Plan Review Notes
Plan Review Notes For Permit 04101257
Permit Number 04101257
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 2) ALL GAS APPLIANCES SHALL BE APPROVED
 FOR RESIDENTIAL USE ONLY. MANUFACTURE
 INSTALLATION INFORMATION WILL WILL BE
 REQUIRED AT TIME OF FINAL AND FINAL
 APPROVAL WILL BE BY THE FIELD
 INSPECTOR.
 NO COMMERCIAL GAS APPLIANCES APPROVED.
 3) SHT P.3 PLUMBING NOTES #13 AIR
 CHAMBERS ARE NOT APPROVED. DELETE
 REFERENCE. SECTION 104.2.1
 4) MINIMUM INFORMATION ON THE TITLE
 BLOCK FOR THE ARCHITECT REQUIRES THE
 FIRM LICENSE NUMBER. 61G1-16.004(2) AND
 FS 481.219
  
  
 REVIEW BY KEN STEVENS