| 2004-11-29 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SHTS A-1, A-2, & P-1 (A) INDICATES |
| | "3/4 INCH GALV. GAS PIPE & 1/2 INCH |
| | WATER AT THESE LOCATIONS ON SHTS A-1 & |
| | A-2, BUT SHT P-1 INDICATES THAT THE (A) |
| | LOCATIONS ARE FOR WASTE AND VENT LINE |
| | PLUS COLD WATER. PLEASE CORRELATE |
| | PUMBING SHEETS WITH THE ARCHITECTURAL |
| | SHEETS. SECTION 104.2.1 |
| | 2) A PROFESSIONAL ENGINEER SHALL SIGN |
| | HES NAME. INITIALS ARE NOT APPROVED. |
| | FAC |
| | 61G15-23.002(1) & FS 471.025 |
| | 3 THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR THE GAS PERMIT REQUIRED. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. - SHOW THE EXISTING |
| | SYSTEM AND ALL PIPE SIZES, WITH |
| | EXISTING |
| | BTU LOAD ON THE SYSTEM. |
| | B. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34).- THE TOTAL BTU LOAD FOR THE |
| | EXISTING SYSTEM SHALL BE SHOWN AS WELL |
| | AT THE TOTAL BTU LOAD FOR NEW SYSTEM. |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM |
| | PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | D) SHT P-2 SHOWS 13 GAS OUTLETS AT 1200 |
| | BTU PER OUTLET. THIS ADDS UP TO 15,600 |
| | BUT'S, BUT GAS INFORMATION INDICATES |
| | THAT IT IS 20,400 BTU'S PLEASE CLARIFY. |
| | SECTION 104.2.1 |
| | |
| | |
| | REVIEW BY KEN STEVENS |