| Plan Review Notes For Permit 04110059 |
| Permit Number |
04110059 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-29 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) INDICATE SOURCE OF MAKE UP WATER FOR | | | THE CAR WASH. AN RPZ BACKFLOW IS | | | REQUIRED IF WATER SERVICE TO CAR WASH IS | | | DIRECTLY CONNECTED TO POTABLE WATER. | | | SECTION 608.13.2 | | | 2) ANY PROTION OF THE DRAINAGE SYSTEM | | | INSTALLED UNDERGROUNG SHALL NOT BE LESS | | | THAN 2 INCHES. SECTION 710.3 - PROPOSED | | | 1 INCH LINE CONNECTION NOT APPROVED. | | | 3) TWO WAY CLEANOUT IS REQUIRED AS THE | | | SANITARY BLDG DRAIN EXITS THE SLAB. | | | SECTION 708.3.5 | | | 4) A TRAP IS REQUIRED FOR THE OVERFLOW | | | LINE TO THE SANITARY SEWER. SECTION | | | 1002.1 | | | 5) A VENT IS REQUIRED FOR THE OVERFLOW | | | LINE TO THE SANITARY SEWER. SECTION | | | 902.1 | | | | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|