| 2004-11-27 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) ARCHITECTURAL SHEETS: PRINTED NAME OF |
| | THE PERSON SEALING THE DOCUMENT IS |
| | REQUIRED PER FAC 61G1-16.004(6) AND FS |
| | 481.2055. |
| | 2) SHOW CLEAR FLOOR SPACE FOR LAVS, |
| | WATER CLOSETS, AND URINAL PER SECTIONS |
| | 11-4.16.2, 11-4.18.3, 11-4.19.3, AND |
| | 11-4.22.3. |
| | 3) SUBMIT A DETAIL FOR THE PANTRY SINK |
| | SHOWING COMPLIANCE WITH SECTION 11-4.24 |
| | AND ALL SUBSECTIONS. |
| | 4) A DRINKING FOUNTAIN IS REQUIRED PER |
| | TABLE 403.1. ALSO SEE SECTION 410.1 |
| | 5) SHT P-1 SANITARY RISER DIAGRAM AND |
| | FLOOR PLAN FOR PIPING. THE SINK SHALL |
| | NOT DRAIN THROUGH THE HORIZONTEL WET |
| | VENT OF THE TOILET ROOMS. SECTION 909.1. |
| | THE SINK SHALL CONNECT DOWNSTREAM OF THE |
| | WET-VENTED FIXTURES. (SEE RED LINE |
| | EXAMPLE ON ONE SET OF PLANS. |
| | 6) SHT P-1 WATER RISER DIAGRAM, AIR |
| | CHAMBERS ARE NOT APPROVED. SECTION |
| | 604.9 |
| | IF WATER HAMMER ARRESTORS ARE INSTALLED, |
| | THEY SHALL BE LOCATED NEAR THE FIXTURE |
| | IN AN "EFFECTIVE RANGE" NOT IN THE |
| | CEILING. PDI-WH 210 AND MANUF. |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | REVIEW BY KEN STEVENS |