| 2006-10-25 20:08:31 | ***** UNSAT ******* |
| | |
| | |
| | 1) NOTE: PLEASE SEE IN ORDER FOR THE SUB CONTRACTORS TO |
| | TAKE OVER AS DESIGNERS FOR MEP'S THE LETTER FROM THE |
| | ENGINEER MUST BE DATED WHEN SIGNED AND SEALED, MUST |
| | ALSO BE CORRECTLY NOTARIZED PER FS 117.05. |
| | PLEASE PROVIDE LETTER OF CLARIFICATION IF THE |
| | ARCHITECTURAL WILL REMAIN THE SAME AS ON RECORD SET. |
| | |
| | 2) NOTE: PLEASE SEE PLANS MAY NOT BE SUBMITTED IN |
| | PEN/PENCIL OR COLORED PEN. PLANS MUST BE AND SHALL BE |
| | SUBMITTED AS "DRAFTMANS" QUALITY AND SHALL BE DONE IN A |
| | MINIMUM OF 1/8" SCALE. PLEASE SEE THE QUALITY OF PLANS |
| | SHALL BE CLEAR AS THIS IS REQUIRED FOR ALL TRADES FOR |
| | ALL REVIEWER(S). PLEASE SEE IN NO CASE CAN PLANS BE |
| | DONE WITH "WHITE-OUT" |
| | FBC 106.1.3,106.3.5.4,FBC ADMIN SECT. |
| | |
| | 3) NOTE: PLEASE SEE THE SITE PLAN SUBMITTED IS SHOWING |
| | A NEW GEN WHICH HAS NOT BEEN PERMITTED OR APPLIED FOR |
| | UNDER THIS ADDRESS.PLEAS KNOW AT THIS TIME NO GEN IS |
| | PERMITTED AND WILL BE VERIFIED BY INSPECTOR. |
| | SUBMIT COMPLETE PACKAGE, PERMIT APPLICATION ETC FOR THE |
| | GEN. |
| | 106.1.2. |
| | |
| | 4) NOTE: PLEASE SEE MISSING FOOTER STEEL AS PART OF THE |
| | GROUNDING ELECTRODE SYSTEM AS REDLINED ON PREVIOUS |
| | PLANS AND REQUIRED FOR NEW FOOTER STEEL PER 250.50 |
| | |
| | 5) NOTE: PLEASE SEE THAT ALL PLANS CONTAINS THE PRINTED |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR SIAD |
| | PLANS/ DESIGN. |
| | |
| | 6) NOTE: PLEASE SEE ALL OF 210.8A |
| | |
| | 7) NOTE: PLEASE SEE MISSIGN RECEPTS PER 210.52C1 |
| | |
| | |
| | ** PLEASE SUBMIT ABOVE AND COMPLETE PLANS AS STATED. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |