2006-12-21 20:09:59** UNSAT **
  
 1) NOTE: PLEASE COMPLETE LOAD CALCULATIONS PER
 220.31B.
 PLEASE ALSO SEE UNDER THE MAIN HOUSE CALCULATIONS,
 THERE ARE MANY ITEMS ON OTHER PANEL SCHEDULES FOR LOADS
 WHICH ARE NOT SHOWN PART OF THE MAIN ELECTRICAL LOAD
 CALCULATIONS?
 PLEASE SEE 220.31, A/C HEAT AT 100%, PLEASE SEE 215.5
 ETC.
  
 2) NOTE: PLEASE SEE MISSING EGRESS LIGHT AND CONTROL
 FOR REAR DOOR PER 210.70.
  
 3) NOTE: PLEASE SEE MISSING REAR OUTDOOR GFI RECEPT PER
 210.52E, 210.8
  
 4) NOTE: PLEASE SEE GENERATOR PERMIT HAS NOT BEEN
 ISSUED AT THIS TIME, AND PLANS MAY NOT INDICATE THIS
 UNIT AND EQUIPMENT UNTIL SUCH TIME AS ISSUED AND SHOULD
 BE STATED ON RISER UNDER A SEPARATE PERMIT.
 FBC 106.1.2.
  
 5) NOTE: PLEASE SHOW LOCATIONS OF ELECTRICAL PANELS IN
 ADDITION IF APPLICABLE. PLANS SEEM TO SHOW WHAT APPEARS
 TO BE PANEL LOCATED IN A CLOSET/PANTRY, HOWEVER NOT
 CLEAR. ARE PANELS LOCATED IN OTHER SECTION OF MAIN
 HOUSE? 110.26, 240.24, 408.7 ETC.
  
 6) NOTE: PLEASE SEE 220.3B4 FOR RECESSED LIGHTS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS, OR COMMENTS, PLEASE CALL,
  
 DEWEY PALMER
 561-805-6717