Plan Review Notes
Plan Review Notes For Permit 04101257
Permit Number 04101257
Review Stop E
Sequence Number 4
Notes
Date Text
2006-10-25 20:08:31***** UNSAT *******
  
  
 1) NOTE: PLEASE SEE IN ORDER FOR THE SUB CONTRACTORS TO
 TAKE OVER AS DESIGNERS FOR MEP'S THE LETTER FROM THE
 ENGINEER MUST BE DATED WHEN SIGNED AND SEALED, MUST
 ALSO BE CORRECTLY NOTARIZED PER FS 117.05.
 PLEASE PROVIDE LETTER OF CLARIFICATION IF THE
 ARCHITECTURAL WILL REMAIN THE SAME AS ON RECORD SET.
  
 2) NOTE: PLEASE SEE PLANS MAY NOT BE SUBMITTED IN
 PEN/PENCIL OR COLORED PEN. PLANS MUST BE AND SHALL BE
 SUBMITTED AS "DRAFTMANS" QUALITY AND SHALL BE DONE IN A
 MINIMUM OF 1/8" SCALE. PLEASE SEE THE QUALITY OF PLANS
 SHALL BE CLEAR AS THIS IS REQUIRED FOR ALL TRADES FOR
 ALL REVIEWER(S). PLEASE SEE IN NO CASE CAN PLANS BE
 DONE WITH "WHITE-OUT"
 FBC 106.1.3,106.3.5.4,FBC ADMIN SECT.
  
 3) NOTE: PLEASE SEE THE SITE PLAN SUBMITTED IS SHOWING
 A NEW GEN WHICH HAS NOT BEEN PERMITTED OR APPLIED FOR
 UNDER THIS ADDRESS.PLEAS KNOW AT THIS TIME NO GEN IS
 PERMITTED AND WILL BE VERIFIED BY INSPECTOR.
 SUBMIT COMPLETE PACKAGE, PERMIT APPLICATION ETC FOR THE
 GEN.
 106.1.2.
  
 4) NOTE: PLEASE SEE MISSING FOOTER STEEL AS PART OF THE
 GROUNDING ELECTRODE SYSTEM AS REDLINED ON PREVIOUS
 PLANS AND REQUIRED FOR NEW FOOTER STEEL PER 250.50
  
 5) NOTE: PLEASE SEE THAT ALL PLANS CONTAINS THE PRINTED
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR SIAD
 PLANS/ DESIGN.
  
 6) NOTE: PLEASE SEE ALL OF 210.8A
  
 7) NOTE: PLEASE SEE MISSIGN RECEPTS PER 210.52C1
  
  
 ** PLEASE SUBMIT ABOVE AND COMPLETE PLANS AS STATED.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 [email protected]
 561-805-6717
  