Plan Review Notes
Plan Review Notes For Permit 04110101
Permit Number 04110101
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 2) THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.3.2
 3) SHT PO.1 WATER RISER DIAGRAM, THE
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE", NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS. (SEE PLUMBING NOTES 13)
 4) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME. INITIALS ARE NOT APPROVED. FAC
 61G15-23.002(1) & FS 471.025 - THIS IS
 FOR ALL M.E.P. SHEETS.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]