| Plan Review Notes For Permit 04110101 |
| Permit Number |
04110101 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-16 00:00:00 | ************** UNSAT *********** | | | | | | 1)NOTE: PLEASE HAVE PLANS SIGNED WITH | | | "LEGAL" "SIGNATURE" . INITIALS ARE NOT | | | PERMITTED. | | | PLANS ARE ALSO REQUIRED TO BE DATED | | | UNDER THE SAME FS'S | | | THIS IS REQUIRED FOR ALL SHEETS AND FOR | | | ALL TRADES WHEATER OR NOT COMMENT IS | | | MADE BY OTHER REVIEWERS. | | | FS 471.025, FAC 61G15-23.002 | | | | | | 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. | | | 230.42,215.3 ETC. | | | | | | 3)NOTE: PLEASE CLARIFY IF THERE IS AN | | | EXISTING OR NEW SIGN CIRCUIT(S). 600.5 | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWERS WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW, IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|