Plan Review Notes
Plan Review Notes For Permit 04101257
Permit Number 04101257
Review Stop E
Sequence Number 2
Notes
Date Text
2005-05-10 00:00:00************* UNSAT 2ND REVIEW ********
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 THESE COMMENTS ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW.
  
 1)NOTE: NOTE #1, NO, PLEASE SEE ALL
 TITLE BLOCKS FOR ARCHITECTUAL FIRM ARE
 STILL MISSING THE REQUIRED LICENSE
 INFORMAITON AS REQUIRED UNDER FAC
 61G1-16.004 AND FS 481.219.
 ONLY THE ARCH'S AR # WAS ADDED.
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE EQUIPMENT
 GROUNDING CONDUCTORS ARE STILL SHOWN
 FROM GUTTER TO MAINS.??
 250.6,250.24
  
 5)NOTE: NOTE #5 NO, PLEASE SEE 220.4B
 FOR RECESSED LIGHTING FIXTURES.
 THESE ARE TO BE SHOWN ABOVE NORMAL
 LIGHTING LOADS.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTEL NOTE #7 OK.
  
 8)NOTE: NOTE #8 OK.
  
 9)NOTE: NOTE #9 OK, HOWEVER PLEASE SEE
 NEW NOTES FOR GROUNDING AT DEATCHED
 BLDGS NOW THAT SERVICE IS SHOWN.
  
 10)NOTE: NOTE #10 OK, FOUND INRESPONSE
 LETTER, HOWEVER RISER DIAGRAM NEEDS TO
 SHOW THIS AS LTR WILL NOT BE PART OF
 PLANS FOR INSPECTOR.
  
 11)NOTE: NOTE #11 NO, PLEASE SEE
 ADDTIONS TO EXISTING BLDGS AS SET-FORTH
 IN FBC CHAPTER 34 AS PREVIOUSLY NOTED.
 IF MAIN HOUSE IS HAS HISTORIC
 DESIGNATION, THEN MAIN HOUSE WOULD BE
 EXEMPT.
  
 12)NOTE: NOTE #12, NO, PLEASE SEE LOWER
 HALF OF SEAL ON SOME SHEETS IS STILL NOT
 COMING THROUGH COMPLETELY.
  
 13)NOTE: NOTE #13, NO RESPONSE NEEDED,
 BLDG VALUATION ADJUSTED.
  
 14)NOTE: NOTE #14, OK. PLEASE SEE THE
 SAME COMMENT WILL BE IN EFFECT THIS
 REVIEW ALSO AS SHEETS WILL BE REQUIRED
 TO BE CHANGED OUT.
  
 15)NOTE: NOTE #15 NO RESPONSE NEEDED,
 HOWEVER, PLEASE SEE ZONING COMMENTS.
  
 NEW NOTES:
  
 1)NOTE: PLEASE SEE SINCE SERVICE
 LOCATIONS ARE NOW SHOWN, PLEASE SEE
 GROUNDING ELECTRODE SYSTEM AT DEATCHED
 BLDG NEEDS TO BE SHOWN PER 250.32,
 250.50. PLEASE SHOW/INCLUDE NEW FOOTER
 STEELAND COLD WATER (IF METAL) AT
 DETACHED NEW ADDTION/HOUSE.
  
 2)NOTE: PLEASE SEE NEW GUTTER IS NOW
 SHOWN AS 14"X14'X4', PLEASE SEE THE
 MAINS ARE SHOWN ABOVE THIS EQUIPMENT.
 PLEASE SEE 110.26, GUTTER SHALL NOT
 EXTEND MORE THAN 6" FROM MAINS SHOWN.
 PLEASE SEE THIS IS A NOTE GIVEN PER
 DESIGN SHOWN.
  
 3)NOTE: PLEASE SEE KITCHEN ISLAND
 RECEPTS. GFI SERVING COUNTERSPACE MAY
 NOT EXTEND MORE THAN 6" OUT AND 6" DOWN
 TO GFI TO SERVE THAT COUNTERSPACE.
 PLEASE SEE COUNTER SHOWN.
 PLEASE ALSO SEE OTHER COUNTERSPACE WHICH
 APPEARS TO BE A PENINSULAR COUNTERSPCE
 W/OUT ANY GFI.
 PLEASE SEE 2210.52C1-5
  
 4)NOTE: PLEASE CLARIFY WHICH CIRCUITS
 ARE FEEDING OLD/ORIG HOUSE.??
 215.5
  
 5)NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND PLANS WITH REPEAT
 COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASEDO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]