| 2004-11-18 00:00:00 | ************ UNSAT ************** |
| | |
| | 1)NOTE: PLEASE INCLUDE ALL INFORMATION |
| | ON TITLE BLOCKS FOR ARCH FIRM AS |
| | REQUIRED UNDER FAC 61G1-16.004 AND FS |
| | 481.219. THIS IS REQUIRED ON ALL SHEETS |
| | AND FOR ALL TRADES WHEATHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE SEE NOE SEC'S ARE SHOWN |
| | ON RISER FROM METER TO GUTTER? |
| | 310.16, 240.4, 215.5 ETC |
| | |
| | 3)NOTE: PLEASE INDICATE SIZE OF METER |
| | CAN. 215.5 |
| | |
| | 4)NOTE: PLEASE SEE 250.6,250.24. |
| | EQUIPMENT GROUNDING CONDUCTORS ARE ONLY |
| | INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 5)NOTE: PLEASE SUBMIT COMPLETED LOAD |
| | CALCUALTIONS PER 220.31B |
| | PLEASE SHOW LT LOAD ETC. |
| | PLEASE SEE 220.4B4 FOR ANY RECESSED |
| | LTS. |
| | |
| | 6)NOTE: PLEASE SEE PANEL SCHEDULE "A" |
| | AND AWG FOR ALL ON RIGHT-HAND SIDE.?? |
| | MISPRINT? |
| | |
| | 7)NOTE: PLEASE SEE 2002 NEC 210.12 FOR |
| | REQUIREMENTS OF ARC FAULT PROTECTION. |
| | PANEL SCHEDULE AND CIRCUITING ONLY |
| | INDICATES FOR RECEPTS. |
| | SEE 2002 NEC, WHICH REQUIRES ALL |
| | "OUTLETS". |
| | |
| | |
| | 8) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 9)NOTE: PLEASE VERIFY ENTIRE SERVICE AND |
| | LOCATION??? PLANS SHOW SERVICE ON |
| | "DETACHED" GARAGE. |
| | PLEASE SEE PANELS IN HOUSE WOULD REQUIRE |
| | MAINS ETC. 225.31 |
| | PLEASE SHOW GROUNDING PER 250.32. |
| | |
| | 10)NOTE: PLEASE CLARIFY WHICH PANEL FEED |
| | GARAGE? |
| | 215.5 |
| | |
| | 11)NOTE:PLEASE SEE FBC CHAPTER 34 FOR |
| | ADDITIONS TO EXISTING DWELLINGS. |
| | 3401.7.1.2.1 |
| | PLEASE PROVIDE COMPLETE LAYOUT OF |
| | EXISTING. PLEASE SHOW EITHER ALL |
| | EXISTING LOCATIONS FOR GFI'S AND SD'S OR |
| | SHOW ALL LOCATIONS TO BE "INSTALLED |
| | NEW". ALL SD'S ARE REQUIRED TO BE TIED |
| | INTO NEW SD'S IN NEW ADDITION. |
| | PLEASE SEE NFPA-72 8-1.4.1.6.2,8-1.4.2 |
| | FOR LOCATIONS. |
| | |
| | 12)NOTE: PLEASE BE SURE "RAISED SEAL" IS |
| | CLEAR AND VISABLE WITH ALL INFORMATION |
| | REQUIRED ON SEAL. |
| | FS 471.025 |
| | |
| | 13)NOTE: PLEASE SEE POSSIBLE BUILDING |
| | COMMENTS FOR VALUE.FBC 104.6.5 |
| | |
| | 14) NOTE: PLEASE REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | ONE SET OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | 15)NOTE: PLEASE SEE COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY HAVE AFFECT ON |
| | ELECTRICAL PLANS. |
| | PLEASE SEE ZONING COMMENTS FOR REMOVAL |
| | OF ANY KITCHEN IN EXSITING DWELLING. |
| | THIS MAY BE INCLUDED ON THIS PERMIT. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS , |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | ME. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |