2004-11-05 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.215.5
  
 2)NOTE: PLEASE CLARIFY OF SERVICE SHOWN
 IS NEW OR EXISTING?
 PLEASE SHOW LOCATION OF SERVICE/PANELS
 ETC.
 IF THIS A NEW SERVICE, THIS MAY OR MAY
 NOT BE PERMITTED PER 230.2.
 230.72 ETC
 PLEASE ALSO VERIFY AIC RATING SHOWN AT
 77,000, THIS DOES NOT SEEM TO BE A
 NORMAL RATED SIZE.??
 110.9
  
 3)NOTE: PLEASE SHOW ANY AND ALL NEW A/C
 EQUIPMENT ALONG WITH REQUIRED
 DISCONNECTS PER 440.11 ON ELECTRICAL
 PLANS.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.