUTO
 MOBILE PARKING GARAGE SHALL COMPLY WITH
  
 THE VENTILATION REQUIREMENTS FOR 411.5.
  
 THIS REVIEW WILL CONTINUE WED 12-08-04JW
2004-12-01 00:00:00************ UNSAT ******************
  
 THE FOLLOWING NOTES FOR 3900 N. FLAGLER
 BLUILDINGS 1-6
 04110182,
 04110183,
 04110184,
 04110185
 PLEASE SEE MANY OF THE FOLLOWING
 COMMENTS ARE TYPICAL FOR EACH BLDG.
  
  
 1)NOTE: PLEASE SEE BLDG REVIEW
 COMMENTS:
 EACH BLDG TO BE UNDER SEPARATE PERMITS.
 MULTIPLE BLDGS UNDER ONE PERMIT MAY
 CREATE ISSUES WITH INSPECTIONS AND
 C.O.'S.
  
 2)NOTE: PLEASE SEE FAC 61G1-16.004, FAC
 61G15-23.002 FOR ALL REQUIRED
 INFORMATION ON TITLE BLOCKS.
 CERTIFICATE
 OF AUTHORIZATION #'S PER FS
 481.219,471.023.
 THIS IS FOR ALL SHEETS AND FOR ALL
 TRADES WHEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWER(S).
  
 3)NOTE: PLEASE PROVIDE ROOM
 DESIGNATIONS
 ON PLANS.
  
 4)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING IN DWELLING UNITS. PLEASE SEE
 2'
 OF WALL SPACE, W/IN 6' OF DOOR ETC.
 PLEASE SEE MANY OF THESE AREAS ARE
 REDLINED ON ONE OF THE SETS OF PLANS
 TURNED IN.
  
 5)NOTE: PLEASE SEE 210.52H FOR MISSING
 HALLWAY RECEPT.
  
 6)NOTE: PLEASE SEE 110.26 FOR SPACING
 ABOUT ELECTRICAL EQUIPMENT.
 WORKING SPACE FOR EQUIPMENT OPERATING
 AT
 600 VOLTS, NOMINAL, OR LESS TO GROUND
 AND LIKELY TO REQUIRE EXAMINATION,
 ADJUSTMENT, SERVICING, OR MAINTENANCE
 WHILE ENERGIZED SHALL COMPLY WITH THE
 DIMENSIONS OF 110.26(A)(1), (2), AND
 (3)
 OR AS REQUIRED OR PERMITTED ELSEWHERE
 IN
 THIS CODE PLEASE SEE SOME UNITS APPEAR
 TO HAVE ROOMS TOO SMALL AND/OR ITEMS
 LIKE APPLIANCES IN REQUIRED SPACE.
  
 7)NOTE: PLEASE SEE 210.8A6, ALL RECEPTS
 IN KITCHENS SERVING KITCHEN
 COUNTERSPACE
 ARE REQUIRED TO BE GFI/GFI PROTECTED.
 PLEASE INDICATE.
 PLEASE SEE SYMBOL LEGEND: SOME OF THESE
 RECEPTS AS SHOWN ON PLANS IN KITCHENS
 DO
 NOT APPEAR TO BE ON LEGEND?
 THIS SAME SYMBOL SHOWN FOR BATH
 RECETPS.
  
 THIS IS "ASSUMED" TO BE A "GFI".
  
 8)NOTE: PLEASE SEE SMOKE DETECTORS IN
 UNITS: THESE ARE REQUIRED TO BE WIRED
 "IN-LINE" , YET SD'S ARE SHOWN ON
 MULTIPLE CIRCUITS, SOME AS MANY AS 5
 CIRCUITS IN SOME UNITS.?
 THIS WOULD NOT WORK AS SHOWN.
  
  
 9)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 20A #12
  
 10)NOTE: PLEASE SEE FIXTURE TYPE "J" AS
 SHOWN ON LEGEND FOR CLOSETS.
 PLEASE SEE 410.8, SOME OF THESE DO NOT
 SEEM TO MEET CLEARENCE REQUIREMNTS.
 THE VOLUME BOUNDED BY THE SIDES AND
 BACK
 CLOSET WALLS AND PLANES EXTENDING FROM
 THE CLOSET FLOOR VERTICALLY TO A HEIGHT
 OF 1.8 M (6 FT) OR THE HIGHEST
 CLOTHES-HANGING ROD AND PARALLEL TO THE
 WALLS AT A HORIZONTAL DISTANCE OF 600
 MM
 (24 IN.) FROM THE SIDES AND BACK OF THE
 CLOSET WALLS, RESPECTIVELY, AND
 CONTINUING VERTICALLY TO THE CLOSET
 CEILING PARALLEL TO THE WALLS AT A
 HORIZONTAL DISTANCE OF 300 MM (12 IN.)
 OR THE WIDTH OF THE SHELF, WHICHEVER IS
 GREATER; FOR A CLOSET THAT PERMITS
 ACCESS TO BOTH SIDES OF A HANGING ROD,
 THIS SPACE INCLUDES THE VOLUME BELOW
 THE
 HIGHEST ROD EXTENDING 300 MM (12 IN.)
 ON
 EITHER SIDE OF THE ROD ON A PLANE
 HORIZONTAL TO THE FLOOR EXTENDING THE
 ENTIRE LENGTH OF THE ROD.
 PLEASE SEE SOME UNIT'S CLOSETS ARE MUCH
 SMALLER THAN OTHERS.
  
 11)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR
 SD PLACEMENTS AND CLEARENCES FROM BATH
 DRS, KITCHEN DRS AND COOKING
 APPLIANCES.
 PLEASE ALSO SEE EXCEPTIONS.
 PLEASE PLACE NOTE ON PLANS FOR ABOVE.
  
 12)NOTE:PLEASE SEE "DINING ROOM" RECEPT
 REQUIREMENTS FOR CIRCUITING.
 PLEASE SEE THESE RECEPTS MUST BE ON A
 20A SM APPL CIRCUIT, 2 OR MORE.
 SOME SHOWN ON LIGHTINGCIRCUIT(S)?
  
 13)NOTE: PLEASE SEE UNIT H-5, BEDRM
 SHOWN W/OUT DOORS? OPEN TO KITCHEN AND
 LIVING ROOM AREA??
  
 14)NOTE: PLEASE VERIFY LOADS FOR A/C,
 AHU'S. PLEASE SEE LOAD CALCULATIONS
 INDICATE SOME AT 15KW AND OTHERS AT
 12KW
 ARE THESE SPLIT? AND IF SO PLEASE
 INDICATE LOAD ON INDIVIDUAL UNITS IN
 ORDER TO VERIFY OCP, AWG PER
 424.3B,310.16.
  
 15)NOTE: PLEASE SEE 694.4B(1)
 OVERCURRENT DEVICE SELECTION.
 THE OVERCURRENT PROTECTIVE DEVICE(S)
 SHALL BE SELECTED OR SET TO CARRY
 INDEFINITELY THE SUM OF THE
 LOCKED-ROTOR
 CURRENT OF THE FIRE PUMP MOTOR(S) AND
 THE PRESSURE MAINTENANCE PUMP MOTOR(S)
 AND THE FULL-LOAD CURRENT OF THE
 ASSOCIATED FIRE PUMP ACCESSORY
 EQUIPMENT
 WHEN CONNECTED TO THIS POWER SUPPLY.
 PLEASE VERIFY METHOD OF OVERCURRENT
 PROTECTION. PLEASE VERIFY IF OCP IS
 PROVIDED IN FIRE PUMP CONTROLLER OR
 DISCONNECT?
 TWO MEANS OF OCP ID NOT PERMITTED.
 PLEASE SUBMIT COMPLETE MANUFACTURE
 SPECS
 FOR FIRE PUMP, AND FIRE PUMP
 CONTROLLER.
  
 16)NOTE: PLEASE SEE 220.16 SMALL
 APPLIANCE AND LAUNDRY LOADS ? DWELLING
 UNIT.
 PLEASE INDICATE THE SMALL APPL CIRCUITS
 ON PANEL SCHEDULE.
 SMALL APPLIANCE CIRCUIT LOAD IN EACH
 DWELLING UNITSHALL BE COMPUTED AT
 1500
 VOLT-AMPERES FOR EACH 2-WIRE
 SMALL-APPLIANCE BRANCH CIRCUIT REQUIRED
 BY 210.11(C)(1).
  
 17)NOTE: PLEASE VERIFY LOCATIONS OF
 "SHUNT-TRIP" PUSHBUTTONS ON PLANS?
 PLEASE VERFIY IF MAINS IN METER BANKS
 CONTAIN DISCONNECTION MEANS PER
 230.76,230.79?
 THE SERVICE DISCONNECTING MEANS FOR
 UNGROUNDED SERVICE CONDUCTORS SHALL
 CONSIST OF EITHER (1) A MANUALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER
 EQUIPPED WITH A HANDLE OR OTHER
 SUITABLE
 OPERATING MEANS OR (2) A POWER-OPERATED
 SWITCH OR CIRCUIT BREAKER, PROVIDED THE
 SWITCH OR CIRCUIT BREAKER CAN BE OPENED
 BY HAND IN THE EVENT OF A POWER SUPPLY
 FAILURE.
 THE SERVICE DISCONNECTING MEANS SHALL
 HAVE A RATING NOT LESS THAN THE LOAD TO
 BE CARRIED, DETERMINED IN ACCORDANCE
 WITH ARTICLE 220. IN NO CASE SHALL THE
 RATING BE LOWER THAN SPECIFIED IN
 230.79(A), (B), (C), OR (D).
  
 18)NOTE: PLEASE SEE 250.104
 THIS NOTE IS FOR ANY POSSIBLE "METAL"
 FIRE SPRINLER PIPE(S).
 THE METAL WATER PIPING SYSTEM SHALL BE
 BONDED AS REQUIRED IN (1), (2), (3), OR
 (4) OF THIS SECTION. THE BONDING
 JUMPER(S) SHALL BE INSTALLED IN
 ACCORDANCE WITH 250.64(A), (B), AND
 (E).
 THE POINTS OF ATTACHMENT OF THE BONDING
 JUMPER(S) SHALL BE ACCESSIBLE.
 METAL WATER PIPING SYSTEM(S) INSTALLED
 IN OR ATTACHED TO A BUILDING OR
 STRUCTURE SHALL BE BONDED TO THE
 SERVICE
 EQUIPMENT ENCLOSURE, THE GROUNDED
 CONDUCTOR AT THE SERVICE, THE GROUNDING
 ELECTRODE CONDUCTOR WHERE OF SUFFICIENT
 SIZE, OR TO THE ONE OR MORE GROUNDING
 ELECTRODES USED. THE BONDING JUMPER(S)
 SHALL BE SIZED IN ACCORDANCE WITH TABLE
 250.66 EXCEPT AS PERMITTED IN
 250.104(A)(2) AND (A)(3).
  
 19)NOTE: PLEASE SEE FPL REQUIREMENST
 FOR
 ELECTRICAL SERVICE INSTALLATIONS.
 METERING EQUIPMENT "INDOORS" MAY BE A
 MAX OF 72"/6' AND A MIN OF 22" ABOVE
 FLR
 TO THE CENTELINE OF THE METER.
 PLEASE SEE RISER DIAGRAM APPEARS TO
 SHOW
  
 METER CENTERS ON THE FLOORS.
  
 20)NOTE: PLEASE SEE 250.106 LIGHTNING
 PROTECTION SYSTEMS.
 THE LIGHTNING PROTECTION SYSTEM GROUND
 TERMINALS SHALL BE BONDED TO THE
 BUILDING OR STRUCTURE GROUNDING.
 ELECTRODE SYSTEM.
 PLEASE SEE IF ANY SYSTEM(S) ARE
 INSTALLED THEN THEY MUST MEET NFPA-780
  
 21)NOTE: PLEASE GIVE INDICATION OF THE
 ARC FAULT PROTECTION PER 2002 NEC
 210.12, WHICH REQUIRES PROTECTION FOR
 ALL "OUTLETS", SD'S LTS, RECEPTS, FANS
 ETC.
 IT IS NOTED ON PANEL SCHEDULES ABOUT
 ARC
 FAULT PROTECTION, HOWEVER PLEASE ADD TO
 TO THE EXISTING NOTE.
  
 22)NOTE: PLEASE SEE FIRE REVIEW, PLEASE
 SEE THAT A "KNOX-BOX" WILL BE REQUIRED
 FOR EACH BLDG.
 PLEASE SEE FIRE FOR SPECIFICS.
  
 23)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO THREE COMPLETE SETS
  
 FOR REVIEW AND STAMPING.
  
 24)NOTE: PLEASE SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
2004-11-30 00:00:00IN ELECTRICAL FOR REVIEW,NOTES WILL
 FOLLOW.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved