| Plan Review Notes For Permit 04101257 |
| Permit Number |
04101257 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-11-02 15:15:13 | DENIED; | | | 1. PERSON RESPONSABLEFOR DRAWING TO SIGN, PRINT AND | | | DATE PLANS. NO PEN OR PENCIAL TO BE USED ON PLANS. | | | 2. FLOOR PLAN HAS CHANGED, A NEW FLOOR PLAN SHOULD BE | | | SUBMITED WITH AS BUILTS. | | | 3.GAS RISER DIAGRAM WAS APPROVED UNDER ARCHITECTAL PLAN | | | NOT SHOWN ON AS BUILT. | | | 4.PLUMBING AS BUILT SANITARY NOT TO CODE. AUTOMATIC | | | CLOTHES WASHER MUST DISCHARGE DOWN STREAM OF THE | | | BATHROOM GROUP. SEE SECTION | | | 909.1 WET VENT. | | | 5.SIZE ALL PIPES WATER AND SANITARY THAT ARE ON THE | | | DRAWINGS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|