Plan Review Notes
Plan Review Notes For Permit 04101257
Permit Number 04101257
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-18 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE INCLUDE ALL INFORMATION
 ON TITLE BLOCKS FOR ARCH FIRM AS
 REQUIRED UNDER FAC 61G1-16.004 AND FS
 481.219. THIS IS REQUIRED ON ALL SHEETS
 AND FOR ALL TRADES WHEATHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE NOE SEC'S ARE SHOWN
 ON RISER FROM METER TO GUTTER?
 310.16, 240.4, 215.5 ETC
  
 3)NOTE: PLEASE INDICATE SIZE OF METER
 CAN. 215.5
  
 4)NOTE: PLEASE SEE 250.6,250.24.
 EQUIPMENT GROUNDING CONDUCTORS ARE ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 5)NOTE: PLEASE SUBMIT COMPLETED LOAD
 CALCUALTIONS PER 220.31B
 PLEASE SHOW LT LOAD ETC.
 PLEASE SEE 220.4B4 FOR ANY RECESSED
 LTS.
  
 6)NOTE: PLEASE SEE PANEL SCHEDULE "A"
 AND AWG FOR ALL ON RIGHT-HAND SIDE.??
 MISPRINT?
  
 7)NOTE: PLEASE SEE 2002 NEC 210.12 FOR
 REQUIREMENTS OF ARC FAULT PROTECTION.
 PANEL SCHEDULE AND CIRCUITING ONLY
 INDICATES FOR RECEPTS.
 SEE 2002 NEC, WHICH REQUIRES ALL
 "OUTLETS".
  
  
 8) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 9)NOTE: PLEASE VERIFY ENTIRE SERVICE AND
 LOCATION??? PLANS SHOW SERVICE ON
 "DETACHED" GARAGE.
 PLEASE SEE PANELS IN HOUSE WOULD REQUIRE
 MAINS ETC. 225.31
 PLEASE SHOW GROUNDING PER 250.32.
  
 10)NOTE: PLEASE CLARIFY WHICH PANEL FEED
 GARAGE?
 215.5
  
 11)NOTE:PLEASE SEE FBC CHAPTER 34 FOR
 ADDITIONS TO EXISTING DWELLINGS.
 3401.7.1.2.1
 PLEASE PROVIDE COMPLETE LAYOUT OF
 EXISTING. PLEASE SHOW EITHER ALL
 EXISTING LOCATIONS FOR GFI'S AND SD'S OR
 SHOW ALL LOCATIONS TO BE "INSTALLED
 NEW". ALL SD'S ARE REQUIRED TO BE TIED
 INTO NEW SD'S IN NEW ADDITION.
 PLEASE SEE NFPA-72 8-1.4.1.6.2,8-1.4.2
 FOR LOCATIONS.
  
 12)NOTE: PLEASE BE SURE "RAISED SEAL" IS
 CLEAR AND VISABLE WITH ALL INFORMATION
 REQUIRED ON SEAL.
 FS 471.025
  
 13)NOTE: PLEASE SEE POSSIBLE BUILDING
 COMMENTS FOR VALUE.FBC 104.6.5
  
 14) NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 15)NOTE: PLEASE SEE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AFFECT ON
 ELECTRICAL PLANS.
 PLEASE SEE ZONING COMMENTS FOR REMOVAL
 OF ANY KITCHEN IN EXSITING DWELLING.
 THIS MAY BE INCLUDED ON THIS PERMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS ,
 PLEASE DO NOT HESITATE IN CONTACTING
 ME.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  