Plan Review Notes
Plan Review Notes For Permit 04110059
Permit Number 04110059
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) INDICATE SOURCE OF MAKE UP WATER FOR
 THE CAR WASH. AN RPZ BACKFLOW IS
 REQUIRED IF WATER SERVICE TO CAR WASH IS
 DIRECTLY CONNECTED TO POTABLE WATER.
 SECTION 608.13.2
 2) ANY PROTION OF THE DRAINAGE SYSTEM
 INSTALLED UNDERGROUNG SHALL NOT BE LESS
 THAN 2 INCHES. SECTION 710.3 - PROPOSED
 1 INCH LINE CONNECTION NOT APPROVED.
 3) TWO WAY CLEANOUT IS REQUIRED AS THE
 SANITARY BLDG DRAIN EXITS THE SLAB.
 SECTION 708.3.5
 4) A TRAP IS REQUIRED FOR THE OVERFLOW
 LINE TO THE SANITARY SEWER. SECTION
 1002.1
 5) A VENT IS REQUIRED FOR THE OVERFLOW
 LINE TO THE SANITARY SEWER. SECTION
 902.1
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]