| 2006-02-21 00:00:00 | *********** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE FS 481.221 WHICH |
| | REQUIRES THE ARCHITECT TO ALSO DATE |
| | PLANS WHEN SIGNING AND SEALING SAID |
| | DOCUMENTS. |
| | PLEASE SEE THIS IS NOTED AS "AS-BUILTS" |
| | INSTEAD OF DATE? |
| | PLEASE SEE COMMENTS BELOW |
| | |
| | 2)NOTE: PLEASE SEE AHU IS SHOWN ON A/C |
| | LAYOUT BUT NOT ON ELECTRICAL? PLEASE |
| | SHOW WITH CIRCUITING. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE CIRCUITING ON PLANS |
| | DOES NOT CORRELATE WITH NOTE FOR |
| | CIRCUITING OF EM/ EXT LTS. PLEASE SEE |
| | 700.12E WHICH REQUIRES EM/EXT LTS TO BE |
| | CIRCUITED TO THE LOCAL BRANCH CIRCUIT OF |
| | NORMAL LIGHTING IN ANY ONE AREA. |
| | PLEASE ALSO SEE PANEL SCHEDULE. |
| | |
| | 4)NOTE: PLEASESEE CIRCUIT ON SCHEDULE |
| | MENTIONS LTS FO PANEL ROOM?? |
| | PLEASE VERIFY WHAT THIS IS AS A PANEL |
| | ROOM COULD NOT BE LOCATED ON PLANS. |
| | |
| | 5)NOTE: PLEASE CORRELATE THE RISER AND |
| | PANEL SUBMITTED AS THESE ARE SHOWN WITH |
| | DIFFERENT SIZES. |
| | 215.5 |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. PLEASE BE SURE TO SEE ANY |
| | POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |