2005-01-14 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE NOTES ON PREVIOUS
 REVIEW FROM BLDG AND ELECTRICAL REVIEW.
 ALL OLD/VOIDED SHEETS ARE TO BE REMOVED
 FROM SETS AND ANY NEW SHEETS ARE TO BE
 INSERTED INTO COMPLETE SETS FOR REVIEW
 AND STAMPING.
  
 2)NOTE: PLEASE SEE A PANEL SCHEDULE IS
 NOW SUBMITTED, HOWEVER THIS PANEL
 SCHEDULE DOES NOT INDICATE ANY WIRE
 SIZES, OVER CURRENT PROTECTION FOR
 CIRCUITS? ETC.
 215.5
 PLEASE ALSO SEE 700.12 E FOR CIRCUITING
 OF EM/EXT LTS. THE BRANCH CIRCUIT
 FEEDING THE UNIT EQUIPMENT SHALL BE THE
 SAME BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW