Plan Review Notes
Plan Review Notes For Permit 04101257
Permit Number 04101257
Review Stop M
Sequence Number 5
Notes
Date Text
2006-10-26 08:50:58MECHANICAL REVISION
 *** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES #1AND 2, PLEASE
 CORRECT.
  
 2) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 3) PLEASE SHOW THE EQUIPMENT LISTING ON THE REVISED
 MECH. PLANS.
  
 4) PLEASE SHOW THE SIZE OF THE RETURN AIR DUCTS (FLEX)
 TO THE TWO 14X14 RETURN GRILLS IN THE MASTER BEDROOM
 AND THE HALLWAY.
  
 5) PLEASE PROVIDE RETURN AIR TO THE DINING ROOM AND
 DEN, PER 2001 FBC/M 601.4. (SEE NOTE #6).
  
 6) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.