| Plan Review Notes For Permit 04110084 |
| Permit Number |
04110084 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-30 00:00:00 | DENIED: | | | 1.RETURN AIR JUMPER FROM RM #102 & 103 | | | IS NOT SIZED.PROVIDE DUCT AND GRILLE | | | SIZE.PER 2001 FBC(M)601.4 EXCEPTION | | | #1, RETURN AIR JUMPER SHALL BE A MINIMUM | | | OF 1 1/2 TIMES THE SQUARE INCHES OF | | | SUPPLY (12"). | | | | | | 2.RETURN AIR GRILLE FROM RM #103 IS | | | NOT SIZED.PLEASE REVISE. | | | | | | 3.PROVIDE OUTSIDE OUTSIDE AIR | | | CALCULATIONS PER 2001 FBC(M) TABLE | | | 403.3. | | | | | | 4.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|