| Plan Review Notes For Permit 04110101 |
| Permit Number |
04110101 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-12 00:00:00 | 1) FIRE ALARM CIRCUITS SHALL BE CLASS | | | A, STYLE D NOT CLASS B, STYLE C AS | | | SHOWN ON PAGE FAO.1. | | | | | | 2) DUCT SMOKE DETECTORS WHEN | | | ACTIVATED SHALL CAUSE AN ALARM NOT | | | A SUPERVISORY SIGNAL AS SHOWN ON | | | PAGE FA0.1. | | | | | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR FIRE SPRINKLERS AND FIRE ALARM | | | REMODELS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|