| 2006-09-17 00:00:00 | *** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS | | | REVIEW WHICH STATES TO CORRELATE RISER | | | AND PANEL SHOWN FOR SIZE ETC. | | | PLEASE SEE MLO, MCB?? | | | 106.1.2 FBC ADMIN SECT. | | | | | | 2) NOTE: THIS IS ONLY A NOTE, HOWEVER | | | PLEASE VERIFY THE OCP ON THE MAIN | | | DISCONNECT AS SHOWN. PLEASE SEE THE | | | EQUIPMENT GROUNDING CONDUCTOR FROM THE | | | MAIN TO THE SUB PANEL IS SHOWN 3 SIZES | | | ALRGER THAN NEEDED BASED ON THE OCP | | | SHOWN ON THE MAIN. 250.122 . | | | THIS IS OK, HOWEVER IF SHOWN LIKE THIS | | | ON RISER THEN THIS IS WHAT WILL BE | | | REQUIRED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REWVIEW. | | | 561-805-6717 | | | [email protected] |
|